Plan Review Details - Permit 14101000
Plan Review Stops For Permit 14101000
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-06 Cont ID  
Sent By jwitmer Date 2014-11-06 Time 11:58 Rev Time 0.00
Received By jwitmer Date 2014-11-06 Time 11:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-11-20 Cont ID  
Sent By dhayes Date 2014-11-20 Time 11:55 Rev Time 0.00
Received By dhayes Date 2014-11-20 Time 11:55 Sent To  
Notes
2014-11-20 13:53:3411/20/2014
 PROJECT: LOFT APTS
 PERMIT#: 14101000
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) GFP OF EQUIPMENT REQUIRED ON WYE ELECTRICAL SYSTEMS
 OF MORE THAN 150V TO GROUND AND NOT EXCEEDING 600VOLTS
 PHASE TO PHASE FOR EACH SERVICE DISCONNECT OVER
 1000AMPS. NEC230.95
  
 2) THE GROUND-FAULT PROTECTION SYSTEM SHALL BE
 PERFORMANCE TESTED WHEN FIRST INSTALLED ON SITE AND A
 RECORD OF THE TEST SHALL BE AVAILABLE FOR THE INSPECTOR
 ON SITE. NEC 230.95(C)
  
 3) THE LINE DIAGRAM INDICATE A 600AMP METER CAN AHEAD
 OF PANEL HDP. THERE ARE NO METER CAN APPROVED FOR
 600AMPS. REVISE PLANS ACCORDINGLY.
  
 4) VERIFY THE FIRE PUMP FEEDERS, CIRCUIT CONDUCTORS,
 AND PUMP WIRING ARE APPROPRIATELY FIRE PROTECTED.
 INDICATE THE FIRE RATING AND MATERIAL PROPSED. NEC
 695.6, 695.14
  
 5) VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING
 NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR,
 PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE
 ACCESSORIES. VERIFY THE MAXIMUM VOLTAGE DROP IS NOT
 MORE THAN 15 % BELOW NORMAL STARTING AND 5% BELOW WHEN
 THE MOTOR IS OPERATING AT 115% OF THE FULL LOAD CURRENT
 RATING. NEC 695.6, 695.7
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-05 Cont ID  
Sent By pleduc Date 2014-11-05 Time   Rev Time 0.00
Received By pleduc Date 2014-11-05 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-20 Cont ID  
Sent By dhayes Date 2014-11-20 Time 13:53 Rev Time 0.00
Received By dhayes Date 2014-10-30 Time 17:18 Sent To  
Notes
2014-10-31 17:18:52C10
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-11-18 Cont ID  
Sent By hmoser Date 2014-11-18 Time 14:06 Rev Time 0.00
Received By hmoser Date 2014-11-18 Time 13:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-11-19 Cont ID  
Sent By aaponte Date 2014-11-19 Time 10:29 Rev Time 0.00
Received By aaponte Date 2014-11-19 Time 10:29 Sent To  
Notes
2014-11-14 12:08:0111/14/14