Plan Review Details - Permit 14100990
Plan Review Stops For Permit 14100990
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-04-01 Cont ID  
Sent By shill Date 2015-04-01 Time 17:41 Rev Time 0.00
Received By shill Date 2015-04-01 Time 17:27 Sent To  
Notes
2015-04-01 17:35:36****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****LETTER FROM ENGINEER REQUIRED AT INSPECTION****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 2010 RESIDENTIAL 301.2.1.4.2, A GROUND SURFACE
 ROUGHNESS WITHIN EACH 45 DEGREE SECTOR SHALL BE
 DETERMINED UPWIND FOR 1500 FEET.
  
 PLEASE SEE DEFINITIONS FOR "SURFACE ROUGHNESS B" AND
 "SURFACE ROUGHNESS C." ALTHOUGH THIS APPEARS TO BE
 EXPOSURE B IN MOST DIRECTIONS, THE LARGE PARK TO THE
 NORTHWEST OF THIS PROPERTY WOULD PUT THIS IN EXPOSURE
 C.
  
 ENGINEER TO EITHER PROVIDE A LETTER STATING THAT THIS
 DESIGN COMPLIES WITH EXPOSURE C OR CONTACT ME TO
 DISCUSS OPTIONS.
  
 THE LETTER IS TO BE PROVIDED AT INSPECTION AND RETURNED
 TO THIS OFFICE BY THE FIELD INSPECTOR. IF THE INSPECTOR
 DOES NOT RETURN THE LETTER TO THIS OFFICE, THE
 CONTRACTOR IS RESPONSIBLE FOR BRINGING THE LETTER TO
 THE BUILDING DIVISION.
  
 2. A SEPARATE ELECTRICAL PERMIT IS REQUIRED. MAKE
 REFERENCE TO THIS REVISION # WHEN SUBMITTING
 APPLICATION.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-03 Cont ID  
Sent By shill Date 2015-02-03 Time 16:38 Rev Time 0.00
Received By shill Date 2015-02-03 Time 16:33 Sent To  
Notes
2015-02-03 16:36:18****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1-2. OK
  
 3. INCLUDE WIND DESIGN CRITERIA ON PLAN, FBC 2010
 RESIDENTIAL 301.
  
 4. OK
  
 5. THE CERTIFICATE OF AUTHORIZATION NUMBER FOR THE
 COMPANY IS TO BE INCLUDED IN THE TITLE BLOCK, FS471,
 FAC61G15-23.002. PLEASE INCLUDE. (NUTEK ENGINEERING,
 LLC SHOULD HAVE A LICENSE NUMBER WHICH IS REQUIRED TO
 BE ON THE PLAN).
  
 NEW COMMENT:
  
 6. THE PLANS SUBMITTED ARE POOR PHOTOCOPIES. DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED, SEALED DATED ORIGINALS FS471.
  
 7. ADVISORY (DID NOT PREVENT PERMIT FROM BEING ISSUED)
 - WHEN RESUBMITTING, PLEASE COMPLETE THE RE-SUBMITTAL
 FORM WITH ACCURATE AND COMPLETE INFORMATION. THE
 CONTRACTOR NAME WAS ABBREVIATED TO "AREI LLC";
 CONTRACTOR OF RECORD IS "AMERICAN ROOFING & EXTERIORS".
 PLEASE BE ADVISED THAT CORRECT INFORMATION HELPS OUR
 DEPARTMENT TO PROPERLY FILE AND LATER LOCATE PERMIT
 DOCUMENTS, SO YOU ARE ENCOURAGED TO INCLUDE LEGIBLE AND
 CORRECT INFORMATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-10 Cont ID  
Sent By shill Date 2014-11-10 Time 16:06 Rev Time 0.00
Received By shill Date 2014-11-10 Time 16:06 Sent To E
Notes
2014-11-10 16:35:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE THE SPECIFICATION FOR INSTALLATION IN THE
 FORM OF A PLAN. A LETTER WAS PROVIDED WITH A NARRATIVE
 DESCRIBING THE JOB AS WELL AS INFORMATION FROM THE
 INTERNET REGARDING TERRA COTTA (HOLLOW TILE). ALSO
 THERE WAS A SKETCH WHICH IS NOT ENTIRELY LEGIBLE. IT IS
 SUGGESTED TO PROVIDE A TYPED PLAN RATHER THAN SCRIPT.
 SEE FBC 107, PLANS TO BE A MINIMUM OF 1/8" SCALE,
 ARCHITECTURAL QUALITY.
  
 2. PROVIDE A PLAN SHOWING HOUSE OUTLINE AND LOCATION OF
 PROPOSED IMPROVEMENT, FBC 107.
  
 3. INCLUDE WIND DESIGN CRITERIA ON PLAN, FBC 2010
 RESIDENTIAL 301.
  
 4. ORIGINAL APPLICATION WAS TO "REPLACE WINDOW WITH
 IMPACT FRENCH DOOR IN BEDROOM HALL", SO AN ELECTRICAL
 REVIEW WAS NOT DONE. ELECTRICAL WORK IS SHOWN ON THE
 ISSUED PLAN. AS CONTRACTOR HAS NOT APPLIED FOR AN
 ELECTRICAL PERMIT, THIS WILL BE REVIEWED AT THIS TIME.
  
 5. THE CERTIFICATE OF AUTHORIZATION NUMBER FOR THE
 COMPANY IS TO BE INCLUDED IN THE TITLE BLOCK, FS471,
 FAC61G15-23.002. PLEASE INCLUDE.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-11-14 Cont ID  
Sent By dhayes Date 2014-11-14 Time 16:39 Rev Time 0.00
Received By dhayes Date 2014-11-14 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-01 Cont ID  
Sent By shill Date 2015-04-01 Time 17:41 Rev Time 0.00
Received By shill Date 2015-03-19 Time 08:48 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-03 Cont ID  
Sent By shill Date 2015-02-03 Time 16:38 Rev Time 0.00
Received By shill Date 2015-01-27 Time 10:31 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-14 Cont ID  
Sent By dhayes Date 2014-11-14 Time 16:39 Rev Time 0.00
Received By dhayes Date 2014-11-10 Time 16:35 Sent To  
Notes
2014-11-10 16:35:24TO DAH DESK
  