Plan Review Details - Permit 14100982
Plan Review Stops For Permit 14100982
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-11-06 Cont ID  
Sent By jgomez Date 2014-11-06 Time 13:20 Rev Time 0.00
Received By jgomez Date 2014-11-06 Time 13:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-30 Cont ID  
Sent By jgomez Date 2014-10-30 Time 16:16 Rev Time 0.00
Received By jgomez Date 2014-10-30 Time 13:33 Sent To  
Notes
2014-10-30 16:36:36ROOF RECOVER BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE THE RAS 117 CALCULATIONS SUBMITTED. THE
 ENGINEER NEEDS TO UTILIZE THE WITHDRAWAL RESISTANCE
 VALUE TAKEN FROM THE TESTING APPLICATION STANDARD (TAS
 105) AS REQUIRED BY LIMITATION #5.4 FROM FLORIDA
 PRODUCT APPROVAL FL16440-R2 SUBMITTED. SEC. 1609 OF
 2010 FBC.
  
 2- RECOVER INSTALLATIONS REQUIRES AN INSPECTION OF THE
 EXISTING ROOF AS REQUIRED BY LIMITATION #5.6 OF FLORIDA
 PRODUCT APPROVAL FL16440-R2. ALSO, CITY OF WEST PALM
 BEACH REQUIRES A BUILDING PRE-INSPECTION (INSPECTION
 CODE 101) ONCE THE PERMIT IS ISSUED AND BEFORE ANY WORK
 IS DONE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-06 Cont ID  
Sent By jgomez Date 2014-11-06 Time 13:19 Rev Time 0.00
Received By jgomez Date 2014-11-06 Time 13:19 Sent To  
Notes
2014-11-06 13:19:52FIRST RE-SUBMITTAL. JG.