Plan Review Details - Permit 14100967
Plan Review Stops For Permit 14100967
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-12-01 Cont ID  
Sent By rmcdouga Date 2014-12-01 Time 12:52 Rev Time 0.00
Received By rmcdouga Date 2014-12-01 Time 12:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-13 Cont ID  
Sent By rmcdouga Date 2014-11-13 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2014-11-13 Time 06:51 Sent To  
Notes
2014-11-13 09:58:47PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 THE HANDICAP ACCESSIBLE RAMP IS NOT ADA COMPLIANT. 2010
 FBC ACCESSIBILITY. ADDRESS THE FOLLOWING COMMENTS.
  
 2) SEC. 405.5 CLEAR WIDTH. THE CLEAR WIDTH OF A RAMP
 RUN AND, WHERE HANDRAILS ARE PROVIDED, THE CLEAR WIDTH
 BETWEEN HANDRAILS SHALL BE 36 INCHES (915 MM) MINIMUM.
 THE PLANS SHOW THE HANDRAILS ARE 36" FROM CENTER TO
 CENTER.
  
 3) SEC. 405.7 LANDINGS. RAMPS SHALL HAVE LANDINGS AT
 THE TOP AND THE BOTTOM OF EACH RAMP RUN. LANDINGS SHALL
 COMPLY WITH 405.7. SECTION 405.7.3 LENGTH. THE LANDING
 CLEAR LENGTH SHALL BE 60 INCHES (1525 MM) LONG MINIMUM.
 SHOW ON THE PLANS THAT THE LANDING AT THE BOTTOM OF THE
 RAMP COMPLIES.
  
 4) SEC. 405.8 HANDRAILS. RAMP RUNS WITH A RISE GREATER
 THAN 6 INCHES (150 MM) SHALL HAVE HANDRAILS COMPLYING
 WITH 505. 505.10 HANDRAIL EXTENSIONS. HANDRAIL GRIPPING
 SURFACES SHALL EXTEND BEYOND AND IN THE SAME DIRECTION
 OF STAIR FLIGHTS AND RAMP RUNS IN ACCORDANCE WITH
 505.10. 505.10.1 TOP AND BOTTOM EXTENSION AT RAMPS.
 RAMP HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE
 LANDING FOR 12 INCHES (305 MM) MINIMUM BEYOND THE TOP
 AND BOTTOM OF RAMP RUNS. EXTENSIONS SHALL RETURN TO A
 WALL, GUARD, OR THE LANDING SURFACE, OR SHALL BE
 CONTINUOUS TO THE HANDRAIL OF AN ADJACENT RAMP RUN. SEE
 FIGURE 505.10.1 TOP AND BOTTOM HANDRAIL EXTENSION AT
 RAMPS
  
 5) SEC. 405.9 EDGE PROTECTION. EDGE PROTECTION
 COMPLYING WITH 405.9.1 OR 405.9.2 SHALL BE PROVIDED ON
 EACH SIDE OF RAMP RUNS AND AT EACH SIDE OF RAMP
 LANDINGS.
 - 405.9.1 EXTENDED FLOOR OR GROUND SURFACE. THE FLOOR
 OR GROUND SURFACE OF THE RAMP RUN OR LANDING SHALL
 EXTEND 12 INCHES (305 MM) MINIMUM BEYOND THE INSIDE
 FACE OF A HANDRAIL COMPLYING WITH 505.
 - 405.9.2 CURB OR BARRIER. A CURB OR BARRIER SHALL BE
 PROVIDED THAT PREVENTS THE PASSAGE OF A 4 INCH (100 MM)
 DIAMETER SPHERE, WHERE ANY PORTION OF THE SPHERE IS
 WITHIN 4 INCHES (100 MM) OF THE FINISH FLOOR OR GROUND
 SURFACE.
  
 6) 405.10 WET CONDITIONS. LANDINGS SUBJECT TO WET
 CONDITIONS SHALL BE DESIGNED TO PREVENT THE
 ACCUMULATION OF WATER. (405.3 CROSS SLOPE. CROSS SLOPE
 OF RAMP RUNS SHALL NOT BE STEEPER THAN 1:48.)
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-11-26 Cont ID  
Sent By rmcdouga Date 2014-11-26 Time 15:57 Rev Time 0.00
Received By dhayes Date 2014-11-26 Time 15:57 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-30 Cont ID  
Sent By rmcdouga Date 2014-11-13 Time 11:10 Rev Time 0.00
Received By dhayes Date 2014-10-30 Time 10:41 Sent To  
Notes
2014-10-30 10:46:3510/30/2014
 PROJECT: RESIDENTIAL RENNOVATION
 PERMIT#: 14100967
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE ELECTRICAL PLANS OF SUFFICIENT DETAIL AND
 CLAIRITY.FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH
 WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL.
 COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW
 CIRCUITS ON FLOOR PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-01 Cont ID  
Sent By rmcdouga Date 2014-12-01 Time 12:52 Rev Time 0.00
Received By rmcdouga Date 2014-11-19 Time 07:32 Sent To  
Notes
2014-11-19 07:36:57INCOMING SENT TO D. HAYES'S DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-13 Cont ID  
Sent By rmcdouga Date 2014-11-13 Time 11:10 Rev Time 0.00
Received By rmcdouga Date 2014-10-30 Time 16:38 Sent To E
Notes
2014-10-30 10:55:26R14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-11-13 Cont ID  
Sent By rmcdouga Date 2014-11-13 Time 18:44 Rev Time 0.00
Received By rmcdouga Date 2014-11-13 Time 18:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-11-13 Cont ID  
Sent By rmcdouga Date 2014-11-13 Time 07:07 Rev Time 0.00
Received By rmcdouga Date 2014-11-13 Time 07:07 Sent To  
Notes
2014-11-13 11:09:37PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE AHRI CERTIFICATIONS OR A LETTER FROM THE
 MANUFACTURER THAT SHOWS THAT THE EXISTING AIR HANDLER
 IS COMPATIBLE WITH THE NEW CONDENSING UNIT AS REQUIRED
 BY FBC ENERGY CONSERVATION SECTION 101.4.7.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-13 Cont ID  
Sent By rmcdouga Date 2014-11-13 Time 07:07 Rev Time 0.00
Received By rmcdouga Date 2014-11-13 Time 07:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-11-10 Cont ID  
Sent By sgraham Date 2014-11-10 Time 15:37 Rev Time 0.00
Received By sgraham Date 2014-11-10 Time 15:37 Sent To  
Notes
***NONE***