 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET FP-112: THE SYSTEM PROTECTING THE TURBINE
 GENERATOR BEARING INDICATES A SINGLE INTERLOCK
 PREACTION; HOWEVER, AFTER A FIELD INSPECTION, THIS
 APPEARS TO BE DOUBLE INTERLOCK SYSTEM DUE TO A RISER
 MOUNTED AIR COMPRESSOR.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE