Plan Review Details - Permit 14100821
Plan Review Stops For Permit 14100821
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-11-15 Cont ID  
Sent By jwitmer Date 2014-11-15 Time 09:54 Rev Time 0.00
Received By jwitmer Date 2014-11-15 Time 09:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-05 Cont ID  
Sent By jwitmer Date 2014-11-05 Time 11:55 Rev Time 0.00
Received By jwitmer Date 2014-11-05 Time 10:27 Sent To  
Notes
2014-11-05 11:54:58BUILDING PLAN REVIEW
 PERMIT: 14100821
 ADD: 7477 RIVERWALK CIR.
 CONT: COLORS GROUP
 TEL: (561)762-6303
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 05/ 2014
 ACTION: DENIED
  
 1) COVERSHEET;
 1A) THE BUILDING TYPE IS LISTED AS A TYPE IIB. THIS
 STRUCTURE WAS NOT BUILT AS A TYPE IIB. ALL ROOF FRAMING
 MEMBERS AND ROOF DECKING WOULD HVE TO BEEN BUILT USING
 FIRE RETARDANT TREATED WOOD. THIS STRUCTURE IS A TYPE
 VB CONSTRUCTION. ORIGINAL PERMIT BUILT UNDER IS
 96000065 / 1991 SSBC.
  
 1B) THIS PLANS ALSO INDICATES A LEVEL 3 ALTERATION.
 2010 EXISTING BUILDING CODE 405.1 SCOPE. LEVEL 3
 ALTERATIONS APPLY WHERE THE WORK AREA EXCEEDS 50
 PERCENT OF THE AGGREGATE AREA OF THE BUILDING AND MADE
 WITHIN ANY 12-MONTH PERIOD. THE SCOPE OF WORK ON THE
 COVER SHEET DOES NOT INDICATE THE WORK AREA BEING OVER
 50% OF THE FLOOR AREA.
  
 1C) THE COVERSHEET INDICATES A NUMBER OF SEATS OF 53
 THERE ARE MORE SEATS THAT THAT, PLEASE PROVIDE THE
 OCCUPANT LOAD AS SECTION 2010 FBC-B 1004.1 DESIGN
 OCCUPANT LOAD AND TABLE 1004.1.1.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-11-13 Cont ID  
Sent By tlarge Date 2014-11-13 Time 16:53 Rev Time 0.00
Received By dhayes Date 2014-11-13 Time 16:53 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-03 Cont ID  
Sent By dhayes Date 2014-11-03 Time 13:40 Rev Time 0.00
Received By dhayes Date 2014-11-03 Time 13:40 Sent To  
Notes
2014-11-03 15:36:1911/3/2014
 PROJECT: CAFE REMODEL
 PERMIT#: 14100821
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A LOAD CALCULATION FOR THE NEW PANEL "K" AND
 FOR THE ELECTRICAL SERVICE THAT FEEDS IT.
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) PROVIDE THE DESCRIPTION FOR THE SYMBOL THAT IS A
 SQUARE WITH THE LETTER T INSIDE IT. ASSUMING IT IS FOR
 A TELEVISION CATV OUTLET PROVIDE ADDITIONAL DETAILED
 INFORMATION ABOUT WHAT IT PROPSED TO FEED THESE OUTLET
 LOCATIONS AND FROM WHERE
  
 4) PROVIDE MORE DETAILED INFORMATION FOR THE CIRCUITS
 THAT ARE BEING DEMO'D IN CAFE AREA.
  
 5) PROVIDE MORE DETAILED INFORMATION FOR THE CIRCUITS
 ASSOCIATED WITH AND UNDER THE HOOD. THERE ARE SHUNT
 TRIP CIRCUITS IDENTIFIED IN THE PANEL SCHEDULE "K"
 PROVIDE ADDITIONAL INFORMATION ON HOW AND WHAT IS
 PROPOSED TO FEED AND TRIP THE SHUNT TRIP CIRCUIT
 BREAKERS. CLARIFY THE USE OF CIRCUIT K5 AND K7
  
 6) PROVIDE MORE DETAILED INFORMATION ON THE ELECTRICAL
 PLANS AN THE RELOCATED WATER HEATER. IDENTIFY THE
 CIRCUIT FEEDING IT ON THE FLOOR PLAN AND PANELSCHEDULE.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR HOOD, FIRE SUPRESSION SYSTEM.
 SECURITY, CCTV, AUDIO VIDEO, AND NETWORK, COMMUNICATION
 AND POS..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-03 Cont ID  
Sent By scaldero Date 2014-11-03 Time 11:22 Rev Time 0.00
Received By scaldero Date 2014-11-03 Time 11:22 Sent To  
Notes
2014-11-03 11:24:19PERMIT # 14100821
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISO:
 APPROVAL OF PERMIT DOES NOT INLCUDE APPROVAL OF
 FURNITURE LAYOUT, SEATING PLAN, OR OCCUPANCY LOAD.
 THESE ITEMS TO BE REVIEWED BY FIELD INSPECTOR AND FINAL
 APPROVAL GIVEN AT TIME OF FIELD INSPECTION.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-17 Cont ID  
Sent By tklarge Date 2014-11-17 Time 04:04 Rev Time 0.00
Received By tklarge Date 2014-11-13 Time 16:57 Sent To  
Notes
2014-11-13 16:57:23B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-05 Cont ID  
Sent By skennedy Date 2014-11-05 Time 15:14 Rev Time 0.00
Received By skennedy Date 2014-10-27 Time 13:30 Sent To  
Notes
2014-10-28 13:31:28EXPEDITED!!!! INCOMING SENT TO C-09. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-10-28 Cont ID  
Sent By jwitmer Date 2014-10-28 Time 13:31 Rev Time 0.00
Received By jwitmer Date 2014-10-28 Time 13:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-10-30 Cont ID  
Sent By hmoser Date 2014-10-30 Time 13:43 Rev Time 0.00
Received By hmoser Date 2014-10-30 Time 13:37 Sent To  
Notes
2014-10-30 13:44:41NO MECHANICAL WORK AT THIS TIME HM.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-11-17 Cont ID  
Sent By tklarge Date 2014-11-17 Time 04:04 Rev Time 0.00
Received By tklarge Date 2014-11-17 Time 03:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By tklarge Date 2014-11-07 Time 09:44 Rev Time 0.00
Received By tklarge Date 2014-11-05 Time 10:03 Sent To  
Notes
2014-11-05 10:16:351) COVER SHEET - SCOPE OF WORK ( ARCH. NOTES) - NOTE #
 7 STATES "REPLACE EXISTING 3 - COMPARTMENT SINK... AND
 NOTE #8 STATES "REMOVE 3 COMPARTMENT SINK" AND UNDER
 THE PLUMBING NOTES IT STATES "RELOCATE EXISTING 3
 COMPARTMENT SINK W/NEW." ON SHT.1.0A UNDER CONSTRUCTION
 NOTES #8 THE SCOPE OF WORK IS SOMEWHAT DIFFERENT. IT IS
 DIFFICULT TO DECIPHER EXACTLY WHAT IS BEING DONE WITH
 THE 3 COMPARTMENT SINK. CLEAN UP THE NOTES AND DESCRIBE
 EXACTLY THE SCOPE OF WORK TO BE DONE. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 2) SHT. 3.1 P SHOWS A SINK IN AN EXISITING SPACE AS
 BEING EXISTING BUT IT IS NOT SHOWN ON THE EXISTING
 FLOOR PLAN. CLARIFY.
 3) SUBMIT A WATER RISER FOR REVIEW. WPB AMENDMENTS TO
 2010 FBC SEC. 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-11-05 Cont ID  
Sent By sgraham Date 2014-11-05 Time 14:53 Rev Time 0.00
Received By sgraham Date 2014-11-05 Time 14:53 Sent To B
Notes
***NONE***