Plan Review Details - Permit 14100819
Plan Review Stops For Permit 14100819
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By jwitmer Date 2014-12-19 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2014-12-19 Time 07:06 Sent To  
Notes
2014-12-22 08:46:54 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-05 Cont ID  
Sent By jwitmer Date 2014-11-05 Time 09:50 Rev Time 0.00
Received By jwitmer Date 2014-11-05 Time 09:33 Sent To  
Notes
2014-11-05 09:49:59BUILDING PLAN REVIEW
 PERMIT: 14100819
 ADD: 533 CLEMATIS ST.
 CONT: SULLIVAN
 TEL: (561)305-1465
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 05/ 2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 107.2.1.ADDITIONAL INFORMATION IS REQUIRED.
 THE PERMIT APPLICATION INDICATES THIS TO BE INTERIOR
 DEMO ONLY OF A BAR, FOR A VALUE OF $15,000.00. NO
 DEMOLITON PLANS WERE SUBMITTED.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) COVERSHEET CODE ANALYSIS:
 2A) TYPE V, SPRINKLERED, PLEASE IDENTIFY IF THIS IS A
 VA OR VB BUILDING TYPE. 2010 FBC-B TABLE 503.
 2B) OCCUPANCY CLASSIFICATION A2 SMALL ASSEMBLY, THIS IS
 OLD CODE LANGUAGE, A A2 OCCUPANCY IS NIGHTCLUBS,
 RESTAURANTS, ETC
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-23 Cont ID  
Sent By dhayes Date 2014-12-23 Time 09:09 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 15:20 Sent To  
Notes
2014-12-23 09:08:5712/23/2014
 PROJECT: 533 CLEMATIS
 PERMIT#: 14100819
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) PROVIDE AS BUILT WITH AN ELECTRICAL LIGHTING PLANS
 INDICATING THE DUAL VOTAGE EMERGENCY AND EXIT LIGHTING
 FOR THE REQUIRED ILLUMINATED MEANS OF EGRESS,
 STAIRWARYS, LIGHTING FOR ELECTRICAL PANELS, TASK
 LIGHTING, AND GENERAL LIGHTING. INDICATE HOW CIRCUITRY
 IS INSTALLED FOR CONTROL OF NEW AND EXISTING LIGHTING.
 INDICATE WHAT IS EXISTING TO REMAIN AND WHAT IS
 PROPOSED TO BE NEW. NEC 700.16, 700.12(F), NFPA 101
 7.8.1.1*
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, NETWORK, DATA, AND, COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-26 Cont ID  
Sent By dhayes Date 2014-11-26 Time 15:06 Rev Time 0.00
Received By dhayes Date 2014-11-26 Time 12:13 Sent To  
Notes
2014-11-26 15:06:3111/26/2014
 PROJECT: 533 CLEMATIS
 PERMIT#: 14100819
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE PANEL SCHEDULE FOR PANEL KI AND MDP CIRCUITS
 IN OFFICE AS BATHROOM AND LOAD CALCULATION AND THERE IS
 NO CIRCUIT IN MDP INDICATED FOR SUB-PANEL K2.. EVERY
 CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4 REVISE PANEL SCHEDULE AND
 LOAD CALCULATION FOR PANEL MDP.
  
 2) REVISE RISER DIAGRAM FOR CLARITY AND ACCURACY. THE
 RISER DIAGRAM INDICATE A 250AMP PANEL K1 BEING FED FROM
 PANEL MDP WITH 4, #4/0 AND 1,#8 #6 AND A 225AMP PANEL
 K2 BEING FED FROM PANEL MDP WITH 4,#3 AND 1,#8. NONE OF
 THIS IS ADAQUATE TO SUPPORT THE LOAD PROPOSED TO BE
 FED. NEC 310.16
  
 3) CLARIFY THE SCOPE OF WORK. THE DESCRIPTION OF WORK
 ON THE APPLICATION AND ON THE PLAN ARE CONFLICTING.
 CLARIFY WHAT THE ACTUAL SCOPE OF WORK IS AND WHAT IS
 EXISTING TO REMAIN, WHAT IS PROPOSED TO RENOVATED AND
 WHAT IS TO BE INSTALLED NEW.
  
 4) THE RISER DIAGRAM ON SHEET 2.1E STATES "ALL APNELS
 AND SERVICES ARE EXISTING" YET THE RISER DIAGRAM ITSELF
 INDICATES A NEW SERVICE FOR THE RESTAURANT. A NEW
 400AMP MAIN, FEEDER MDP, K1 & K2,
  
 5) THERE IS REFERENCE TO NOTES ON SHEET 2.1E BUT THERE
 ARE NO NOTES. THERE ARE ALSO TWO SHEETS #2.1E CLARIFY.
  
 6) THERE IS A REFLECTED CEILING PLAN BUT THERE IS NO
 ELECTRICAL LIGHTING PLAN. PROVIDE ELECTRICAL LIGHTING
 PLANS INDICATING HOW THE LIGHTING IS PROPOSED TO BE
 CONTROLED. CLARIFY
  
 THERE IS A NOTE ON SHEET 2.1E THAT STATES
 "RECIRCULATING PUMPS CEILING SPACE MOUNTED" BUT THERE
 IS NO CIRCUITRY OR CONTROLS INVOLOVING ANY
 RECIRCULATING PUMPS. CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-16 Cont ID  
Sent By pleduc Date 2014-12-16 Time   Rev Time 0.00
Received By pleduc Date 2014-12-16 Time 11:10 Sent To  
Notes
2014-12-16 12:11:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE FOLLOWING COMMENTS HAVE BEEN RE-COMMENTED FROM THE
 FIRST REVIEW DUE TO A CLOUDED STATEMENT ON THE FIRST
 SHEET "KEY PLAN" THAT STATES "THIS SPACE SHALL BE
 SPRINKLERED UNDER THIS PERMIT" ALL FIRE ALARM AND FIRE
 SPRINKLER WORK SHALL BE SUBMITTED AND APPROVED THROUGH
 SEPARATE SHOP DRAWINGS.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-29 Cont ID  
Sent By pleduc Date 2014-10-29 Time   Rev Time 0.00
Received By pleduc Date 2014-10-29 Time 13:51 Sent To  
Notes
2014-10-29 14:02:22THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-10-27 Cont ID  
Sent By fmittner Date 2014-10-27 Time 11:45 Rev Time 0.00
Received By fmittner Date 2014-10-27 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-23 Cont ID  
Sent By dhayes Date 2014-12-23 Time 09:11 Rev Time 0.00
Received By dhayes Date 2014-12-15 Time 18:10 Sent To  
Notes
2014-12-15 18:15:10B30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-26 Cont ID  
Sent By dhayes Date 2014-11-26 Time 15:06 Rev Time 0.00
Received By dhayes Date 2014-10-27 Time 11:21 Sent To  
Notes
2014-10-28 11:21:33B-10

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By tklarge Date 2014-12-19 Time 05:28 Rev Time 0.00
Received By tklarge Date 2014-12-19 Time 04:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-02 Cont ID  
Sent By tklarge Date 2014-11-02 Time 08:42 Rev Time 0.00
Received By tklarge Date 2014-11-02 Time 08:42 Sent To  
Notes
2014-11-02 08:49:271) THE KEY PLAN NOTES THAT THE RESTROOMS AND KITCHEN
 ARE EXISTING TO REMAIN YET THE LEGEND ON SHT.1.0A SHOWS
 THE PARTITIONS AROUND THE RESTROOM AND KITCHEN AS NEW.
 CLARIFY.
 2) SHT.3.0A SHOWS NEW PLUMBING THROUGHOUT THE AREA
 TYING INTO THE EXISTING. CLARIFY. THIS SHEET ALSO HAS
 NOTES THAT READ "SEE DETAIL 19" & CIRCLED NUMBERS THAT
 REFER TO DEMOLITION NOTES. AND THERE ARE NO DEMOLITION
 NOTES OR NUMBER NOTES ON THIS SHEET. CLARIFY.
 WPB AMEND. TO FBC SEC. 107.2.1.
 3) SHT. 1.1A - INDICATE THE CONNECTION POINT OF THE
 "NEW PLUMBING" TO THE EXISTING SYSTEM (SANITARY OR
 GREASE). WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  