| 2014-10-25 07:56:54 | PLAN REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVAL FOR THE 3M, AH160 ROOF TILE | | | ADHESIVE NOA NO. 13-0502.02 HAS BEEN SUPERSEDED BY NOA | | | NO. 14-0805.01. SUBMIT TWO COPIES OF THE CURRENT | | | PRODUCT APPROVAL. DCA RULE 9N-3. THE CURRENT NOA CAN BE | | | FOUND ON THE FOLLOWING WEBSITE. | | | HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP | | | | | | 2) SUBMIT TWO COPIES OF A ROOF DIAGRAM THAT SHOWS THE | | | THE LOCATION OF THE TWO SKYLIGHTS IN RELATION TO THE | | | ROOF ZONES. THE MAXIMUM DESIGN PRESSURES ARE SUCH THAT | | | THEY CAN NOT BE LOCATED IN THE CORNER AREAS (ROOF ZONE | | | 3). FBC R301.1 |
|
|
|