| 2014-10-24 13:22:19 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. PLAN DOES NOT INDICATE WHETHER EXIT DOORS OR ONLY |
| | WINDOWS ARE TO BE COVERED BY SHUTTERS. REVISE PLAN TO |
| | INDICATE. |
| | |
| | 2. IF DOORS ARE AFFECTED, PROVIDE A FLOOR PLAN SHOWING |
| | EXITING INCLUDING ALL EXITS, OVERALL BUILDING SIZE, |
| | BASIC FLOOR PLAN. THIS MAY BE SENT FOR PRELMINIARY |
| | REVIEW VIA EMAIL. |
| | |
| | SEE FBC 1003.6. HURRICANE SHUTTERS OVER EXIT DOORS ARE |
| | CONSIDERED ON A CASE BY CASE BASIS AS THERE IS NO |
| | PROVISION IN THE BUILDING CODE FOR THIS APPLICATION. |
| | |
| | FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF |
| | EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE |
| | INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS |
| | OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER. |
| | OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH |
| | OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY |
| | THIS CHAPTER. |
| | |
| | 1008.1.4.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S, |
| | HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE |
| | PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM |
| | THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL |
| | KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS |
| | OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE |
| | FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY |
| | THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS |
| | ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR |
| | EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL |
| | SLIDING OR VERTICAL SECURITY GRILLES. |
| | |