Plan Review Details - Permit 14100749
Plan Review Stops For Permit 14100749
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-11-13 Cont ID  
Sent By dhayes Date 2014-11-13 Time 15:43 Rev Time 0.00
Received By dhayes Date 2014-11-13 Time 15:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-27 Cont ID  
Sent By dhayes Date 2014-10-27 Time 15:47 Rev Time 0.00
Received By dhayes Date 2014-10-27 Time 15:47 Sent To Z
Notes
2014-10-27 15:51:0410/27/2014
 PROJECT: PARKING LOT LIGHTING
 PERMIT#: 14100749
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) PROVIDE WIND LOAD CALCULATIONS IN ACCORDANCE WITH
 THE FBC CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE
 PROVISIONS OF THE ALTERNATE ALL HEIGHTS METHOD IN FBC
 SECTION 1609.6 TO INCLUDE THE POLE WITH THE LUMINAIRE
 INSTALLED. .
  
 2) FBC-ENERGY 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 3) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY. SUITABILITY FOR
 INSTALLATION AND USE IN CONFORMITY WITH THE PROVISIONS
 OF THIS CODE. NEC 110.3(B)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-13 Cont ID  
Sent By dhayes Date 2014-11-13 Time 15:42 Rev Time 0.00
Received By dhayes Date 2014-11-13 Time 15:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-29 Cont ID  
Sent By dkittred Date 2014-10-29 Time 08:08 Rev Time 0.00
Received By dkittred Date 2014-10-23 Time 13:30 Sent To  
Notes
2014-10-23 13:30:26ROUTED TO ELECTRICAL

Review Stop Z ZONING
Rev No 1 Status P Date 2014-10-29 Cont ID  
Sent By dkittred Date 2014-10-29 Time 08:08 Rev Time 0.00
Received By dkittred Date 2014-10-29 Time 08:04 Sent To  
Notes
***NONE***