Plan Review Details - Permit 14100698
Plan Review Stops For Permit 14100698
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-02 Cont ID  
Sent By jwitmer Date 2014-12-16 Time 14:39 Rev Time 0.00
Received By skennedy Date 2014-12-16 Time 12:05 Sent To  
Notes
2015-01-02 09:36:45REVIEW BY JWITMER.
2014-12-16 14:26:41BUILDING PLAN REVIEW
 PERMIT: 1410069
 ADD: 222 LAKEVIEW SUITE # 300
 CONT: GREEN CONSTRUCTION
 TEL: (305) 670-1000
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. DEC. 16/2014
 ACTION: BUILDING PROVISO
  
 NOTICE: THE PERMIT APPLICATION UNDER DISCREPTION OF
 WORK: TYPED SUITE 300/ HAND WRITTEN 1ST FLOOR BUILD
 OUT, THIS REVIEW WILL BE FOR A 3RD FLOOR BUILDOUT AS
 STATED ON PLANS.
  
  
 PERMIT # 14081026 FOR ELEVATORS/ SHAFTS
 & PRESSURIZATION OF SHAFT
  
 BLDG. PROVISO:
  
 PRIVATE RESTROOM # 355:
  
 2010 FL ACCESS. CODE 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
  
 2010 FL. ACCESS. CODE 609.8 STRUCTURAL STRENGTH.
 ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS
 USED WHEN A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS
 (1112 N) IS APPLIED AT ANY POINT ON THE GRAB BAR,
 FASTENER, MOUNTING DEVICE, OR SUPPORTING STRUCTURE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-17 Cont ID  
Sent By jwitmer Date 2014-11-17 Time 13:51 Rev Time 0.00
Received By jwitmer Date 2014-11-17 Time 11:56 Sent To  
Notes
2014-11-17 12:28:54BUILDING PLAN REVIEW
 PERMIT: 1410069
 ADD: 222 LAKEVIEW SUITE # 300
 CONT: GREEN CONSTRUCTION
 TEL: (305) 670-1000
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 17/2014
 ACTION: DENIED
  
 NOTICE: THE PERMIT APPLICATION UNDER DISCREPTION OF
 WORK: TYPED SUITE 300/ HAND WRITTEN 1ST FLOOR BUILD
 OUT, THIS REVIEW WILL BE FORE A 3RD FLOOR BUILDOUT AS
 STATED ON PLANS.
  
  
 1) SHEET A-04:
 !A) IT ROOM # 345 PLEASE PROVIDE WHAT THE CLEAR
 UNOBSTRUCKED SWING OF THE DOOR? SHOW COMPLIANCE WITH
 2010 FBC-B 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE
 HALF OF THE REQUIRED WIDTH OF A CORRIDOR, PASSAGEWAY,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF A CORRIDOR OR PASSAGEWAY, WHEN FULLY
 OPEN.
  
 1B) THE EXECUTIVE OFFICE # 367 THE CORRIDOR DOES NOT
 PROVIDE WHAT THE REDUCED WIDTH IS IN THE NEW OFFICESITE
 THAT IS PROVIDED. COORIDORS WITH OCCUPANT LOADS GREATER
 THAN 44 INCHES, 2010 FBC-B 1018.2 .
  
 1C)(1) PRIVATE RESTROOM # 355 PLEASE PROVIDE COMPLIANCE
 WITH 2010 FBC-ACCESSIBILITY CODE 213.2 TOILET ROOMS AND
 BATHING ROOMS. WHERE TOILET ROOMS ARE PROVIDED, EACH
 TOILET ROOM SHALL COMPLY WITH 603. 603.2.1 TURNING
 SPACE. TURNING SPACE COMPLYING WITH 304 SHALL BE
 PROVIDED WITHIN THE ROOM.
  
 1C)(2) PLEASE SHOW COMPLIANCE ALSO WITH ACCESS. CODE
 604.3.2 OVERLAP. THE REQUIRED CLEARANCE AROUND THE
 WATER CLOSET SHALL BE PERMITTED TO OVERLAP THE WATER
 CLOSET, ASSOCIATED GRAB BARS, DISPENSERS, SANITARY
 NAPKIN DISPOSAL UNITS, COAT HOOKS, SHELVES, ACCESSIBLE
 ROUTES, CLEAR FLOOR SPACE AND CLEARANCES REQUIRED AT
 OTHER FIXTURES, AND THE TURNING SPACE. NO OTHER
 FIXTURES OR OBSTRUCTIONS SHALL BE LOCATED WITHIN THE
 REQUIRED WATER CLOSET CLEARANCE.
  
 1C)(3) THE PLANS DO NOT PROVIDE DETAILS FOR BACKING
 2010 FBC- ACCESS. CODE 609.
  
 1C)(4) IF A INSWING DOOR IS TO BE INSTALLED PLEASE SHOW
 COMPLYANCE WITH ACCESS. CODE 603.2.3 DOOR SWING. ECEP.
 # 2 WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE.
  
 1D) SHEET A-04 BOTH KITCHENETTES 336 & 350 APPEAR TO BE
 MISMARKED DETAIL IS SHOWN AS DETAIL # 3/ A-09 WHERE AS
 SHEET A-07.5 SHOWS THE CORRECT DETAIL. DISCREPANCY IN
 PLANS. 107.2.1.3.
  
 1E) THE (2) NEW ELEVATORS THAT ARE NOT PART OF THIS
 CONTRACT WILL EFFECT THE OUTCOME OF THIS PROJECT,
 PLEASE INDICATE HOW COMPLIANCE WITH FBC-B 708.14.1
 ELEVATOR LOBBIES OR A EXCEPTION WILL BE COMPLIED WITH.
  
 2) SHEET A-07.6 DETAIL 6 SHOWS A RAMP AND RAISED
 PLATFORM. NOTE THIS IS A HIGH-RISE AND MUST MEET
 COMPLIANCE WITH 2010 FBC-B 603.1. 410.4 PLATFORM
 CONSTRUCTION.
 PERMANENT PLATFORMS SHALL BE CONSTRUCTED OF MATERIALS
 AS REQUIRED FOR THE TYPE OF CONSTRUCTION OF THE
 BUILDING IN WHICH THE PERMANENT PLATFORM IS LOCATED.
 PERMANENT PLATFORMS ARE PERMITTED TO BE CONSTRUCTED OF
 FIRE-RETARDANT-TREATED WOOD FOR TYPES I, II AND IV
 CONSTRUCTION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By dhayes Date 2014-12-19 Time 14:36 Rev Time 0.00
Received By dhayes Date 2014-12-19 Time 14:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-24 Cont ID  
Sent By dhayes Date 2014-10-24 Time 09:26 Rev Time 0.00
Received By dhayes Date 2014-10-24 Time 09:26 Sent To  
Notes
2014-10-24 09:57:0410/24/2014
 PROJECT: INTERIOR BUILDOUT. SUITE 1400
 PERMIT#: 14100698
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) INDICATE LOCATIONS FOR ELECTRICAL SERVICE AND
 PANELBOARDS ILLUSTRATED ON SINGLE LINE RISER DIAGRAM ON
 SHEETE3.1.
  
 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 3) A SEPARATE SUBMITTAL WITH SHOP DRAWINGS AND PRODUCT
 DATA SHEETS FOR ACCESS CONTROL AND FIRE ALARM SYSTEMS.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-12-17 Cont ID  
Sent By pleduc Date 2014-12-17 Time   Rev Time 0.00
Received By pleduc Date 2014-12-16 Time 17:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-23 Cont ID  
Sent By pleduc Date 2014-10-23 Time   Rev Time 0.00
Received By pleduc Date 2014-10-23 Time 14:17 Sent To  
Notes
2014-10-23 14:33:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 A LIFE SAFETY PLAN WAS NOT INCLUDED WITH THE SUBMITTAL.
 THE LIFE SAFETY PLAN SHALL INCLUDE, BUT NOT LIMITED TO,
 THE PROPOSED OCCUPANCY LOAD, ALL EXIT PATHS, EXIT
 SIGNS, EXITS, EMERGENCY LIGHTS, COMMON PATHS OF TRAVEL,
 TRAVEL DISTANCES, FIRE EXTINGUISHER LOCATIONS.
  
 SHEET A - 04 INDICATED A WALL ENCROACHMENT INTO THE
 HALLWAY AT THE EXECUTIVE OFFICE 367, LOCATION. THE
 REDUCED HALL DIMENSION IS NOT INDICATED AND THE REDUCED
 HALL IS NOT APPROVED. IT IS RECOMMENDED THAT THE WALL
 BE MOVED INTO THE ROOM TO MAINTAIN THE HALLWAY
 DIMENSION(AS HAND DRAWN ON ONE OF THE SHEETS).
  
 SHEET A - 04, THE DOOR TO CLOSET 345 INDICATES IT
 SWINGS IN TO CORRIDOR. THE DOOR CAN NOT SWING INTO MORE
 THAN 1/2 THE CORRIDOR WIDTH AND IS NOT APPROVED.
  
 SHEET A - 01, INDICATES THAT A FIRE ALARM WILL BE
 INSTALLED; HOWEVER, NO FIRE ALARM PLANS ARE INCLUDED.
 AN ENGINEERED FIRE ALARM PLAN SHALL BE SUBMITTED WITH
 THIS PLAN AND SHOP DRAWINGS SUBMITTED BY THE INSTALLING
 CONTRACTOR.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-31 Cont ID  
Sent By hmoser Date 2014-12-31 Time 14:38 Rev Time 0.00
Received By hmoser Date 2014-12-09 Time 17:13 Sent To  
Notes
2014-12-10 17:14:28INCOMING SENT TO B27.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-17 Cont ID  
Sent By jwitmer Date 2014-11-17 Time 13:51 Rev Time 0.00
Received By jwitmer Date 2014-10-22 Time 17:16 Sent To  
Notes
2014-10-22 17:17:04B17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-12-31 Cont ID  
Sent By hmoser Date 2014-12-31 Time 14:38 Rev Time 0.00
Received By hmoser Date 2014-12-31 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-11-04 Cont ID  
Sent By hmoser Date 2014-11-04 Time 15:45 Rev Time 0.00
Received By hmoser Date 2014-11-04 Time 15:07 Sent To  
Notes
2014-11-04 15:45:18PASS PROVISO
 REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROL
 FLORIDA ENERGY CODE 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-20 Cont ID  
Sent By tklarge Date 2014-12-20 Time 05:58 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 05:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-02 Cont ID  
Sent By tklarge Date 2014-11-02 Time 03:21 Rev Time 0.00
Received By tklarge Date 2014-11-02 Time 02:36 Sent To  
Notes
2014-11-02 03:21:471) RM. 355 - THE TOILET ROOM SHALL COMPLY WITH THE 2010
 FL. ACCESSIBILITY CODE SECS.213.2 , 603 & 305. SHOW THE
 REQUIRED TURNING SPACE WITHIN THE TOILET ROOM IN
 ACCORDANCE W/ SEC.304.3.OF 2010 FAC. SHOW THE REQUIRED
 CLEAR FLOOR SPACE FOR THE WATER CLOSET AND THE
 LAVATORY. THE CLEARANCE FOR THE WATER CLOSET SHALL
 COMPLY W/FAC SEC.604.3.
 2) BACKING FOR THE GRSB BARS SHALL BE INSTALLED PER FAC
 SEC. 604.5.
 3) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATION
 SHEETS AND INSTALLATION MANUAL PER THE WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 4) SHOCK ARRESTORS SHALL BE INSTALLED ON THE WATER
 LINES TO THE REFRIGERATORS PER 2010 FL. PLUMBING CODE
 SEC.604.9.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  