Plan Review Details - Permit 14100681
Plan Review Stops For Permit 14100681
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 10:19 Rev Time 0.00
Received By skennedy Date 2015-02-15 Time 10:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-22 Cont ID  
Sent By skennedy Date 2014-11-22 Time 16:13 Rev Time 0.00
Received By skennedy Date 2014-11-22 Time 16:13 Sent To  
Notes
2014-11-22 16:18:041ST REVIEW: FBC 2010
  
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16; INCLUDE WIND
 SPEED, EXPOSURE, & RISK CATAGORY.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-13 Cont ID  
Sent By Misc2 Date 2015-02-13 Time 14:03 Rev Time 0.00
Received By dhayes Date 2015-02-13 Time 13:45 Sent To B
Notes
2015-02-13 14:26:30APPROVED WITH EXCEPTION. SEE PROVISO FOR COMPLIANCE:
  
 1) NEC 600.3 LISTING.
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING
 SHALL BE LISTED AND INSTALLED IN CONFORMANCE WITH THAT
 LISTING, UNLESS OTHERWISE APPROVED BY SPECIAL
 PERMISSION.
  
 2) NEC 600.6(A)(1) DISCONNECT
 EACH SIGN OR BRANCH CIRCUIT SUPPLYING A SIGN, SHALL BE
 CONTROLLED BY AN EXTERNALLY OPERABLE SWITCH OR CIRCUIT
 BREAKER THAT WILL OPEN ALL UNGROUNDED CONDUCTORS WITHIN
 SIGHT OF THE SIGN.
  
 3) FBC-E 505.2.4 CONTROL
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A PHOTOSENSOR AND A TIME
 SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING DURING LOSS OF POWER FOR A PERIOD
 OF AT LEAST 10 HOURS.
  
 4) WPB AMENDMENTS. FBC SECTION 109.3 VALUATION
 PROVIDE PROOF OF OVERALL VALUE OF THE PROJECT IS
 REQUIRED AND SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE ARCHITECTURAL DESIGN FEES, FABRICATION,
 STRUCTURAL, AND ELECTRICAL, PLUS OVERHEAD AND PROFIT.
 FINAL PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-21 Cont ID  
Sent By dhayes Date 2014-11-21 Time 13:06 Rev Time 0.00
Received By dhayes Date 2014-11-21 Time 13:03 Sent To B
Notes
2014-11-21 13:23:58ROUTED TO MISC. 2
  
 11/21/2014
 PROJECT: MARATHON SIGN
 PERMIT#: 14100681
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WPB AMENDMENTS TO FBC 107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. THE INFORMATION AT THE TOP OF SHEET C2.0
 ABOVE THE MARATHON SIGN IS NOT LEGIBLE.
  
 2) NEC 600.3 AND 11O.3(B)
 ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ?
 FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. PROVIDE THE
 LISTING INFORMATION FOR THE SIGN AS A WHOLE AND FOR THE
 DRIVERS TO BE INSTALLED FOR OPERATION OF THE LED'S
  
 3) NEC 600.6(A)(1)
 EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN OR
 OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. INDICATE OM
 THE PLANS WHERE AND HOW THE PROPOSED INSTALLATION WILL
 CONFORM TO THE NEC 600.6
  
 4) FBC-E 505.2.4
 ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL
 HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN
 NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME
 CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES
 SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS
 OF POWER FOR A MINIMUM OF 10 HOURS. INDICATE ON THE
 PLAN HOW THE COMPLETED INSTALLATION WILL COMPLY WITH
 THE FBC-E 505.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-15 Cont ID  
Sent By skennedy Date 2015-02-15 Time 10:19 Rev Time 0.00
Received By skennedy Date 2015-01-28 Time 12:26 Sent To  
Notes
2015-01-29 12:26:52TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-22 Cont ID  
Sent By skennedy Date 2014-11-22 Time 16:13 Rev Time 0.00
Received By skennedy Date 2014-10-22 Time 10:43 Sent To  
Notes
2014-10-23 10:36:21TO ZONING
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-02-12 Cont ID  
Sent By eschneid Date 2015-02-12 Time 18:22 Rev Time 0.25
Received By eschneid Date 2015-02-12 Time 18:22 Sent To E
Notes
2015-02-12 18:25:04 
  
 NORTH (FRONT) FACADE
  
 PERMITTED: 35.4 SQ. FT.
 PROPOSED MARATHON LETTERS: 7.75 SQ. FT.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-11-14 Cont ID  
Sent By eschneid Date 2014-11-14 Time 08:27 Rev Time 0.75
Received By eschneid Date 2014-11-14 Time 08:27 Sent To E
Notes
2014-11-14 10:17:30FAILED
  
 NORTH (FRONT) FACADE
  
 PERMITTED: 35.4 SQ. FT.
 PROPOSED MARATHON LETTERS: 8.07 SQ. FT.
 PROPOSED BRANDING DECALS: UNABLE TO DETERMINE, BUT
 APPEARS TO CONTAIN AT LEAST 200 SQ. FT.
  
 1) THE BRANDING DECALS ARE SIGNAGE AND MAY NOT BE
 INSTALLED THE ENTIRE LENGTH OF THE FASCIA.
  
 EAST (SIDE) FACADE
  
 PERMITTED: 7.2 SQ. FT.
 PROPOSED MARATHON LETTERS: 8.07 SQ. FT.
 PROPOSED BRANDING DECALS: UNABLE TO DETERMINE, BUT
 APPEARS TO CONTAIN AT LEAST 40 SQ. FT.
  
 2) THE PROPOSED MARATHON SIGN EXCEEDS THE PREMITTED
 SIGNAGE.
  
 3) THE BRANDING DECALS ARE SIGNAGE AND EXCEED THE
 PERMITTED SIGNAGE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.