| 2014-11-08 07:49:45 | BUILDING PLAN REVIEW |
| | PERMIT: 14100679 |
| | ADD: 2600 FLORIDA AVENUE |
| | CONT: TBD / TO BE DETERMINED |
| | TEL: (561) 313-0965 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. NOV. 08/2014 |
| | ACTION: DENIED |
| | |
| | NOTE: |
| | THE MEZZANINE LEVEL MEETS THE SQUARE FOOTAGE |
| | REQUIREMENTS EVEN WITH THE ENCLOSED AREA BENEATH THE |
| | MEZZANINE AS SHOWN(2010 FBC-B 505.2 AREA LIMITATION). |
| | THE OCCUPANT LOAD OF LESS THAN 10 WILL STILL MEET THE |
| | REQUIRED OPENNESS REQUIREMENT, (2010 FBC-B 505.4 EXC # |
| | 1). 1. MEZZANINES OR PORTIONS THEREOF ARE NOT REQUIRED |
| | TO BE OPEN TO THE ROOM IN WHICH THE MEZZANINES ARE |
| | LOCATED, PROVIDED THAT THE OCCUPANT LOAD OF THE |
| | AGGREGATE AREA OF THE ENCLOSED SPACE DOES NOT EXCEED |
| | 10. |
| | |
| | UNKNOWN FACTORS: |
| | 1) THE USAGE WILL NEED TO BE DEMONSTRATED, IBELIEVE ON |
| | THE PERMIT APPLICATION UNDER THE CONTRACTOR COMPANY |
| | NAME LISTED IS EG2-EDUCATIONAL GALLERY GROUP. IS THAT |
| | THE PROPOSED NAME OF THE BUSINESSFOR THE NEW OCCUPANCY? |
| | IF SO WHAT IS THE TARGET AGE GROUP YOU WILL BE WORKING |
| | WITH, KIDS K-12 GRADE OR ADULTS, THIS EFFECTS THE |
| | OCCUPANCY CLASSIFICATION AND THE REVIEWS TO BE |
| | COMPLETED UNDER THE CHANGE OF OCCUPANCY OF THIS PERMIT. |
| | FOR THE PURPOSE OF THIS REVIEW I WILL BE LOOKING AT THE |
| | PROPOSED TARGET GROUP YOU WILL BE WORKING WITH AS |
| | ADULTS. |
| | IF ADULTS IS THE GROUP MOST LIKELY TO ATTEND THE |
| | STUDIO, THE OCCUPANCY WILL BE A BUSINESS OCCUPANCY, |
| | TRAINING AND SKILL DEVELOPMENT NOT WITHIN A SCHOOL OR |
| | ACADEMIC PROGRAM. 2010 FBC-B 304.1. |
| | |
| | NOTE IF THIS IS TO BE AN ART GALLERY THEN THE OCCUPANCY |
| | WOULD BE A A-3 AND WOULD BE COMPLETELY DIFFERENT AS |
| | WELL AS IF CHILDREN ARE THE TARGET AGE YOU WOULD BE |
| | WORKING WITH, THEN IT WOULD BE EDUCATIONAL. |
| | |
| | 2) THERE IS NO INFORMAION ON THE EXISTING STAIR OR |
| | GAURDRAIL SYSTEMS. PLEASE PROVIDE ADDITIONAL DETAILS |
| | FOR CODE COMPLIANCE WITH THE 2010 FBC-B 1009.4.2 STAIR |
| | RISERS AND TREAD WIDTH. |
| | 1009.4.5 PROFILE/ SOLID RISER REQUIREMENTS & EXCEPTIONS |
| | 1009.6 STAIRWAY CONSTRUCTION. |
| | ALL STAIRWAYS SHALL BE BUILT OF MATERIALS CONSISTENT |
| | WITH THE TYPES PERMITTED FOR THE TYPE OF CONSTRUCTION |
| | OF THE BUILDING, EXCEPT THAT WOOD HANDRAILS SHALL BE |
| | PERMITTED FOR ALL TYPES OF CONSTRUCTION. |
| | 1009.6.3 ENCLOSURES UNDER STAIRWAYS. |
| | THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE SPACES |
| | UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE |
| | PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION |
| | OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY |
| | ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED |
| | SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR |
| | ENCLOSURE. |
| | HANDRAILS: |
| | 1012.2 HEIGHT. |
| | HANDRAIL HEIGHT, MEASURED ABOVE STAIR TREAD NOSINGS, OR |
| | FINISH SURFACE OF RAMP SLOPE, SHALL BE UNIFORM, NOT |
| | LESS THAN 34 INCHES (864 MM) AND NOT MORE THAN 38 |
| | INCHES (965 MM). HANDRAIL HEIGHT OF ALTERNATING TREAD |
| | DEVICES AND SHIP LADDERS, MEASURED ABOVE TREAD NOSINGS, |
| | SHALL BE UNIFORM, NOT LESS THAN 30 INCHES (762 MM) AND |
| | NOT MORE THAN 34 INCHES (864 MM). |
| | EXCEPTION: HANDRAILS FOR STAIRS NOT REQUIRED TO BE |
| | ACCESSIBLE THAT FORM PART OF A GUARDRAIL MAY BE 42 |
| | INCHES (1067 MM) HIGH. |
| | GAURDRAILS: 1013.3 OPENING LIMITATIONS. |
| | REQUIRED GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW |
| | PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM |
| | THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT. |
| | |
| | 3) THE PLANS FAIL TO PROVIDE EMERGENCY LIGHTING AS WELL |
| | AS DIRECTIONAL & EXIT LIGHTING. |
| | 1006.1.6.2 BATTERY-OPERATED ELECTRIC LIGHTS AND OTHER |
| | TYPES OF PORTABLE LAMPS OR LANTERNS SHALL NOT BE USED |
| | FOR PRIMARY ILLUMINATION OF MEANS OF EGRESS. |
| | BATTERY-OPERATED ELECTRIC LIGHTS SHALL BE PERMITTED TO |
| | BE USED AS AN EMERGENCY SOURCE TO THE EXTENT PERMITTED |
| | UNDER SECTION 1006.2.3.4. |
| | |
| | 1006.3.8 WHERE THE DIRECTION OF TRAVEL TO REACH THE |
| | NEAREST EXIT IS NOT APPARENT, A DIRECTIONAL SIGN |
| | COMPLYING WITH SECTIONS 1006.3.5 OR 1006.3.6 READING |
| | ?EXIT,? OR A SIMILAR DESIGNATION WITH A DIRECTIONAL |
| | INDICATOR SHOWING THE DIRECTION OF TRAVEL SHALL BE |
| | PLACED IN EVERY LOCATION. DIRECTIONAL SIGNS SHALL BE |
| | LISTED. |
| | |
| | 1006.3.1 EXITS SHALL BE MARKED BY AN APPROVED SIGN |
| | READILY VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. |
| | EVERY EXIT SIGN SHALL BE SUITABLY ILLUMINATED BY A |
| | RELIABLE LIGHT SOURCE. EXTERNALLY AND INTERNALLY |
| | ILLUMINATED SIGNS SHALL BE VISIBLE IN BOTH NORMAL AND |
| | EMERGENCY LIGHTING. |
| | |
| | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO |
| | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA |
| | TUS.ASPX FOR PERMIT STATUS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |