Plan Review Details - Permit 14100673
Plan Review Stops For Permit 14100673
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By rmcdouga Date 2014-11-07 Time 17:32 Rev Time 0.00
Received By rmcdouga Date 2014-11-07 Time 07:37 Sent To E
Notes
2014-11-07 17:32:09PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE DESCRIPTION OF WORK ON THE APPLICATION IS TO
 DEMOLISH ELECTRICAL WIRING ( REMOVE 2ND AND 3RD PANELS)
 AND REMOVE ILLEGAL WALLS (NO NEW CONSTRUCTION) WITH A
 VALUATION OF $2000.00 FOR THE WORK. THE 3 SHEETS OF
 PLANS THAT WERE SUBMITTED DO NOT CORRESPOND WITH THE
 DESCRIPTION ON THE APPLICATION. ONE SHEET IS TITLED
 ALTERATIONS TO RESIDENCE AND THE OTHER TWO SHEETS ARE
 TITLED "GUEST HOUSE AS-BUILTS". PROVIDE PLANS THAT
 CLEARLY SPECIFY THE WORK THAT WILL BE DONE. FBC 107.2.1
  
 2) UN-PERMITTED CONVERSION
  
 THE SCOPE OF WORK FOR THIS PERMIT IS TO ADDRESS THE
 ILLEGAL CONVERSION OF AN EXISTING GARAGE TO AN
 APARTMENT OR ACCESSORY STRUCTURE.
 ACCORDING TO CITY RECORDS, THIS STRUCTURE WAS
 ORIGINALLY CONSTRUCTED AS A DETACHED GARAGE. IT WAS
 CONVERTED TO AN APARTMENT WITH A KITCHEN, BEDROOM AND
 BATHROOM WITHOUT THE REQUIRED PERMITS OR INSPECTIONS.
 UNDER THE 2010 FBC EXISTING BUILDING THIS IS CONSIDERED
 A CHANGE OF OCCUPANCY. IN ORDER FOR THIS STRUCTURE-TO
 BE BROUGHT INTO COMPLIANCE, IT WILL BE REQUIRED TO
 COMPLY WITH THE 2010 FBC EXISTING BUILDING FOR A CHANGE
 OF OCCUPANCY FROM A UTILITY TO AN R-3 OCCUPANCY. THIS
 CHANGE IS FROM A LOWER HAZARD CATEGORY TO A HIGHER ONE.
 THEREFORE, THE FOLLOWING ITEMS WILL NEED TO BE BROUGHT
 INTO COMPLIANCE. THE STRUCTURE WILL BE REQUIRED TO
 COMPLY WITH THE 2010 FBCR WINDLOAD REQUIREMENTS FOR THE
 BUILDING ENVELOPE ( IN ADDITION TO GRAVITY LOADS),
 PRODUCT APPROVALS FOR EXTERIOR DOORS AND WINDOWS,
 EGRESS REQUIREMENTS, LIGHT AND VENTILATION, SMOKE AND
 CARBON MONOXIDE ALARMS, FIRE PROTECTION REQUIREMENTS
 (SEPARATION DISTANCE AND ALLOWABLE OPENINGS), THE
 REQUIREMENTS OF THE 2010 FBC ENERGY CONSERVATION, THE
 REQUIREMENTS OF THE 2010 FBCR MECHANICAL, THE
 REQUIREMENTS OF THE 2010 FBCR PLUMBING AND THE
 ELECTRICAL SYSTEM WILL BE REQUIRED TO COMPLY WITH THE
 2008 NATIONAL ELECTRICAL CODE. THE PLANS WILL NEED TO
 SHOW HOW THE GARAGE WILL BE CONVERTED TO HABITABLE
 SPACE IN COMPLIANCE WITH THE 2010 FBC AND 2008 NEC. THE
 PLANS WILL NEED TO BE REVIEWED BY PALM BEACH COUNTY TO
 DETERMINE IF ANY IMPACT FEES ARE DUE.
  
 3) THE ABOVE REQUIREMENTS APPLY TO THE CONVERSION OF
 THE ATTACHED CARPORT INTO LIVING SPACE.
  
 4) BECAUSE THE WORK WAS DONE WITHOUT PERMITS THE
 VALUATION FOR THE PERMIT IS THE VALUE OF WHAT THE WORK
 WOULD BE TO CONVERT BOTH OF THE AREAS TO LIVING SPACE.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 5) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-08 Cont ID  
Sent By dhayes Date 2014-11-08 Time 09:04 Rev Time 0.00
Received By dhayes Date 2014-11-08 Time 08:56 Sent To  
Notes
2014-11-08 09:22:2911/8/2014
 PROJECT: 901 FOREST HILL
 PERMIT#: 14100673
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) CLARIFICATION REQUIRED. PLEASE PROVIDE ADDITIONAL
 INFORMATION ON THE FOLLOWING:
 A) THE SIZE (AMPERE, VOLTAGE RATING AND TYPE) OF
 DISCONNECT SWITCH AT ELECTRICAL SERVIICE.
 B) THE LOCATION OF THE ELECTRICAL SERVICE.
 C) THE SIZE AND TYPE OF THE SERVICE ENTRANCE CONDUCTORS
 IN THE SERVICE RISER TO THE WEATHERHEAD.
 D) THE SIZE TYPE AND DETAIL OF ALL THE GROUDING
 ELECTROTRODE SYSTEM.
 E) EACH OF THE FEEDERS FROM THE ELECTRICAL SERVICE
 INDICATE 3 CONDUCTORS IN A CONDUIT. THERE IS NO MENTION
 OF A GROUNDING CONDUCTOR. THE ONLY PLACE A GROUNDING
 CONDUCTOR WOULD NOT BE REQUIRED WOULD BE AT THE SERVICE
 ENTRANCE. THE ONLY ALTERNATICE WOULD BE IF THE FEEDER
 CONDUCTORS WERE INSTALLED IN A METLAL CONDUIT WITH THE
 USE OF PROPER GROUNDING LOCKNUTS BONDING BUSINGS ETC...
 F ) THE LOCATION OF THE MAIN HOUSE PANEL
 G) THE OCPD FOR THE SUB PANEL
 H) THE LOCATION OF THE A/C CONDENSING UNITS AND A/C
 AHU'S,THE REQUIRED A/C DISCONNECTS, AND GFI OUTLETS
 WITHIN SITE FOR MECHANICAL EQUIPMENT.
  
 2) REVISE THE RISRE DIAGRAMS, LOAD CALCULATIONS AND
 PANEL SCHEDULES TO CORRECT THE FOLLOWING DEFICIENCIES.
 A) THE OCPD FOR THE SUB PANEL IS NOT INDICATED IN THE
 PANEL SCHEDULE FOR MAIN HOUSE PANEL
 B) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATION SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. NEC 408.4. "GENERAL
 LIGHTING" OR "CONVENIENCE OUTLETS" IS NOT SUFFICIENT.
 CORRECT BOTH PANEL SCHEDULES.
 C) THE LOAD CALCULATION FOR THE "GUEST HOUSE" INDICATES
 1200 WATTS TO COMPENSATE THE GENERAL LIGHTING LOAD AT 3
 WATTS PER SQUARE FOOT, BUT THEN ALSO ADDS AN ADDITIONAL
 4500WATTS FOR "GENERAL LIGHTING" AND ANOTHER 6000WATTS
 FOR "CONVENIENCE OUTLETS" THIS IS NOT A CODE
 REQUIRMENT, AND IS AN INACCURATE ASSESMENT OF THE
 ACTUAL OR DEMAND LOAD OF THE ELECTRICAL SYSTEM.
 D) EACH OF THE FEEDERS FROM THE ELECTRICAL SERVICE
 INDICATE 3 CONDUCTORS IN A CONDUIT. THERE IS NO MENTION
 OF A GROUNDING CONDUCTOR. THE ONLY PLACE A GROUNDING
 CONDUCTOR WOULD NOT BE REQUIRED WOULD BE AT THE SERVICE
 ENTRANCE. THE ONLY ALTERNATICE WOULD BE IF THE FEEDER
 CONDUCTORS WERE INSTALLED IN A METLAL CONDUIT WITH THE
 USE OF PROPER GROUNDING LOCKNUTS BONDING BUSINGS ETC...
 CLARFY AS NEEDED.
 E) PROVIDE AND INDICATE ON THE FLOOR PLAN AND IN THE
 PANEL SCHEDULES THE USE OF A SEPARATE 20AMP CIRCUIT FOR
 THE BATHROOMS. SUCH OUTLETS SHALL HAVE NO OTHER
 OUTLETS.
  
 3) IDENTIFY THE CIRCUITS ON THE FLOOR PLAN(S) TO THE
 CORRESPONDING CIRCUITS IN BOTH PANEL SCHEDULES.
  
 4) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315. INDICATE THE REQUIRED SMOKE DETECTORS
 THROUGHOUT.
  
 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 6) INDICATE OUTLET BOXES USED AS THE SOLE SUPPORT OF A
 CEILING FAN SHALL BE LISTED, SHALL BE MARKED BY THEIR
 MANUFACTURER AS SUITABLE FOR THIS PURPOSE.
  
 7) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11. ADD
 NOTES ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-08 Cont ID  
Sent By dhayes Date 2014-11-08 Time 10:33 Rev Time 0.00
Received By dhayes Date 2014-10-21 Time 14:50 Sent To  
Notes
2014-10-22 14:50:52SENT TO R8 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By rmcdouga Date 2014-11-07 Time 18:29 Rev Time 0.00
Received By rmcdouga Date 2014-11-07 Time 18:29 Sent To  
Notes
2014-11-07 18:30:15BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-11-08 Cont ID  
Sent By rmcdouga Date 2014-11-07 Time 18:29 Rev Time 0.00
Received By rmcdouga Date 2014-11-07 Time 07:37 Sent To  
Notes
2014-11-07 18:37:38PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 MECHANICAL - NO MECHANICAL WORK IS SHOWN ON THE PLANS
 OTHER THAN BATH AND DRYER EXHAUST. HOWEVER, THE PANEL
 SCHEDULE ON THE ELECTRICAL PLAN INDICATES THERE IS
 AIR-CONDITIONING.
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
 FBC ENERGY CONSERVATION - SECT. 103.2.3.2 CODE
 COMPLIANCE CERTIFICATION.
 THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS. FBC ENERGY
 CONSERVATION - SECT. 403.6.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES,
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF
 THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE
 SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN
 SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY
 FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER
 FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD
 KITCHEN AND BATHROOM EXHAUST SYSTEMS.
  
 3) FBC - 107.3.5.3 PROVIDE A MECHANICAL PLAN TO SHOW
 LOCATION AND SIZES OF ALL DUCTS, SUPPLY & RETURN
 GRILLS, CFMS AT EACH OUTLET. PROVIDE AN EQUIPMENT
 SCHEDULE ON THE MECHANICAL PLANS THAT CORRESPONDS WITH
 THE SIZING CALCULATIONS. FBC -107.3.5.1.4 MECHANICAL
 MINIMUM PLAN REVIEW CRITERIA: SHOW, EXHAUST SYSTEMS,
 CLOTHES DRYER EXHAUST, KITCHEN EQUIPMENT EXHAUST,
 SPECIALTY EXHAUST SYSTEMS, EQUIPMENT, EQUIPMENT
 LOCATION, MAKE-UP AIR, ROOF-MOUNTED EQUIPMENT, DUCT
 SYSTEMS, VENTILATION, COMBUSTION AIR, CHIMNEYS,
 FIREPLACES AND VENTS, APPLIANCES, BOILERS,
 REFRIGERATION, BATHROOM VENTILATION, LABORATORY, DESIGN
 FLOOD ELEVATION.
  
 4) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS.
  
 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-05 Cont ID  
Sent By tklarge Date 2014-11-05 Time 05:50 Rev Time 0.00
Received By tklarge Date 2014-11-05 Time 05:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2014-10-27 Cont ID  
Sent By sgraham Date 2014-10-27 Time   Rev Time  
Received By sgraham Date 2014-10-27 Time   Sent To  
Notes
2014-10-27 14:58:5910/27/14 ZONING FAILED
  
 1. PLANS NEED TO REFLECT REMOVING THE ILLEGAL
 CONVERSIONS, THE CARPORT AND THE STORAGE BUILDLING IN
 THE REAR.
  
 2. FENCE PERMIT REQUIRED FOR NEW FENCING.