Plan Review Details - Permit 14100616
Plan Review Stops For Permit 14100616
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-11-05 Cont ID  
Sent By JWITMER Date 2014-11-05 Time 16:36 Rev Time 0.00
Received By jwitmer Date 2014-11-05 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-11-21 Cont ID  
Sent By tlarge Date 2014-11-21 Time 11:45 Rev Time 0.00
Received By dhayes Date 2014-11-21 Time 11:45 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-21 Cont ID  
Sent By DHAYES Date 2014-10-21 Time 09:00 Rev Time 0.00
Received By dhayes Date 2014-10-21 Time 09:00 Sent To  
Notes
2014-10-20 18:03:26MISSING DRAWING E301

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-11-05 Cont ID  
Sent By wjolin Date 2014-11-05 Time 16:39 Rev Time 0.00
Received By wjolin Date 2014-11-05 Time 16:39 Sent To  
Notes
2014-11-05 16:39:49PASSED BY WJ PER SC ON 11/05/14.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-12-17 Cont ID  
Sent By tklarge Date 2014-12-17 Time 11:40 Rev Time 0.00
Received By tklarge Date 2014-12-16 Time 16:26 Sent To  
Notes
2014-12-16 16:27:30SENT TO T. K. LARGES' DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-11 Cont ID  
Sent By skennedy Date 2014-12-11 Time 07:50 Rev Time 0.00
Received By skennedy Date 2014-12-09 Time 10:14 Sent To  
Notes
2014-12-09 10:14:26SENT TO T LARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-22 Cont ID  
Sent By tklarge Date 2014-11-22 Time 09:15 Rev Time 0.00
Received By tklarge Date 2014-11-20 Time 11:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-05 Cont ID  
Sent By jwitmer Date 2014-11-05 Time 16:50 Rev Time 0.00
Received By jwitmer Date 2014-10-20 Time 18:03 Sent To  
Notes
2014-10-20 18:04:02REVISION SENT TO B3 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 4 Status P Date 2014-12-17 Cont ID  
Sent By tklarge Date 2014-12-17 Time 11:38 Rev Time 0.00
Received By tklarge Date 2014-12-17 Time 11:38 Sent To  
Notes
2014-12-17 12:31:10GAS REVIEWED UNDER #14120261

Review Stop P PLUMBING
Rev No 3 Status F Date 2014-12-10 Cont ID  
Sent By tklarge Date 2014-12-10 Time 11:09 Rev Time 0.00
Received By tklarge Date 2014-12-10 Time 10:52 Sent To  
Notes
2014-12-10 10:53:121) SHT.P202 - THERE ARE WATER LINES THAT JUST END
 WITHOUT ANY REFERENCE POINT AS TO WHERE THEY CONNECT,
 CONTINUE, ETC.CLARIFY.(SEE AREAS CLOUDED WITH HI-LITER
 ON SHT. P202.)
 2) THE GAS REVIEW HAS BEEN DONE UNDER PERMIT
 APPLICATION # 14120261.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-11-22 Cont ID  
Sent By tklarge Date 2014-11-22 Time 09:03 Rev Time 0.00
Received By tklarge Date 2014-11-22 Time 08:10 Sent To  
Notes
2014-11-22 09:14:531) SHOW THE SIZES FOR THE WATER DISTIBUTION LINES TO
 THE FIXTURES FOR BATHROOMS NUMBER 158 & 159. 2ND
 REQUEST.
 2) THE GAS LINE CARRYING 2071 CFH IS UNDERSIZED AT 1
 1/4". THE MAXIMUM BTU LOAD FOR 1 1/4' PIPE @2 PSI & 300
 FT. RUN IS 1,940,000. THE SIZE SHALL BE 1 1/2".
 3) THE PIPE SIZES ON THE WATER RISER ARE SO SMALL THEY
 ARE ILLEGIBLE. SIZE THE LINES SO THE DIMENSION IS CLEAR
 AND LEGIBLE. WPB AMEND. TO 2010 FPC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-01 Cont ID  
Sent By JWITMER Date 2014-11-01 Time 06:50 Rev Time 0.00
Received By tklarge Date 2014-11-01 Time 06:43 Sent To  
Notes
2014-11-01 06:50:201) IT APPEARS THAT THE HOT WATER SYSTEM REQUIRES A
 METHOD OF HOT WATER SUPPLY MAINTENANCE PER SEC. 607.2
 OF THE 2010
 FPC.607.2 HOT WATER SUPPLY TEMPERATURE MAINTENANCE.
 WHERE THE DEVELOPED LENGTH OF HOT WATER PIPING FROM THE
 SOURCE OF HOT WATER SUPPLY TO THE FARTHEST FIXTURE
 EXCEEDS 100 FEET (30 480 MM), THE HOT WATER SUPPLY
 SYSTEM SHALL BE PROVIDED WITH A METHOD OF MAINTAINING
 THE TEMPERATURE IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, ENERGY CONSERVATION.
 2) THERE ARE A LOT OF SECTIONS ON THE WATER RISER THAT
 ARE NOT SIZED. CHECK ALL THE SECTIONS AND SIZE THE
 LINES THAT REQUIRE THE SIZING. SEE THE WATER
 DISTRIBUTION PIPING FOR THE RESTROOMS ALSO. WPB AMEND.
 TO 2010 FPC SEC.107.2.1.
 3) SUBMIT MANUF. SPEC SHEETS AND INSTALLATION MANUAL
 FOR THE POINT OF USE WATER HEATERS.WPB AMEND. TO 2010
 FPC SEC.107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  