Plan Review Details - Permit 14100615
Plan Review Stops For Permit 14100615
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-12-24 Cont ID  
Sent By rmcdouga Date 2014-12-24 Time 09:32 Rev Time 0.00
Received By rmcdouga Date 2014-12-24 Time 09:14 Sent To  
Notes
2014-12-24 09:14:20THE ALUMINUM CARPORT WAS REMOVED FROM THE SCOPE OF
 WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-12-22 Cont ID  
Sent By rmcdouga Date 2014-12-22 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2014-12-22 Time 06:58 Sent To E
Notes
2014-12-23 13:42:0412/23/14 ZONING FAILED
  
 1. CARPORT DOES NOT MEET SETBACKS, POSTS ARE ONLY 2.3
 FROM THE SIDE YARD.
2014-12-22 08:21:15PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 BUILDING
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 2) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 EXTERIOR DOORS ( FL-15180.40 ), THE SINGLE HUNG WINDOWS
 ( NOA NO. 12-0213.05 ) AND THE ALUMINUM TUBE MULLIONS (
 NOA NO. 12-0221.09 ) HAVE NOT BEEN REVIEWED AND
 APPROVED IN WRITING BY THE ENGINEER AS REQUIRED BY FBC
 107.3.4.
  
 3) THE INSTALLATION DRAWINGS FOR THE WINDOWS AND
 MULLIONS WERE NOT SHRUNK TO FIT ON THE 8.5" X 11" SIZE
 PAPER AND ARE MISSING INFORMATION. SUBMIT PRODUCT
 APPROVALS WITH COMPLETE DRAWINGS. DCA RULE 9N-3 AND FBC
 107.2.1
  
 4) THERE ARE TWO DIFFERENT EXPOSURE CATEGORIES
 SPECIFIED ON THE PLANS. THE SHEET S-1 HAS "D" AND SHEET
 S-3 HAS "C". THERE CAN BE ONLY ONE EXPOSURE CATEGORY
 AND "C" IS THE CORRECT ONE. FBCR 301.2.1.1
  
 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 ALUMINUM ROOF PANELS THAT HAVE BEEN REVIEWED AND
 APPROVED BY IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. DCA RULE 9N-3 AND FBC 107.3.4
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-21 Cont ID  
Sent By rmcdouga Date 2014-11-21 Time 18:03 Rev Time 0.00
Received By rmcdouga Date 2014-11-21 Time 06:54 Sent To  
Notes
2014-11-21 14:28:40PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 BUILDING
  
 1) THE ENGINEER'S SEAL THAT APPEARS ON THE PLANS IS NO
 LONGER ACCEPTABLE. THE SEAL WAS CHANGED ON JANURARY 1,
 2006 REQUIRING THE WORD "LICENSE" TO BE USED INSTEAD OF
 THE WORD "CERTIFICATE". PLEASE SUBMIT PLANS THAT HAVE A
 SEAL THAT IS ACCEPTED BY THE BOARD OF ENGINEERS. FS 471
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
 A) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS ( NOA NO. 12-0213.05 ) AND THE
 ALUMINUM TUBE MULLIONS ( NOA NO. 12-0221.09 ) HAVE NOT
 BEEN REVIEWED AND APPROVED IN WRITING BY THE ENGINEER.
 B) THE INSTALLATION DRAWINGS WERE NOT SHRUNK TO FIT ON
 THE 8.5" X 11" SIZE PAPER AND ARE MISSING INFORMATION.
 SUBMIT PRODUCT APPROVALS WITH COMPLETE DRAWINGS.
 C) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE EXTERIOR
 DOORS. SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. SHOW SMOKE
 ALARMS ON THE PLANS.
  
 4) SPECIFY THE WIND DESIGN DATA INCLUDING THE EXPOSURE
 CATEGORY ON THE PLANS. FBCR 301.2.1.1
  
 5) SPECIFY THE REQUIRED COMPONENT & CLADDING PRESSURES
 FOR THE WINDOW AND DOORS ON THE PLANS. FBCR 301.2.1 THE
 C & C PRESSURES THAT WERE SPECIFIED ON THE PLANS ( +80
 , -115 PSF ) AND (+50 , -50 PSF )ARE INCORRECT.
  
 6) PROVIDE COMPLETE STRUCTURAL DRAWINGS AND DETAILS FOR
 THE NEW CARPORT TO SHOW THAT IT COMPLIES WITH FBC-R
 301.1. BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF,
 SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS,
 INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD
 LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE. THE
 CONSTRUCTION OF BUILDINGS AND STRUCTURES IN ACCORDANCE
 WITH THE PROVISIONS OF THIS CODE SHALL RESULT IN A
 SYSTEM THAT PROVIDES A COMPLETE LOAD PATH THAT MEETS
 ALL REQUIREMENTS FOR THE TRANSFER OF ALL LOADS FROM
 THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION. SPECIFY THE FOUNDATION AND
 SLAB SIZE AND RE-INFORCEMENT, THE COLUMN, BEAM AND
 RAFTER SIZES AND TYPE OF WOOD. SPECIFY THE RAFTER
 SPACING AND THE ROOF SHEATHING THAT IS REQUIRED.
 SPECIFY ALL OF THE ANCHORS, STRAPS, HANGERS AND
 FASTENERS THAT WILL BE REQUIRED. FBC 107.2.1 AND
 107.2.1.3 IF THE INFORMATION FOR THE ALUMINUM CARPORT
 IS NOT PROVIDED WITH THIS SUBMITTAL, THEN A SEPERATE
 PERMIT, APPLICATION AND REVIEW WILL BE REQUIRED. NOTE
 ON PLANS THAT THE CARPORT AND FRONT PORCH AWNING ARE
 UNDER SEPARATE PERMITS OR SUBMIT ALL REQUESTED
 INFORMATION.
  
 7) SHEET C-1, WHICH IS LISTED IN THE DRAWING INDEX ON
 SP-1, IS MISSING FROM THE PLANS. SUBMIT THE MISSING
 DRAWING OR REVISE THE DRAWING INDEX.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
 RESUBMITTAL PROCEDURE
 YOU ARE REQUIRED TO FILL OUT A RESUBMITTAL FORM TO BE
 SUBMITTED WITH THE CORRECTED PLANS.
 THE PERMIT CLERK WILL RETRIEVE THE DENIED APPLICATION,
 PLANS AND OTHER DOCUMENTS FOR YOU.
 YOU ARE REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT
 HAVE BEEN CORRECTED AND REPLACE THEM WITH THE NEW ONES.
 THE CLERK WILL PROVIDE YOU WITH A STAPLE REMOVER AND A
 STAPLER. ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN
 REMOVED SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG
 WITH THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS SHALL BE SUBMITTED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-06 Cont ID  
Sent By rmcdouga Date 2014-11-06 Time 18:37 Rev Time 0.00
Received By rmcdouga Date 2014-11-06 Time 11:39 Sent To  
Notes
2014-11-06 16:08:07PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 THE PLANS THAT WERE SUBMITTED APPEAR TO BE UNFINISHED
 AND INCOMPLETE.
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 BUILDING
  
 1) THE ENGINEER'S SEAL THAT APPEARS ON THE PLANS IS NO
 LONGER ACCEPTABLE. THE SEAL WAS CHANGED ON JANURARY 1,
 2006 REQUIRING THE WORD "LICENSE" TO BE USED INSTEAD OF
 THE WORD "CERTIFICATE". PLEASE SUBMIT PLANS THAT HAVE A
 SEAL THAT IS ACCEPTED BY THE BOARD OF ENGINEERS. FS 471
  
 2) SPECIFY THE DISTANCE FROM THE NEW CARPORT ADDITION
 TO THE PROPERTY LINE ON THE PLANS. FBCR 302 AND TABLE
 R302.1 REQUIRES A MINIMUM FIRE SEPARATION DISTANCE OF 3
 FEET FOR WALLS AND ROOF OVERHANG PROJECTIONS WITHOUT
 FIRE-RESISTANCE RATINGS.
  
 3) SPECIFY THE WINDOW TYPES AND DIMENSIONS ON THE
 PLANS.
  
 4) SPECIFY THE DOOR TYPES AND DIMENSIONS ON THE PLANS.
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW, AND DOOR STATE OF FLORIDA OR MIAMI-DADE NOAS.
  
 6) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 7) R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES.
  
 8) R301.2.1.2 PROTECTION OF OPENINGS.
 WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR
 WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12
 OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN.
 IF GLAZING IN THE WIDOWS AND DOORS IS NOT RATED FOR
 LARGE MISSILE IMPACT, THEN SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE IMPACT PROTECTION DEVICES, AN
 INSTALLATION SCHEDULE AND A KEY PLAN.
  
 9) SPECIFY THE WIND DESIGN DATA INCLUDING THE EXPOSURE
 CATEGORY ON THE PLANS. FBCR 301.2.1.1
  
 10) SPECIFY THE COMPONENT & CLADDING PRESSURES FOR THE
 WINDOW AND DOORS ON THE PLANS. FBCR 301.2.1
  
 11) PROVIDE COMPLETE STRUCTURAL DRAWINGS AND DETAILS
 FOR THE NEW CARPORT TO SHOW THAT IT COMPLIES WITH FBC-R
 301.1. BUILDINGS AND STRUCTURES, AND ALL PARTS THEREOF,
 SHALL BE CONSTRUCTED TO SAFELY SUPPORT ALL LOADS,
 INCLUDING DEAD LOADS, LIVE LOADS, ROOF LOADS, FLOOD
 LOADS, AND WIND LOADS AS PRESCRIBED BY THIS CODE. THE
 CONSTRUCTION OF BUILDINGS AND STRUCTURES IN ACCORDANCE
 WITH THE PROVISIONS OF THIS CODE SHALL RESULT IN A
 SYSTEM THAT PROVIDES A COMPLETE LOAD PATH THAT MEETS
 ALL REQUIREMENTS FOR THE TRANSFER OF ALL LOADS FROM
 THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING
 ELEMENTS TO THE FOUNDATION. SPECIFY THE FOUNDATION AND
 SLAB SIZE AND RE-INFORCEMENT, THE COLUMN, BEAM AND
 RAFTER SIZES AND TYPE OF WOOD. SPECIFY THE RAFTER
 SPACING AND THE ROOF SHEATHING THAT IS REQUIRED.
 SPECIFY ALL OF THE ANCHORS, STRAPS, HANGERS AND
 FASTENERS THAT WILL BE REQUIRED. FBC 107.2.1 AND
 107.2.1.3
  
 12) FBC-R803.2.3.1 SHEATHING FASTENINGS.
 WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO
 ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING
 MINIMUM DIMENSIONS:
 1. 0.113 INCH NOMINAL SHANK DIAMETER.
 2. RING DIAMETER OF 0.012 OVER SHANK DIAMETER.
 3. 16 TO 20 RINGS PER INCH.
 4. 0.280 INCH FULL ROUND HEAD DIAMETER.
 5. 2 INCH NAIL LENGTH.
 WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G <
 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE
 4 INCHES ON CENTER IN NAILING ZONE 3 IN ACCORDANCE WITH
 FIGURE R803.2.3.1 WHERE VASD AS DETERMINED IN
 ACCORDANCE WITH SECTION R301.2.1.3 IS 130 MPH OR
 GREATER.
  
 13) SHEET C-1, WHICH IS LISTED IN THE DRAWING INDEX ON
 SP-1, IS MISSING FROM THE PLANS.
  
 14) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
 RESUBMITTAL PROCEDURE
 YOU ARE REQUIRED TO FILL OUT A RESUBMITTAL FORM TO BE
 SUBMITTED WITH THE CORRECTED PLANS.
 THE PERMIT CLERK WILL RETRIEVE THE DENIED APPLICATION,
 PLANS AND OTHER DOCUMENTS FOR YOU.
 YOU ARE REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT
 HAVE BEEN CORRECTED AND REPLACE THEM WITH THE NEW ONES.
 THE CLERK WILL PROVIDE YOU WITH A STAPLE REMOVER AND A
 STAPLER. ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN
 REMOVED SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG
 WITH THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS SHALL BE SUBMITTED.
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-12-22 Cont ID  
Sent By dhayes Date 2014-12-22 Time 12:03 Rev Time 0.00
Received By dhayes Date 2014-12-22 Time 11:12 Sent To  
Notes
2014-12-22 11:46:2112/22/2014
 PROJECT: MURRAY ROAD HOUSE
 PERMIT#: 14100615
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) FOR A ONE FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST
 ONE RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT
 GRADE LEVEL AND LOCATED NOT MORE THAN 2.0 M (61.2 FT)
 ABOVE GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. NEC 210.52(E)(3)
  
 2) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. NEC
 210.63 SEE 210.8(A)(3)
  
 3) ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 RECEPTACLES INSTALLED IN THE LOCATIONS SPECIFIED IN (1)
 THROUGH (8) SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. NEC 210.8(A)(6) WITHIN 6' OF
 THE SINK.
  
 4) VERIFY SUFFICIENT ACCESS AND WORKING SPACE SHALL BE
 PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT
 TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF
 SUCH EQUIPMENT. NEC 110.26
  
 5) VERIFY RECEPTACLE SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8
 M (6 FT) FROM A RECEPTACLE OUTLET. NEC 210.52
  
 6) AS BUILT REQUIRED IF PROJECT IS DIFFERENT THAN
 PLANS. A CIRCUIT #13 IN THE PANEL SCHEDULE IS
 IDENTIFIED AS NEW LIGHTING AT BEDROOM AND BATH.
 INDICATE ANY NEW WORK ON THE PLANS. FBC-WPB AMENDMENTS
 107.3.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2014-12-08 Cont ID  
Sent By skennedy Date 2014-12-08 Time 14:05 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
2014-12-08 14:07:01APPLICANT ELECTED TO SUBMIT COMPLETE NEW DESIGN
 DOCUMENTS PRIOR TO SECOND ELECTRICAL REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-28 Cont ID  
Sent By dhayes Date 2014-10-28 Time 11:03 Rev Time 0.00
Received By dhayes Date 2014-10-28 Time 11:03 Sent To  
Notes
2014-10-28 11:34:5510/28/2014
 PROJECT: MURRAY RD. HOUSE
 PERMIT#: 14100615
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) COUNTERTOP OUTLETS IN THE KITCHEN SHALL BE INSTALLED
 IN ACCORDANCE WITH THE PROVISIONS OF NEC 210.52(C) AT
 LEAST ONE ADDITIONAL OUTLET(S) IS REQUIRED.
  
 2) ELECTRICAL FLOOR PLAN DOES'NT MATCH ARCHITECTURAL
 FLOOR PLAN. THE LAUNDRY RM IS LOCATED IN A DIFFERENT
 LOCATION ON EACH.
  
 3) IDENTIFY OUTLETS ON THE FLOOR PLAN WITH CORESPONDING
 CIRCUIT NUMBERS FROM THE PANEL SCHEDULE. WPB AMENDMENTS
 TO THE FBC 107.3.2
  
 4) PROVIDE A PANEL SCHEDULE INDICATING THE CIRCUIT
 NUMBERS, ROOM/DEVICE DESIGNATIONS, AMP AND VOLTAGE
 RATINGS.WPB AMENDMENTS TO THE FBC 107.3.2
  
 5) INDICATE THE LOCATIONS AND CIRCUITING OF SMOKE/CO
 DETECTORS. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-12-24 Cont ID  
Sent By rmcdouga Date 2014-12-24 Time 09:32 Rev Time 0.00
Received By rmcdouga Date 2014-12-24 Time 09:11 Sent To  
Notes
2014-12-24 09:11:38SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-22 Cont ID  
Sent By dhayes Date 2014-12-22 Time 12:12 Rev Time 0.00
Received By dhayes Date 2014-12-08 Time 14:07 Sent To  
Notes
2014-12-08 14:07:55RESUB SENT TO R03.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-08 Cont ID  
Sent By skennedy Date 2014-12-08 Time 14:07 Rev Time 0.00
Received By skennedy Date 2014-11-19 Time 14:49 Sent To  
Notes
2014-11-20 14:50:19RE-SUBMITTAL SENT TO SHELF R3 FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-06 Cont ID  
Sent By rmcdouga Date 2014-11-06 Time 18:48 Rev Time 0.00
Received By rmcdouga Date 2014-10-20 Time 11:08 Sent To  
Notes
2014-10-21 11:08:43SENT TO R7 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-11-21 Cont ID  
Sent By rmcdouga Date 2014-11-21 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2014-11-21 Time 06:55 Sent To  
Notes
2014-11-21 08:20:10NO MECHANICAL PERMIT WAS SUBMITTED AND NO NEW
 MECHANICAL WORK IS SHOWN ON THE PLANS. A SEPARATE
 PERMIT, APPLICATION AND REVIEW IS REQUIRED FOR
 MECHANICAL.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-11-06 Cont ID  
Sent By rmcdouga Date 2014-11-06 Time 18:39 Rev Time 0.00
Received By rmcdouga Date 2014-11-06 Time 18:39 Sent To  
Notes
2014-11-06 18:47:20PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS DO NOT CLEARLY INDICATE THE SCOPE OF THE
 PROPOSED MECHANICAL WORK. CLEARLY LIST ALL MECHANICAL
 WORK THAT WILL BE DONE ON THE PLAN. IF NEW SUPPLY DROPS
 ARE BEING ADDED SPECIFY THE DUCT SIZE, GRILL SIZE AND
 CFMS FOR EACH NEW OUTLET.
  
 2) ADDITIONAL COMMENTS MAY RESULT BASED ON THE SCOPE OF
 MECHANICAL WORK.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-18 Cont ID  
Sent By tklarge Date 2014-12-18 Time 06:48 Rev Time 0.00
Received By tklarge Date 2014-12-18 Time 06:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-11-01 Cont ID  
Sent By tklarge Date 2014-11-01 Time 04:11 Rev Time 0.00
Received By tklarge Date 2014-11-01 Time 04:09 Sent To  
Notes
2014-11-01 04:11:03****PROVISO****
 PLUMBING INSPECTOR MAY REQUIRE A SANITARY RISER DIAGRAM
 FOR ANY CHANGES MADE TO THE PLUMBING SYSTEM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 4 Status N Date 2014-12-24 Cont ID  
Sent By rmcdouga Date 2014-12-24 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2014-12-24 Time 09:11 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status F Date 2014-12-22 Cont ID  
Sent By rmcdouga Date 2014-12-22 Time 10:04 Rev Time 0.00
Received By rmcdouga Date 2014-12-22 Time 10:04 Sent To  
Notes
2014-12-22 10:11:25THE CARPORT IS AN ALUMINUM STRUCTURE PER THE PLANS. THE
 PRODUCT APPROVALS FOR THE METAL ROOF PANELS ARE
 REQUIRED TO BE SUBMITTED PER DCA RULE 9N-3.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2014-11-21 Cont ID  
Sent By rmcdouga Date 2014-11-21 Time 18:04 Rev Time 0.00
Received By rmcdouga Date 2014-11-21 Time 18:04 Sent To  
Notes
2014-11-21 18:08:03THE CARPORT AND FRONT PORCH WILL BE ALUMINUM STRUCTURES
 PER THE PLANS. THE PRODUCT APPROVALS FOR THE METAL ROOF
 PANELS ARE REQUIRED TO BE SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-11-06 Cont ID  
Sent By rmcdouga Date 2014-11-06 Time 18:47 Rev Time 0.00
Received By rmcdouga Date 2014-11-06 Time 18:47 Sent To  
Notes
2014-11-06 18:48:20NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.

Review Stop Z ZONING
Rev No 6 Status P Date 2015-03-10 Cont ID  
Sent By sgraham Date 2015-03-10 Time 15:41 Rev Time 0.00
Received By sgraham Date 2015-03-10 Time 15:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2014-12-24 Cont ID  
Sent By sgraham Date 2014-12-24 Time 09:01 Rev Time 0.00
Received By sgraham Date 2014-12-24 Time 09:01 Sent To  
Notes
2014-12-24 09:02:4112/24/14 THE OWNER REMOVED THE CARPORT ADDITION FROM
 THE PLANS, COULD NOT MAKE SIDE SETBACKS.

Review Stop Z ZONING
Rev No 4 Status F Date 2014-12-23 Cont ID  
Sent By sgraham Date 2014-12-23 Time 13:40 Rev Time 0.00
Received By sgraham Date 2014-12-23 Time 13:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2014-12-11 Cont ID  
Sent By sgraham Date 2014-12-11 Time 15:18 Rev Time 0.00
Received By sgraham Date 2014-12-11 Time 15:18 Sent To  
Notes
2014-12-11 15:19:5012/11/14 ZONING FAILED
  
 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY

Review Stop Z ZONING
Rev No 2 Status F Date 2014-12-01 Cont ID  
Sent By sgraham Date 2014-12-01 Time 16:00 Rev Time 0.00
Received By sgraham Date 2014-12-01 Time 16:00 Sent To  
Notes
2014-12-01 16:01:3712/1/14 ZONING FAILED
  
 1. PROVIDE TWO UP TO DATE SURVEYS SHOWING THE LOCATIONS
 OF NEW ADDITIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-10-27 Cont ID  
Sent By sgraham Date 2014-10-27 Time 15:01 Rev Time 0.00
Received By sgraham Date 2014-10-27 Time 15:01 Sent To  
Notes
2014-10-27 15:02:0510/27/14 ZONING FAILED.
  
 1. PROVIDE TWO UP TO DATE SURVEYS