Plan Review Details - Permit 14100612
Plan Review Stops For Permit 14100612
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-01-21 Cont ID  
Sent By   Date 2015-01-21 Time 13:15 Rev Time 0.00
Received By   Date 2015-01-21 Time 12:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-01-06 Cont ID  
Sent By jwitmer Date 2015-01-06 Time 15:28 Rev Time 0.00
Received By jwitmer Date 2015-01-06 Time 15:13 Sent To  
Notes
2015-01-06 15:17:55BUILDING PLAN REVIEW
 REVISION: 14100612
 PERMIT: 13120617
 ADD: 2905 45TH ST.
 CONT: GEORGE & ASSOCIATES CONTRACTORS, INC.
 TEL: (772)332-3675
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES.JAN. 06/2015
 ACTION: DENIED
  
 1) THE COVER SHEET STILL SHOWS A SWING DOOR ON THE
 PRIVATE DOOR # 208. 2010 FBC-B 1014.2 EGRESS THROUGH
 INTERVENING SPACES. EGRESS THROUGH INTERVENING SPACES
 SHALL COMPLY WITH THIS SECTION. (2) AN EXIT ACCESS
 SHALL NOT PASS THROUGH A ROOM THAT CAN BE LOCKED TO
 PREVENT EGRESS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-04 Cont ID  
Sent By JWITMER Date 2014-12-04 Time 11:27 Rev Time 0.00
Received By jwitmer Date 2014-12-04 Time 10:45 Sent To  
Notes
2014-12-04 11:27:49BUILDING PLAN REVIEW
 REVISION: 14100612
 PERMIT: 13120617
 ADD: 2905 45TH ST.
 CONT: GEORGE & ASSOCIATES CONTRACTORS, INC.
 TEL: (772)332-3675
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. DEC. 04/2014
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET A2.1 2010 FBC-B 1014.2 EGRESS
 THROUGH INTERVENING SPACES. EGRESS THROUGH INTERVENING
 SPACES SHALL COMPLY WITH THIS SECTION. (2) AN EXIT
 ACCESS SHALL NOT PASS THROUGH A ROOM THAT CAN BE LOCKED
 TO PREVENT EGRESS.
  
 2) 2ND REQUEST. SHEET A2.1. CORRIDOR 205 HAS A RAMP UP
 TO UPPER PORTION OF FLOOR, THE LATCH SIDE OF DOOR 206
 IS LESS THAN 24 INCHES FROM THE EDGE OF THE RAMP. PLESE
 SEE 2010 FL. ACC. CODE FIGURE 404.2.4.1 (J) LATCH
 APPROACH LATCH SIDE.
  
 3) 2ND REQUEST WILL NEED TO COMPLY. SHEET A2.1 NEW WALL
 WILL BE REQUIRED( SEE COMMENT # 1) CONNECTING THE
 CORRIDOR TO THE LOCKER ROOM AND DOOR 209. IF THIS IS TO
 BE AN EXTENSION OF THE CORRIDOR THE MINIMUM WIDTH OF
 THE CORRIDOR WOULD HAVE TO BE 48" SEE FL ACC. CODE
 FIGURE 404.2.4.1 (G). CAN NOT EGRESS THROUGH LOCKABLE
 DOORS.1014.2(2) 2. AN EXIT ACCESS SHALL NOT PASS
 THROUGH A ROOM THAT CAN BE LOCKED TO PREVENT EGRESS.
  
 4)2ND REQUEST, MISSING SHEETS A3.0 & S2.0 THESE SHEETS
 WERE IN THE LAST SET OF REVISION DRAWINGS. SHEET A3.0
 DETAIL # 6 RAMP SECTION ALSO INDICATES THE CUTTING OF
 THE CEILING FRAMING MEMBERS TO GAIN HEIGHT IN THIS
 AREA. WHAT TYPE OF FRAMING MENBERS ARE THEY AND HOW
 WILL THE MODIFICATION BE MADE? IDENITFY THE TOP OF
 FRAMING THAT HAS TO BE MODIFIED. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-06 Cont ID  
Sent By JWITMER Date 2014-11-06 Time 17:27 Rev Time 0.00
Received By jwitmer Date 2014-11-06 Time 16:05 Sent To  
Notes
2014-11-06 17:21:30BUILDING PLAN REVIEW
 REVISION: 14100612
 PERMIT: 13120617
 ADD: 2905 45TH ST.
 CONT: GEORGE & ASSOCIATES CONTRACTORS, INC.
 TEL: (772)332-3675
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 06/2014
 ACTION: DENIED
  
 1) SHEET A2.1 LEFT SIDE OF PAGE ROOMS 206, 207 & 208
 ARE RED LINED AS TO A DIFFERENT LOCATION AS SHOWN ON
 PLANS. THEY ARE NOT SIGNED NOR DATED BY THE DESINGNER
 OF RECORD AS A CHANGE OF LOCATION. 107.2.1.3 ADDITIONAL
 INFORMATION. PLEASE PROVIDE A LIFE SAFETY PLAN FOR THE
 AREA BEING RECONFIGURED IT APPEARS THE EGRESS TO
 ENCLOSED STAIRWELL IS GOING THROUGH ADJOINING ROOMS
 THAT ARE LOCKABLE.
  
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION. (2) AN EXIT ACCESS SHALL NOT PASS THROUGH
 A ROOM THAT CAN BE LOCKED TO PREVENT EGRESS.
  
 2) SHEET A2.1. CORRIDOR 205 HAS A RAMP UP TO UPPER
 PORTION OF FLOOR, THE LATCH SIDE OF DOOR 206 IS LESS
 THAN 24 INCHES FROM THE EDGE OF THE RAMP. PLESE SEE
 2010 FL. ACC. CODE FIGURE 404.2.4.1 (J) LATCH APPROACH
 LATCH SIDE.
  
 3) SHEET A2.1 THE RED LINED PLANS APPEAR TO HAVE A NEW
 WALL CONNECTING THE CORRIDOR TO THE LOCKER ROOM AND
 DOOR 209. IF THIS IS TO BE AN EXTENSION OF THE CORRIDOR
 THE MINIMUM WIDTH OF THE CORRIDOR WOULD HAVE TO BE 48"
 SEE FL ACC. CODE FIGURE 404.2.4.1 (G).
  
 4) SHEET A3.0 DETAIL # 6 RAMP SECTION ALSO INDICATES
 THE CUTTING OF THE CEILING FRAMING MEMBERS TO GAIN
 HEIGHT IN THIS AREA. WHAT TYPE OF FRAMING MENBERS ARE
 THEY AND HOW WILL THE MODIFICATION BE MADE? IDENITFY
 THE TOP OF FRAMING THAT HAS TO BE MODIFIED. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-01-22 Cont ID  
Sent By rlecky Date 2015-01-22 Time 10:43 Rev Time 0.00
Received By rlecky Date 2015-01-22 Time 10:37 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-01-06 Cont ID  
Sent By rlecky Date 2015-01-06 Time 11:09 Rev Time 0.00
Received By rlecky Date 2015-01-06 Time 11:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-23 Cont ID  
Sent By RLECKY Date 2014-12-23 Time 10:41 Rev Time 0.00
Received By dhayes Date 2014-12-23 Time 10:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-21 Cont ID  
Sent By SKENNEDY Date 2014-10-21 Time 13:59 Rev Time 0.00
Received By rlecky Date 2014-10-21 Time 13:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2015-01-20 Cont ID  
Sent By pleduc Date 2015-01-20 Time   Rev Time 0.00
Received By pleduc Date 2015-01-16 Time 16:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2014-12-31 Cont ID  
Sent By pleduc Date 2014-12-31 Time   Rev Time 0.00
Received By pleduc Date 2014-12-31 Time 13:50 Sent To  
Notes
2014-12-31 14:20:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PREVIOUS COMMENTS FROM FIRE PREVENTION HAVE NOT
 BEEN ADDRESSED.
  
 EXITING THROUGH PRIVATE ROOM 208 IS NOT APPROVED. THE
 EXIT HALLWAY/CORRIDOR SHALL BE CONTINUED TO THE LOCKER
 ROOM DOOR.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-11-25 Cont ID  
Sent By PLEDUC Date 2014-11-25 Time   Rev Time 0.00
Received By pleduc Date 2014-11-25 Time 11:52 Sent To  
Notes
2014-11-25 12:24:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PREVIOUS COMMENTS FROM FIRE PREVENTION HAVE NOT
 BEEN ADDRESSED.
  
 EXITING THROUGH PRIVATE ROOM 208 IS NOT APPROVED. THE
 HALLWAY SHALL BE CONTINUED TO THE LOCKER ROOM DOOR.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-23 Cont ID  
Sent By WJOLIN Date 2014-10-23 Time   Rev Time 0.00
Received By pleduc Date 2014-10-23 Time 12:47 Sent To  
Notes
2014-10-23 16:59:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 A LIFE SAFETY PLAN WAS NOT SUBMITTED WITH THIS PLAN.
 THE LIFE SAFETY PLAN SHALL INCLUDE THE OCCUPANCY LOADS,
 EXIT PATHS WITH OCCUPANY LOADS, TRAVEL DISTANCES, ALL
 EXIT SIGNS, EXITS, EMERGENCY LIGHTS, FIRE EXTIGUISHER
 LOCATIONS. IT IS EXTREMELY IMPORTANT TO KNOW AND
 UNDERSTAND HOW PEOPLE AND HOW MANY PEOPLE WILL BE USING
 EACH EXIT AND GETTING OUT OF THIS MEZZANINE SPACE IN
 THE EVENT OF A FIRE.
  
 SHEET A 2-1, THE PROPOSED REAR EXITING THROUGH PRIVATE
 ROOM 208 IS NOT APPROVED. THE 4'6" CORRIDOR SHALL BE
 CONTINUED TO THE LOCKER ROOM DOOR. IT IS RECOMMENDED
 THAT THE ROOMS BE SHIFTED TO ALLOW THIS HALLWAY
 CONFIGUATION. (AS HAND DRAWN ON ONE OF SHEET PLANS)
  
 SHEET CRV UNDER GENERAL NOTES, REFERENCE SHALL BE MADE
 THAT A FIRE ALRM IS REQUIRED AND FOR THE FUTURE
 SUBMITTAL SHOP DRAWINGS.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-01-23 Cont ID  
Sent By tklarge Date 2015-01-23 Time 14:23 Rev Time 0.00
Received By tklarge Date 2015-01-12 Time 16:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-06 Cont ID  
Sent By jwitmer Date 2015-01-06 Time 15:18 Rev Time 0.00
Received By jwitmer Date 2014-12-30 Time 14:07 Sent To  
Notes
2014-12-30 14:07:55SENT TO B17

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-30 Cont ID  
Sent By skennedy Date 2014-12-30 Time 11:19 Rev Time 0.00
Received By skennedy Date 2014-11-21 Time 10:11 Sent To  
Notes
2014-11-22 10:11:58B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-06 Cont ID  
Sent By jwitmer Date 2014-11-06 Time 17:27 Rev Time 0.00
Received By jwitmer Date 2014-10-20 Time 17:51 Sent To  
Notes
2014-10-20 17:52:02REVISION SENT TO B13 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-01-22 Cont ID  
Sent By hmoser Date 2015-01-22 Time 11:05 Rev Time 0.00
Received By hmoser Date 2015-01-22 Time 11:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-12-30 Cont ID  
Sent By hmoser Date 2014-12-30 Time 15:10 Rev Time 0.00
Received By hmoser Date 2014-12-30 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-12-30 Cont ID  
Sent By HMOSER Date 2014-12-30 Time 11:19 Rev Time 0.00
Received By skennedy Date 2014-12-30 Time 11:18 Sent To  
Notes
2014-12-30 11:20:10PREVIOUSLY PASSED BY HMOSER. APPLICANT NEEDS TO INSERT
 APPROVED PAGES INTO RE-SUBMITTAL. SAK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-11-04 Cont ID  
Sent By JWITMER Date 2014-11-04 Time 12:46 Rev Time 0.00
Received By hmoser Date 2014-11-04 Time 09:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2015-01-23 Cont ID  
Sent By tklarge Date 2015-01-23 Time 14:23 Rev Time 0.00
Received By tklarge Date 2015-01-23 Time 13:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-01-05 Cont ID  
Sent By tklarge Date 2015-01-05 Time 09:18 Rev Time 0.00
Received By tklarge Date 2015-01-05 Time 09:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-11-27 Cont ID  
Sent By TKLARGE Date 2014-11-27 Time 03:45 Rev Time 0.00
Received By tklarge Date 2014-11-27 Time 07:43 Sent To  
Notes
2014-11-27 07:52:481) THE SHOWER SHALL BE HANDICAPPED ACCESSIBLE PER THE
 2010 FL. ACCESSIBILITY CODE SECS. 213.3.6 & 608 ,
 309.4. SUBMIT ALL DETAILS. 2ND REQUEST.
 2) SHT. P0-1 - SECTION 905.3 2010 FPC - VENT CONNECTION
 TO DRAINAGE SYSTEM - EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. 2ND REQUEST.
 3) SIZE THE VENT FOR THE SHOWER ON THE PLAN.COMPLY
 W/FPC SEC.916.1 & TABLE 906.1 OF THE 2010 FPC.2ND
 REQUEST.
 4) MEP PLANS SHALL BE SIGNED & SEALED BY THE DESIGN
 PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE RULE
 61G15-23.001 & 23.002.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-11-01 Cont ID  
Sent By tklarge Date 2014-11-01 Time 04:41 Rev Time 0.00
Received By tklarge Date 2014-11-01 Time 04:32 Sent To  
Notes
2014-11-01 04:41:281) THE SHOWER SHALL BE HANDICAPPED ACCESSIBLE PER THE
 2010 FL. ACCESSIBILITY CODE SECS. 213.3.6 & 608 ,
 309.4. SUBMIT ALL DETAILS.
 2) SHT. P0-1 - SECTION 905.3 2010 FPC - VENT CONNECTION
 TO DRAINAGE SYSTEM - EVERY DRY VENT CONNECTING TO A
 HORIZONTAL DRAIN SHALL CONNECT ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE.
 3) SIZE THE VENT FOR THE SHOWER ON THE PLAN.COMPLY
 W/FPC SEC.916.1 & TABLE 906.1 OF THE 2010 FPC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  