 |
Plan Review Details - Permit 14100419
| Plan Review Stops For Permit 14100419 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2015-08-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-05 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-05 |
Time |
14:19 |
Sent To |
E |
|
| Notes |
| 2015-08-05 16:25:45 | W. P. B. BUILDING PLAN REVIEW | | | REVISION: 14100419 | | | MASTER: 14060978 | | | ADD: 1501 NORTHPOINT PARKWAY # 100 | | | CONT:DAVID JOYNER CONSTRUCTION | | | TEL: (561)965-3795 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 5TH REVIEW | | | DATE: WED. AUG. 05/2015 | | | ACTION: BUILDING PROVISO: | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) DETAIL # 1/ 2.1 INDICATES THE OCCUPANCY WALL BETWEEN | | | THE BUSINESS OCCUPANCY AND STORAGE OCCUPANCY. THE | | | COVERSHEET STATES THERE IS A MIXED USE OCCUPANCY | | | BUSINESS AND S-1 MODERATE HAZARD PROVIDE A REVISION | | | PROVIDING THE WALL ASSEMBLY EITHER A UL LISTING OR | | | GYPSUM ASSOCIATION NUMBER. 2010 FBC-B TABLE 508.4 & | | | 508.4.4.1 CONSTRUCTION. REQUIRED SEPARATIONS SHALL BE | | | FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION | | | 707 AS TO COMPLETELY SEPARATE ADJACENT OCCUPANCIES. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-23 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-23 |
Time |
06:46 |
Sent To |
|
|
| Notes |
| 2015-06-23 07:32:02 | W. P. B. BUILDING PLAN REVIEW | | | REVISION: 14100419 | | | PERMIT: 14060978 | | | ADD: 1501 NORTHPOINT PARKWAY # 100 | | | CONT:DAVID JOYNER CONSTRUCTION | | | TEL: (561)965-3795 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 4TH REVIEW | | | DATE: TUES. JUNE 23/2015 | | | ACTION: DENIED | | | | | | 1-8) COMPLIED. | | | | | | 9) THE PLANS FROM COGAN WIRE AND METAL PRODUCTS HAS | | | NOTES: | | | 9A) 3RD REQUEST. THE RESPONSE INDICATES THE STRUCTURAL | | | ENGINEER HAS REVIEWED THE LOADING OF THE SLAB, PLEASE | | | PROVIDE THE ENGINEERS LETTER SIGNED AND SEALED DOCUMENT | | | STATING SUCH. THE MAXIMUM UNFACTORED AXIAL LOAD APPLIED | | | ON THE SLAB BY A COLUMN IS 26,600 LBS. | | | | | | 9B) 3RD REQUEST. RESPONSE IS THE OWNER HAS OBTAINED THE | | | SERVICES OF A REGISTERED ENGINEER FOR THIS ANALYSIS. | | | PLEASE PROVIDE THE SIGNED AND SEALED DOCUMENT FOR THE | | | STRUCTURAL ANALYSIS ON THE SLAB AND OR FOUNDATION. | | | THE CAPACITY OF THE SLAB AND OR FOUNDATION MUST BE | | | VERIFIED BY THE CLIENT AND OR THE OWNER. | | | | | | 10) COMPLIED. | | | | | | 11) NEW COMMENT FROM 3RD REVIEW, THE COVERSHEET STATES | | | THERE IS A MIXED USE OCCUPANCY BUSINESS AND S-1 | | | MODERATE HAZARD YET THERE IS NO OCCUPANCY SEPARATION | | | BETWEEN THE 2 OCCUPANCIES. THERE SHOULD BE A (1) HOUR | | | FIRE SEPARATION BETWEEN THE 2 OCCUPANCIES. SEE TABLE | | | 508.4, THIS TABLE HAS BEEN BACKWARDS ON THE S1/ S2 | | | CLASSIFICATION SINCE THE CONCEPTION OF THIS TABLE IN | | | THE 2007 FBC-B. PLEASE SEE BOAF INFORMAL INTERPRETATION | | | 7357 JULY 1/2014. | | | | | | 12) COMPLIED. | | | | | | 13) BUILDING PROVISO: NEW COMMENT FROM 3RD REVIEW. | | | PLEASE BE ADVISED REVISIONS WILL ALSO BE REQUIRED | | | BECAUSE OF SITE VIOLATIONS FOUND BY FIELD VISITS FROM | | | BOTH THE FIRE DEPARTMENT AND BUILDING DEPARTMENT. | | | | | | 14) THE NEW 2ND FLOOR AREA OF 2,668 SQ, FT, WILL NEED | | | TO BE REVIEWED BY PAL BEACH COUNTY IMPACT FEE OFFICE. | | | IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERRMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2015-06-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-12 |
Time |
17:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-11 |
Time |
06:31 |
Sent To |
|
|
| Notes |
| 2015-06-12 17:58:54 | W. P. B. BUILDING PLAN REVIEW | | | REVISION: 14100419 | | | PERMIT: 14060978 | | | ADD: 1501 NORTHPOINT PARKWAY # 100 | | | CONT:DAVID JOYNER CONSTRUCTION | | | TEL: (561)965-3795 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 3RD REVIEW | | | DATE: FRI. JUNE 12/2015 | | | ACTION: DENIED | | | | | | 1-6) COMPLIED. | | | | | | 7) THE NEW PLANS SHOW A TRUE STEEL FRAMED SECOND FLOOR, | | | STAIRS GUARDRAIL & HANDRAIL ASSEMBLY. THIS TYPE OF | | | BUILDING REQUIRES A ON-SITE RESIDENT INSPECTOR. | | | | | | 7A) COMPLIED. 2010 WEST PALM BEACH AMENDMENTS TO THE | | | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, | | | 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING | | | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE | | | INSPECTIONS REQUIRED BY SECTION 109. RESIDENT INSPECTOR | | | FORMS RETURNED FILLED OUT. | | | | | | 7B)SEMI-COMPLIED. 3RD REQUEST. . THE RESUME' MUST BE | | | ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN. | | | FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' OF | | | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' | | | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED | | | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL | | | REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN | | | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | CONTACT KEN CONRAD | | | TEL: 561-805-6666 | | | E-MAIL: [email protected] | | | | | | 7C)3RD REQUEST. RESPONSE INDICATES THE ABOVE | | | INFORMATION HAS BEEN SUBMITTED BY THE RESIDENT | | | INSPECTOR ENGINEER. NOT IN THE PACKAGE | | | THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY | | | FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE SUBMITTED TO | | | KEN CONRAD BY E-MAIL. KEN CONRAD: [email protected] | | | RESIDENT INSPECTOR FORMS WILL BE E-MAILED TO: | | | [email protected] | | | | | | 7D) 3RD REQUEST. PLEASE NOTE(3) SETS OF PLANS ARE | | | REQUIRED. THERE IS (2) REVISED DENIED PLANS DATED | | | 3/26/15 BY ARCHITECT JAMES STORM, ONE SET OF THE | | | CONTRACTORS ISSUED PLANS WHY WERE THEY SUBMITTED, THEY | | | ARE TO REMAIN AT THE JOBSITE FOR INSPECTION PURPOSES. | | | NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED. | | | FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT | | | LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH | | | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF | | | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE | | | RESIDENT INSPECTOR, THE OTHER FOR THE MEP INSPECTORS. | | | | | | 7E) NOTICE ONLY!!! PLEASE CALL THE CITY OF WEST PALM | | | BEACHES? AUTOMATED TELEPHONE INSPECTIONS LINE (561) | | | 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF | | | JOBSITE INSPECTIONS. | | | | | | 8) COMPLIED. THE SUBMITTED 2ND FLOOR STRUCTURAL PLAN BY | | | COGAN WIRE & METAL PRODUCTS HAS NOT BEEN REVIEWED BY | | | THE DESIGNER OF RECORD, WILL REQUIRE THERE SHOP DRAWING | | | STAMP OF APPROVAL. FL 61G1-23.015 (2) THE ARCHITECT IS | | | RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT | | | DATA, REPORTS, SHOP DRAWINGS ETC... | | | | | | 9) THE PLANS FROM COGAN WIRE AND METAL PRODUCTS HAS | | | NOTES: | | | 9A) 3RD REQUEST. THE RESPONSE INDICATES THE STRUCTURAL | | | ENGINEER HAS REVIEWED THE LOADING OF THE SLAB, PLEASE | | | PROVIDE THE ENGINEERS LETTER SIGNED AND SEALED DOCUMENT | | | STATING SUCH. THE MAXIMUM UNFACTORED AXIAL LOAD APPLIED | | | ON THE SLAB BY A COLUMN IS 26,600 LBS. | | | | | | 9B) 3RD REQUEST. RESPONSE IS THE OWNER HAS OBTAINED THE | | | SERVICES OF A REGISTERED ENGINEER FOR THIS ANALYSIS. | | | PLEASE PROVIDE THE SIGNED AND SEALED DOCUMENT FOR THE | | | STRUCTURAL ANALYSIS ON THE SLAB AND OR FOUNDATION. | | | THE CAPACITY OF THE SLAB AND OR FOUNDATION MUST BE | | | VERIFIED BY THE CLIENT AND OR THE OWNER. | | | | | | 10) COMPLIED. ALL SHOP DRAWINGS THAT WILL DEAL WITH THE | | | STEEL 2ND FLOOR AND SUPPORTING SYSTEM ARE REQUIRED TO | | | BE REVIEWED BY THE DESIGNER OF RECORD BEFORE SUBMITTAL | | | TO THE BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE | | | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING | | | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... | | | 11) NEW COMMENT, THE COVERSHEET STATES THERE IS A MIXED | | | USE OCCUPANCY BUSINESS AND S-1 MODERATE HAZARD YET | | | THERE IS NO OCCUPANCY SEPARATION BETWEEN THE 2 | | | OCCUPANCIES. THERE SHOULD BE A (1) HOUR FIRE SEPARATION | | | BETWEEN THE 2 OCCUPANCIES. SEE TABLE 508.4, THIS TABLE | | | HAS BEEN BACKWARDS ON THE S1/ S2 CLASSIFICATION SINCE | | | THE CONCEPTION OF THIS TABLE IN THE 2007 FBC-B. PLEASE | | | SEE BOAF INFORMAL INTERPRETATION 7357 JULY 1/2014. | | | 12) NEW COMMENT. THE NEW STORAGE OCCUPANCY 2ND FLOOR, | | | PLEASE PROVIDE FROM THE TRAVEL DISTANCE FROM THE MOST | | | REMOTE POINT OF THE 2ND FLOOR STORAGE OCCUPANCY, DOWN | | | THE OPEN STAIRS AND OUT OF THE BUILDING TO THE EXIT | | | DISCHARGE PER FBC-B 1016.1 EXCEPTION 4 AND TABLE | | | 1016.1. | | | 13) NEW COMMENT. PLEASE BE ADVISED REVISIONS WILL ALSO | | | BE REQUIRED BECAUSE OF SITE VIOLATIONS FOUND BY FIELD | | | VISITS FROM BOTH THE FIRE DEPARTMENT AND BUILDING | | | DEPARTMENT. | | | 14) THE NEW 2ND FLOOR AREA OF 2,668 SQ, FT, WILL NEED | | | TO BE REVIEWED BY PAL BEACH COUNTY IMPACT FEE OFFICE. | | | IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERRMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-04-06 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-04-06 |
Time |
08:38 |
Sent To |
|
|
| Notes |
| 2015-04-06 11:03:53 | W. P. B. BUILDING PLAN REVIEW | | | REVISION: 14100419 | | | PERMIT: 14060978 | | | ADD: 1501 NORTHPOINT PARKWAY # 100 | | | CONT:DAVID JOYNER CONSTRUCTION | | | TEL: (561)965-3795 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: MON. APRIL 06/2015 | | | ACTION: DENIED | | | | | | 1-6) COMPLIED. | | | | | | 7) THE NEW PLANS SHOW A TRUE STEEL FRAMED SECOND FLOOR, | | | STAIRS GAURDRAIL & HANDRAIL ASSEMBLY. THIS TYPE OF | | | BUILDING REQUIRES A ON-SITE RESIDENT INSPECTOR. | | | | | | 7A) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER | | | INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, | | | OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED | | | BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS | | | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER | | | INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR | | | QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED | | | FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT | | | BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING | | | AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE. | | | THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY | | | AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES: | | | | | | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II | | | CONSTRUCTION | | | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS | | | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE | | | STRENGTH (F ?C) IN EXCESS OF 3000 | | | POUNDS PER SQUARE INCH | | | 4. FOR PILE DRIVING | | | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE | | | FOOT | | | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT | | | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR | | | METHODS OF CONSTRUCTION | | | | | | 7B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME' | | | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE | | | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS | | | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE | | | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, | | | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | CONTACT KEN CONRAD | | | TEL: 561-805-6666 | | | E-MAIL: [email protected] | | | | | | 7C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR | | | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE | | | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: | | | [email protected] | | | RESIDENT INSPECTOR FORMS WILL BE E-MAILED TO: | | | [email protected] | | | | | | 7D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE | | | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE | | | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND | | | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO | | | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR | | | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP | | | INSPECTORS. | | | | | | 7E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED | | | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR | | | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE | | | INSPECTIONS. | | | | | | 8) THE SUBMITTED 2ND FLOOR STRUCTURAL PLAN BY COGAN | | | WIRE & METAL PRODUCTS HAS NOT BEEN REVIEWED BY THE | | | DESIGNER OF RECORD, WILL REQUIRE THERE SHOP DRAWING | | | STAMP OF APPROVAL. FL 61G1-23.015 (2) THE ARCHITECT IS | | | RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT | | | DATA, REPORTS, SHOP DRAWINGS ETC... | | | | | | 9) THE PLANS FROM COGAN WIRE AND METAL PRODUCTS HAS | | | NOTES: | | | 9A) THE MAXIMUM UNFACTORED AXIAL LOAD APPLIED ON THE | | | SLAB BY A COLUMN IS 26,600 LBS. | | | | | | 9B) THE CAPACITY OF THE SLAB AND OR FOUNDATION MUST BE | | | VERIFIED BY THE CLIENT AND OR THE OWNER. | | | | | | 10) ALL SHOP DRAWINGS THAT WILL DEAL WITH THE STEEL 2ND | | | FLOOR AND SUPPORTING SYSTEM ARE REQUIRED TO BE REVIEWED | | | BY THE DESIGNER OF RECORD BEFORE SUBMITTAL TO THE | | | BUILDING DEPARTMENT. FL 61G1-23.015 (2) THE ARCHITECT | | | IS RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL | | | PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... | | | | | | 11) THE NEW 2ND FLOOR AREA OF 2,668 SQ, FT, WILL NEED | | | TO BE REVIEWED BY PAL BEACH COUNTY IMPACT FEE OFFICE. | | | IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. | | | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-10-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-10-29 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-10-29 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2014-10-29 15:08:55 | BUILDING PLAN REVIEW | | | REVISION: 14100419 | | | PERMIT: 14060978 | | | ADD: 1501 NORTHPOINT PARKWAY # 100 | | | CONT:DAVID JOYNER CONSTRUCTION | | | TEL: (561)965-3795 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: WED. OCT. 29/ 2014 | | | ACTION: DENIED | | | | | | 1) THE REVISION FORM & PLANS INDICATE THE ADDITIONAL | | | WORK TO BE COVERED UNDER THIS PERMIT AS ADDING (2) | | | MEZZANINES IN (2) A/C ROOMS. PLEASE PROVIDE A OVER ALL | | | FLOOR PLAN WHERE THESE MEZZANINES WILL BE ADDED. PLEASE | | | ALSO CLARIFY THE USAGE OF THE (2) A/C ROOMS WHERE THE | | | MEZZANINES WILL BE ADDED. | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE | | | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL. | | | | | | 2) THE FLOOR PLAN SHALL SHOW THE ROOM IN WHICH THE | | | MEZZANINES ARE TO BE BUILT, PLEASE PROVIDE CODE | | | COMPLIANCE WITH 2010 FBC-B 505.2 AREA LIMITATIONS AND | | | IF EXCEPTION 1 OR 2 ARE BEING TAKEN , THIS BEING A | | | BUILDING TYPE IIA/ SPRINKLERED. | | | | | | 3) PLEASE PROVIDE THE OCCUPANCY TYPE AND OCCUPANCY | | | LOADS FOR EACH MEZZANINE AREA COMPLY WITH 2010 FBC-B | | | 505.3. | | | | | | 4) THE PLANS CURRENTLY DO NOT PROVIDE ENOUGH DETAIL FOR | | | WITHIN THE ROOMS TO SHOW COMPLIANCE WITH 2010 FBC-B | | | 505.4. | | | | | | 5) THE BUILDING THE MEZZANINE IS GOING TO BE INSTALLED | | | IN IS A FIRE SPRINKLERED BUILDING ARE THERE GOING TO | | | HAVE FIRE SPRINKLERS UNDER THE MEZZANINE LEVEL TO | | | PROTECT THE FIRE LOADS BELOW THE MEZZANINE? F] 505.5.2 | | | FIRE SUPPRESSION. | | | WHERE LOCATED IN A BUILDING THAT IS REQUIRED TO BE | | | PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM, EQUIPMENT | | | PLATFORMS SHALL BE FULLY PROTECTED BY SPRINKLERS ABOVE | | | AND BELOW THE PLATFORM, WHERE REQUIRED BY THE STANDARDS | | | REFERENCED IN SECTION 903.3. | | | | | | 6) THE PLANS (14060978) INDICATE THIS TO BE A BUILDING | | | TYPE IIA BUILDING, PLEASE SHOW HOW COMPLIANCE WILL BE | | | ACHIEVED WITH TABLE 601 FIRE-RESISTANCE RATING | | | REQUIREMENTS FOR BUILDING ELEMENTS (HOURS), FLOOR | | | CONSTRUCTION AND SECONDARY MEMBERS. | | | | | | PLEASE NOTE THE PLANS DO INDICATE BOTH THE FLOOR AND | | | LANDING ARE OPEN BAR GRATING IF THE MEZZANINE IS LARGER | | | THAN ALLOWED BY 505.2 THE DESIGNER OF RECORD MAY WANT | | | TO ASK THE BUILDING OFFICIAL TO CONSIDER THIS UNDER | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION 104.11 ALTERNATIVE | | | MATERIALS, DESIGN AND METHODS OF CONSTRUCTION AND | | | EQUIPMENT. THE PROVISIONS OF THIS CODE ARE NOT INTENDED | | | TO PREVENT THE INSTALLATION OF ANY MATERIAL OR TO | | | PROHIBIT ANY DESIGN OR METHOD OF CONSTRUCTION NOT | | | SPECIFICALLY PRESCRIBED BY THIS CODE, PROVIDED THAT | | | ANY SUCH ALTERNAT IVE HAS BEEN APPROVED. AN ALTERNATIVE | | | MATERIAL, DESIGN OR METHOD OF CONSTRUCTION SHALL BE | | | APPROVED WHERE THE BUILDING OFFICIAL FINDS THAT THE | | | PROPOSED DESIGN IS SATISFACTORY AND COMPLIES WITH THE | | | INTENT OF THE PROVISIONS OF THIS CODE, AND THAT THE | | | MATERIAL, METHOD OR WORK OFFERED IS, FOR THE PURPOSE | | | INTENDED, AT LEAST THE EQUIVALENT OF THAT PRESCRIBED IN | | | THIS CODE IN QUALITY, STRENGTH, EFFECTIVENESS, FIRE | | | RESISTANCE, DURABILITY AND SAFETY. WHEN ALTERNATE LIFE | | | SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING GUIDE | | | TO PERFORMANCE-BASED FIRE PROTECTION ANALYSIS AND | | | DESIGN OF BUILDINGS, OR OTHER METHODS APPROVED BY THE | | | BUILDING OFFICIAL MAY BE USED. THE BUILDING OFFICIAL | | | SHALL REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF BE | | | SUBMITTED TO SUBSTANTIATE ANY CLAIM MADE REGARDING THE | | | ALTERNATIVE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-08-14 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-08-14 |
Time |
12:25 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-08-14 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2015-06-25 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-06-25 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-06-03 |
Time |
14:09 |
Sent To |
|
|
| Notes |
| 2015-06-25 10:18:01 | 6/25/2015 | | | PROJECT: NORTHPOINT SUITE 100 | | | PERMIT#: 14100419 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | | COMMENTS: | | | | | | 1) DUPLICATE COMMENT: 1ST FLOOR | | | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT | | | (EMERGENCY AND EXIT LIGHTING) SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA | | | AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 700.12 | | | THE NOTE WAS ADDED TO PG 6.1 HOWEVER THERE IS STILL A | | | CONFLICT. CIRCUIT 1 ON PANEL SCHEDULE PANEL HA IS | | | IDENTIFIED AS THE NIGHT LIGHT CIRCUIT. | | | THE 1ST FLOOR PLAN INDICATE CIRCUIT HA1 IS THE CIRCUIT | | | TO BE USED TO ENERGIZE EMERGENCY AND EXIT LIGHTING AND | | | THE GENERAL LIGHTING IN THAT SAME AREA IS IDENTIFIED AS | | | CIRCUIT HA26 A LIGHTS AND HA28 B LIGHHTS. | | | | | | 2) 2ND FLOOR: | | | EMERGENCY AND EXIT LIGHTING HAS BEEN ADDED BUT THE | | | CIRCUITRY TO FEED IT IS NOT CLEAR. THE LIGHTING | | | CIRCUITS ARE IDENTIFIED ON THE FLOOR PLAN BUT THE | | | EMERGENCY AND EXIT LIGHTS CIRCUITS ARE NOT IDENTIFED | | | ANYWHERE EXCEPT IN PANEL HA AS CIRCUIT HA1 WHICH IS NOT | | | EVEN THE SAME SYSTEM VOLTAGE LET ALONE THE SAME | | | CIRCUIT. CLARIFY WHAT CIRCUITS ARE INTENDED TO FEED | | | LIGHTING AND THE EMERGENCY AND EXIT EGRESS FIXTURES. | | | | | | 3) THE DRINKING FOUNTAIN IS IDENTIFIED AS CIRCUIT LD | | | 22. ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH | | | GROUND FAULT CIRCUIT INTERRUPTER PROTECTION. NEC | | | 422.52. | | | INDICATE ON THE PLAN THIS CIRCUIT IS PROTECTED WITH A | | | GFCI DEVICE. | | | | | | 4) MODULAR FURNITURE CUBICALS HAVE BEEN ADDED TO THE | | | FLOOR PLAN. INDICATE THE CIRCUITS FEEDING THE MODULAR | | | FURNITURE IS INSTALLED IN COMPLIANCE WITH THE NEC 605 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-04-10 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-04-10 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-04-10 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2015-04-10 13:17:13 | 1) SEE FIRE DEPT. COMMENTS REGARDING EMERGENCY | | | LIGHTING. | | | 2) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL | | | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. NEC 700.12 | | | 4) EMERGENCY LIGHTING SYSTEMS SHALL BE DESIGNED AND | | | INSTALLED SO THAT THE FAILURE OF ANY INDIVIDUAL | | | LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF A LAMP, | | | CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT REQUIRES | | | EMERGENCY ILLUMINATION. NEC 700.16 | | | 5) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2015-06-24 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-06-24 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-06-03 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2015-04-09 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2015-04-09 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2015-04-08 |
Time |
16:19 |
Sent To |
E |
|
| Notes |
| 2015-04-09 16:33:20 | 1501 NORTHPOINT PARKWAY, SUITE #100 | | | TRACKING #14100419 | | | MASTER #14060978 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | NOTE: A SITE VISIT WAS PERFORMED 04/09/15 | | | | | | | | | PER NFPA 101 CHAPTER 39 - EXISTING BUSINESS OCCUPANCIES | | | THE TWO STAIR CASES LOCATED IN THE BUSINESS (OFFICE | | | AREAS) OCCUPANCY WILL NEED TO BE COMPLETELY ENCLOSED | | | TOP/BOTTOM BY A 1-HOUR FIRE RATING WITH FIRE RATED | | | OPENINGS/DOORS PER NFPA 101 SECTION 39.3.1 PROTECTION | | | OF VERTICAL OPENINGS. PER 39.3.1.1 VERTICAL OPENINGS | | | SHALL BE ENCLOSED OR PROTECTED IN ACCORDANCE WITH | | | SECTION 8.6 (COMMUNICATING SPACE, ATRIUM, MEZZANINE OR | | | CONVENIENCE OPENING). PER 39.2.4 NUMBER OF MEANS OF | | | EGRESS (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE | | | PROVIDED ON EVERY STORY. | | | | | | THE STORAGE OCCUPANCY NEEDS TO BE SEPARATED | | | (HORIZONTALLY, VERTICALLY, OR BOTH) FROM THE BUSINESS | | | OCCUPANCY BY A 1-HOUR FIRE RATING. PER SECTION 8.3.5.1, | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. | | | | | | PROVIDE A PROPOSED STORAGE LAYOUT FOR THE LARGE | | | WAREHOUSE SPACE. INDICATE WHAT, WHERE, HOW IT WILL ALL | | | BE STORED. | | | | | | PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE | | | AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | | CENTER. | | | | | | THE NW CORRIDOR OF THE FIRST FLOOR IN THE BUSINESS | | | OCCUPANCY CREATES A DEAD-END BECAUSE THE BUSINESS | | | OCCUPANCY IS NOT PERMITTED TO EXIT THROUGH THE STORAGE | | | OCCUPANCY. | | | | | | ADDITIONAL EMERGENCY LIGHTING NEEDED THROUGHOUT BOTH | | | THE STORAGE AND BUSINESS OCCUPANCY. EMERGENCY | | | ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM OF 1.5 | | | HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING. | | | EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO | | | PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN | | | AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN | | | 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT | | | FLOOR LEVEL. | | | | | | WEST STAIR: GUARDS, AT LEAST 42-INCHES TALL, SHALL BE | | | PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, | | | MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. | | | OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH | | | DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE | | | TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND | | | BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE | | | PASSAGE OF A 6-INCH DIAMETER SPHERE. | | | | | | WEST STAIR: HANDRAIL IS NOT CONTINUOUSLY GRASPABLE | | | ALONG THE LOWER STAIR STRINGER. | | | | | | EAST STAIR: HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE | | | STAIR. HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 | | | INCHES AND NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF | | | THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE RAIL | | | FROM THE LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL | | | BE RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT | | | NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A | | | DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN | | | 2 INCHES. | | | | | | FIRE ALARM: THE FIRE ALARM SYSTEM IS DATED, DOES NOT | | | HAVE ANY CAPACITY FOR ADDING NEW DEVICES AND DOES NOT | | | APPEAR TO MEET THE AUDIBLE/VISIBLE REQUIREMENTS OF NFPA | | | 72. SEVERAL COMMON/PUBLIC SPACES HAVE NO FIRE ALARM | | | NOTIFICATION DEVICES. | | | | | | NO ADA ACCESSIBILITY (ELEVATOR/LULA LIFT) TO THE SECOND | | | FLOOR. | | | | | | SEPARATE PLANS AND PERMITS NEEDED FOR FIRE ALARM AND | | | FIRE SPRINKLER ALTERATIONS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-10-16 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-10-16 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-10-15 |
Time |
09:20 |
Sent To |
B |
|
| Notes |
| 2014-10-16 15:19:42 | 1501 NORTHPOINT PARKWAY, SUITE #100 | | | TRACKING #14100419 | | | MASTER #14060978 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | DOES THIS PERMIT REVISION OF ADDING 2 MEZZANINES | | | INCREASE THE PERMIT VALUE OF THE MASTER PERMIT | | | #14060978? | | | | | | NO ADDRESS PROVIDED ON PLANS. | | | | | | PROVIDE A COMPLETE FLOOR PLAN SHOWING THE MEZZANINE IN | | | RELATION TO THE MAIN FLOOR. INDICATE THE SIZE/SQUARE | | | FOOTAGE OF THE MEZZANINES. | | | | | | PROVIDE A LIFE SAFETY PLAN INDICATING OCCUPANCY TYPE, | | | OCCUPANT LOADS, COMMON PATH OF TRAVEL DISTANCES, TRAVEL | | | DISTANCE TO EXITS, LIGHTING, EXIT SIGNS, EMERGENCY | | | LIGHTING, ETC. | | | | | | DESIGN SHALL CONFORM TO THE REQUIREMENTS OF NFPA 101 | | | SECTION 8.6.9 FOR MEZZANINES. | | | | | | THE AGGREGATE AREA OF MEZZANINES LOCATED WITHIN A ROOM, | | | OTHER THAN THOSE LOCATED IN SPECIAL-PURPOSE INDUSTRIAL | | | OCCUPANCIES, SHALL NOT EXCEED ONE-THIRD THE OPEN AREA | | | OF THE ROOM IN WHICH THE MEZZANINES ARE LOCATED. | | | ENCLOSED SPACE SHALL NOT BE INCLUDED IN A DETERMINATION | | | OF THE SIZE OF THE ROOM IN WHICH THE MEZZANINE IS | | | LOCATED. FOR PURPOSES OF DETERMINING THE ALLOWABLE | | | MEZZANINE AREA, THE AGGREGATE AREA OF THE MEZZANINES | | | SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM. | | | | | | ALL PORTIONS OF A MEZZANINE, OTHER THAN WALLS NOT MORE | | | THAN 42-INCHES HIGH, COLUMNS, AND POSTS, SHALL BE OPEN | | | TO AND UNOBSTRUCTED FROM THE ROOM IN WHICH THE | | | MEZZANINE IS LOCATED, UNLESS THE OCCUPANT LOAD OF THE | | | AGGREGATE AREA OF THE ENCLOSED SPACE DOES NOT EXCEED | | | 10. A MEZZANINE HAVING TWO OR MORE MEANS OF EGRESS | | | SHALL NOT BE REQUIRED TO OPEN INTO THE ROOM IN WHICH IT | | | IS LOCATED IF NOT LESS THAN ONE OF THE MEANS OF EGRESS | | | PROVIDES DIRECT ACCESS FROM THE ENCLOSED AREA TO AN | | | EXIT AT THE MEZZANINE LEVEL. | | | | | | GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT | | | THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE, | | | ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN | | | GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER | | | SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR | | | OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT | | | OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH | | | DIAMETER SPHERE. | | | | | | HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR. | | | HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND | | | NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, | | | MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE | | | LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE | | | RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT | | | NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A | | | DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN | | | 2 INCHES. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | INDICATE IF THE BUILDING IS PROTECTED BY AUTOMATIC | | | SPRINKLERS OR A FIRE ALARM SYSTEM. SEPARATE PLANS AND | | | PERMITS WILL BE NEEDED TO ACCOUNT FOR THE MEZZANINES. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2015-08-14 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-08-14 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-08-03 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2015-08-04 08:41:01 | RESUB ROUTED TO JWITMER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-06-25 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-06-25 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-06-18 |
Time |
16:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-06-16 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-06-16 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-06-03 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2015-06-16 11:51:11 | PLANS ARE REMOVED FROM THE REVIEW CYCLE AS IT IS | | | DETERMINED THAT THE SUBMITTED SETS ARE NOT IDENTICAL. | | | THREE SETS OF THE LATEST VERSION OF THE PLANS ARE TO BE | | | RESUBMITTED. | | 2015-06-03 14:19:01 | PLACED IN C06 BIN |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-04-10 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-04-10 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-03-26 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2015-03-26 13:43:51 | ****EXPEDITED**** | | | C06 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-11-05 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2014-11-05 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2014-10-14 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2014-10-23 09:12:02 | 10/23 TO JW DESK | | | | | 2014-10-14 14:23:28 | GIVEN TO WESLEY JOLIN FOR REVIEW. JG. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
5 |
Status |
F |
Date |
2015-08-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-08-05 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-08-05 |
Time |
13:04 |
Sent To |
|
|
| Notes |
| 2015-08-05 13:04:25 | THE NEW 2ND FLOOR AREA OF 2,668 SQ, FT, WILL NEED TO BE | | | REVIEWED BY PAL BEACH COUNTY IMPACT FEE OFFICE. IMPACT | | | FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
4 |
Status |
F |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-23 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-23 |
Time |
07:32 |
Sent To |
|
|
| Notes |
| 2015-06-23 07:33:09 | THE NEW 2ND FLOOR AREA OF 2,668 SQ, FT, WILL NEED TO BE | | | REVIEWED BY PAL BEACH COUNTY IMPACT FEE OFFICE. IMPACT | | | FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2015-06-12 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2015-06-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2015-06-12 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-06-23 07:33:49 | THE NEW 2ND FLOOR AREA OF 2,668 SQ, FT, WILL NEED TO BE | | | REVIEWED BY PAL BEACH COUNTY IMPACT FEE OFFICE. IMPACT | | | FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-06-23 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-06-03 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2015-06-23 07:32:16 | THE NEW 2ND FLOOR AREA OF 2,668 SQ, FT, WILL NEED TO BE | | | REVIEWED BY PAL BEACH COUNTY IMPACT FEE OFFICE. IMPACT | | | FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE | | | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-04-06 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-04-06 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2015-04-06 11:22:51 | IMPACT FEES | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2015-06-23 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2015-06-23 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2015-06-23 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2015-06-18 16:10:21 | RESTAMP |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2015-06-05 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2015-06-05 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2015-06-05 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2015-06-05 13:45:53 | 6/5/15 - ZONING APPROVED, HOWEVER, ONLY ONE SET OF | | | PLANS WERE PROVIDED. TWO SETS OF PLANS ARE REQUIRED. DK |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2015-04-03 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2015-04-03 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2015-03-31 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2015-04-03 12:31:18 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | | | 4/3/15 | | | | | | 1. ONLY A PORTION OF THE SITE WAS USED FOR CALCULATING | | | THE NEW REQUIRED PARKING. PARKING CALCULATION NEEDS TO | | | BE UPDATED TO REFLECT THE ENTIRE SITE. EXISTING PARKING | | | IN EXCESS OF THE MINIMUM PARKING REQUIREMENT CAN BE | | | USED FOR THE REQUIRED NEW PARKING. IF THERE IS NO | | | EXCESS PARKING, THEN NEW PARKING ON SITE WILL NEED TO | | | BE PROVIDED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-11-05 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2014-11-05 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2014-11-05 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2014-11-05 16:58:50 | PLANNING AND ZONING COMMENTS: ****FAILED**** | | | | | | 11/5/14 | | | | | | 1. IT IS UNCLEAR WHERE THE PROPOSED MEZZANINES ARE TO | | | BE LOCATED WITHIN THE BUILDING. PLEASE PROVIDE | | | ADDITIONAL INFORMATION SHOWING THE LOCATION OF THE | | | MEZZANINES WITHIN THE BUILDING. | | | | | | 2. PROPOSED MEZZANINES WILL ADD APPROXIMATELY 3,000 | | | SQUARE FEET TO THE TOTAL BUILDING SQUARE FOOTAGE. | | | ADDITIONAL PARKING WILL BE REQUIRED ON-SITE FOR THE | | | ADDITIONAL SQUARE FOOTAGE. PLEASE PROVIDE PARKING | | | CALCULATIONS TO DEMONSTRATE COMPLIANCE. ANY CHANGES TO | | | THE SITE TO ACCOMMODATE ADDITIONAL PARKING WILL REQUIRE | | | A MINOR PLANNED DEVELOPMENT AMENDMENT APPLICATION (HTTP | | | ://WPB.ORG/PLANNING/WP-CONTENT/UPLOADS/SITES/37/2014/05 | | | /2014-DEVELOPMENT-APPLICATION-REVISED-05.20.2014.PDF) | | | BE SUBMITTED TO THE PLANNING AND ZONING DIVISION FOR | | | REVIEW AND APPROVAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |