Plan Review Details - Permit 14100378
Plan Review Stops For Permit 14100378
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-03-24 Cont ID  
Sent By skennedy Date 2015-03-24 Time 11:47 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-24 Cont ID  
Sent By skennedy Date 2015-02-24 Time 10:06 Rev Time 0.00
Received By skennedy Date 2015-02-24 Time 08:51 Sent To  
Notes
2015-02-24 09:59:382ND REVIEW NEW SINGLE FAMILY RESIDENCE (R3), BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 COMMENTS FROM FIRST REVIEW THAT HAVE NOT BEEN
 ADEQUATELY ADDRESSED ARE BELOW AND REQUIRE RESUBMITTAL;
 SEE ** NOTE:
  
 2- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
 **PROVIDE A PROPOSED FF ELEVATION FOR THE STRUCTURES
 AND THE EXTERIOR PAVING THAT WILL ALLOW FOR APPROPRIATE
 DRAINAGE.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ARCHED WOOD ENTRY DOOR SIZE AS SHOWN ON PLANS.
 (NOTE: NEED TO REVISE DOOR SIZE TO COMPLY WITH EGRESS).
 **SUBMITTED NOA11-0817.12 HAS A MAX. ALLOWABLE WIDTH OF
 36". THE PLAN INDICATES THE DOOR IS TO BE 48". THIS IS
 BEYOND THE LIMITS OF THE APPROVAL.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS TO FBC
 **WILL NEED TO REVIEW FRONT DOOR PRODUCT OR PROVIDE
 LOCAL PRODUCT APPROVAL FOR THE PROPOSED NOA..
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 MASTER BEDROOM BALCONY GUARDRAIL SYSTEM SHOWING
 COMPLIANCE WITH THE LOADS OF TABLE R301.5 AND WITH SEC.
 R312 OF 2010 FBC-RESIDENTIAL.
 **A DEFERRED SUBMITTAL IS PERMISSABLE FOR THE BALCONY
 GUARD SYSTEM.
  
 15- PROVIDE WINDOW AND DOOR MANUFACTURER'S SPECS
 SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS IN ITEM #7.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 **A DEFERRED SUBMITTAL IS PERMISSABLE FOR THIS.
  
 ** PLEASE PROVIDE COMPLETE INFORMATION FOR THE POOL
 UNDER A SEPARATE PERMIT APPLICATION.
 ** PLEASE PROVIDE COMPLETE INFORMATION FOR THE
 LANDSCAPING UNDER A SEPARATE PERMIT APPLICATION
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-27 Cont ID  
Sent By jgomez Date 2014-10-27 Time 14:24 Rev Time 0.00
Received By jgomez Date 2014-10-27 Time 14:12 Sent To  
Notes
2014-10-27 14:26:54NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD.) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 3- PROVIDE SOIL TEST REPORT. SEC. R401.4 OF 2010
 FBC-RESIDENTIAL.
  
 4- DESIGNER OF RECORD TO PROVIDE SPECIFICATIONS ON
 PLANS SHOWING COMPLIANCE WITH UNVENTED ROOF VENTILATION
 SHOWN ON PLANS. SEC. R806.1 OF 2010 FBC-RESIDENTIAL.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ARCHED WOOD ENTRY DOOR SIZE AS SHOWN ON PLANS.
 (NOTE: NEED TO REVISE DOOR SIZE TO COMPLY WITH EGRESS).
 B) WINDOW MULLIONS. NOA 12-0308.37 SUBMITTED EXPIRED
 SEPTEMBER 16,2014. NEED CURRENT NOA.
 C) FIXED WINDOWS. NOA 13-0206.05 SUBMITTED EXPIRED JUNE
 17, 2014. NEED CURRENT NOA.
 D) FLAT ROOF MODIFIED BITUMEN ROOF SYSTEM NOA
 12-0716.18 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
 VISIT THE MIAMI-DADE WEBSITE DOWNLOAD CURRENT NOA AND
 RE-SUBMIT.
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
 OR, WRITE DOWN FLORIDA PRODUCT APPROVAL NUMBER AFTER
 EACH SPECIFIED CONNECTOR.
 F) PRECAST LINTELS AS SHOWN ON PLANS. AND, REVISE
 PRODUCT APPROVAL NUMBER SPECIFIED ON SHEET S.2. NOA
 12-0209.13 FROM FLORIDA PRODUCT APPROVAL FL 158 WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS TO FBC.
  
 7- CLEARLY SPECIFY WHERE IS JELD-WEN DOOR FLORIDA
 PRODUCT APPROVAL FL15558 GOING TO BE INSTALLED. PLANS
 AND ELEVATIONS SUBMITTED DON'T SHOW THIS TYPE OF DOOR.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 8- FLAT ROOF PRODUCT APPROVAL: FROM REVISED NOA
 SUBMITTED (SEE COMMENT #5(D) ABOVE) CLEARLY IDENTIFY
 SPECIFIC APPROVED FLAT ROOF ASSEMBLY TO BE INSTALLED
 AND PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF THE
 NOA. NEED THE RAS 117 CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 9- A) MAIN HOUSE ENTRY DOOR SIZE DOESN'T COMPLY WITH
 SEC. R11.2 OF 2010 FBC-RESIDENTIAL. REVISE AS REQUIRED.
 NOTE:
 B) SAME COMMENT APPLIES TO THE REAR BUILDING: REVISE
 SIZE OF ENTRY DOOR FOR EACH STUDIO TO COMPLY WITH SEC.
 R311.2.
  
 10- WEST ENTRY ELEVATION ON SHEET S.2: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR ARCHED ENTRY DOOR VENEER
 AND PC MOLDING SPECIFY MATERIAL AND THICKNESS AND
 FASTENING TO THE WALL. SEC. R301 OF 2010
 FBC-RESIDENTIAL.
  
 11- SHEET S.2:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 STAIR HANDRAILS SHOWING COMPLIANCE WITH THE LOADS OF
 TABLE R301.5 AND WITH SEC. R311.7.7 OF 2010
 FBC-RESIDENTIAL. SPECIFY LOCATION OF RAILINGS AND
 REVISE TYPICAL STAIR & GUARDRAIL NOTES ON SHEET S.2..
 REFER TO CORRECT CODE SECTIONS FROM THE
 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 MASTER BEDROOM BALCONY GUARDRAIL SYSTEM SHOWING
 COMPLIANCE WITH THE LOADS OF TABLE R301.5 AND WITH SEC.
 R312 OF 2010 FBC-RESIDENTIAL. REVISE TYPICAL STAIR &
 GUARDRAIL NOTES ON SHEET S.2.. REFER TO CORRECT CODE
 SECTIONS FROM THE FBC-RESIDENTIAL.
  
 12- SHEET S.6: MAIN HOUSE AND REAR BUILDING:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 ROOF DRAINAGE TO SHOW COMPLIANCE WITH SEC. R903.4 OF
 2010 FBC-RESIDENTIAL. SPECIFY SIZES OF SCUPPERS,
 DOWNSPOUTS, ETC . ALSO : NEED TO SHOW THEM ON THE
 EXTERIOR ELEVATIONS. ON SHEET S.2.. SEC. 107.2.1 OF
 CITY AMENDMENTS.
  
 B) SPECIFY OVERFLOW SCUPPERS SIZE AND LOCATION TO SHOW
 COMPLIANCE WITH SEC. R903.4.1 OF 2010 FBC-RESIDENTIAL.
  
 C) REVISE THE FIRST PRE-ENGINEERED WOOD TRUSSES NOTE.
 REFER TO CORRECT BUILDING CODE EDITION AND SECTION. THE
 BUILDING CODE IS 2010 NOT 2007.
  
 13- ALL WALL SECTIONS FOR MAIN HOUSE AND REAR BUILDING:
 A) SPECIFY STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1) OF 2010 FBC-RESIDENTIAL.
 B) SPECIFY THE TWO LAYERS OF APPROVED WATER RESISTANT
 BARRIER AS REQUIRED BY SEC. R703.6.3 OF 2010
 FBC-RESIDENTIAL.
 C) CLEARLY SPECIFY THE MINIMUM HEIGHT ABOVE FINISHED
 GRADE AS REQUIRED BY SEC. R404.1.6 AND SEC. R704 OF
 2010 FBC-RESIDENTIAL.
  
 14- ENERGY CALCULATIONS SUBMITTED:
 A) THERE ARE TWO SEPARATE BUILDINGS. PROVIDE ENERGY
 CALCULATIONS FOR EACH BUILDING. SEC. 103.2.1.1.2 OF
 2010 FBC-ENERGY CONSERVATION.
 B) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH AND
 AREA WEIGHTED AVERAGE SPECIFIED IN ITEM #7. SEE PLANS
 AND REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 C) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION ON
 PAGE 3 OF 6. SEE PLANS FOR CORRECT INFORMATION. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
 D) BUILDER NAME ON TOP OF FORM IS INCORRECT. REVISE AS
 REQUIRED. SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 E) SEE MECHANICAL REVIEW COMMENTS AND COORDINATE
 COOLIING AND HEATING INFORMATION WITH REQUESTED REVISED
 A/C EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
 F) ENGINER TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FL. ST.
  
 15- PROVIDE WINDOW AND DOOR MANUFACTURER'S SPECS
 SHOWING COMPLIANCE WITH THE U-FACTOR AND SHGC FACTOR
 SPECIFIED IN THE ENERGY CALCULATIONS IN ITEM #7.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 16- SHEET S.1:
 A) REVISE DESIGN CRITERIA ITEM #7. THIS IS NOT LEVEL OF
 ALTERATION: II. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
 B) REVISE THE STRUCTURAL NOTE "A". ROOF LOADS DON'T
 CORRESPOND TO TYPE OF ROOF ON THIS PROJECT. REVISE AS
 REQUIRED. SPECIFY PROPER LIVE AND DEAD LOADS. SEC. R301
 OF 2010 FBC- RESIDENTIAL.
 C) REVISE PROJECT DATA INFORMATION. A/C AREA 1ST LEVEL
 WAS REPEAT TWICE, INSTEAD OF SAYING 1ST AND 2ND FLOOR
 A/C AREA. SEC. 107.2.1 CITY AMENDMENTS.
  
 17- SECTION A-A ON SHEET S.5:
 A) CLARIFY SIZE OF STAIR TREADS. 11" OR 10". THERE ARE
 TWO DIFFERENT SPECS ON SAME DRAWING. SEC. R311.7.4.2 OF
 2010 FBC-RESIDENTIAL.
 B) PROVIDE SPECIFICATIONS FOR FIREBLOCKING IN ALL AREAS
 AS REQUIRED BY SEC. R302.11 OF 2010 FBC-RESIDENTIAL.
  
 18- SPECIFY CARBON MONOXIDE ALARM ON FIRST FLOOR
 BEDROOM/DEN ROOM. SEC. R315 OF 2010 FBC-RESIDENTIAL.
 (NOTE: THIS IS A BEDROOM ACCORDING TO THE DEFINITION ON
 THE 2010 FBC-ENERGY CONSERVATION).
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REMOVE AND REPLACE ALL REVISED DRAWINGS.
 *** PLEASE PROVIDE COMPLETE INFORMATION FOR THE POOL
 UNDER A SEPARATE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-19 Cont ID  
Sent By dhayes Date 2015-02-19 Time 15:25 Rev Time 0.00
Received By dhayes Date 2015-02-19 Time 15:22 Sent To  
Notes
2015-02-19 15:24:5602/19/2015
 PROJECT: LOVELAND NEW RESIDENCE
 PERMIT#: 14100378
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING
 INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED
 FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO
 ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE
 DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR
 STRUCTURES. NEC 250.94.
  
 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 REQUIRED FOR SWIMMING POOL, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, ETC...
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By dhayes Date 2014-11-07 Time 13:32 Rev Time 0.00
Received By dhayes Date 2014-11-07 Time 13:20 Sent To  
Notes
2014-11-07 16:31:3711/7/2014
 PROJECT: LOVELAND NEW RESIDENCE
 PERMIT#: 14100378
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE ELECTRICAL RISER DIAGRAM TO INDICATE THE USE
 OF A METER ENCLOSURE APPROVED FOR THE PROPOSED LOAD TO
 BE SERVED AND TO IDENTIFY THE VOLTAGE AND AMPERE RATING
 EACH OF THE MAIN BREAKERS.
  
 2) CLARIFICATION REQUIRED. PANEL "A" IS INDICATED WITH
 A 300AMP MAIN. THE RISER DIAGRAM INDICATES IT AS A
 150AMP PANEL FED FROM AN UNIDENTIFIED MAIN.
  
 3) CLARIFICATION REQUIRED. PANEL "B" IS INDICATED AS A
 100AMP PANEL ON THE RISER DIAGRAM BUT AS A 150AMP PANEL
 ON THE PANEL SCHEDULE FED FROM AN UNIDENTIFIED SOURCE.
 .
  
 4) PANEL SCHEDULE FOR PANEL "A" INDICATES A 15AMP
 BRANCH CIRCUIT FOR THE DINING RM. THE DINING ROOM IS A
 ROOM THAT IS REQUIRED TO BE SERVED FROM A 20AMP BRANCH
 CIRCUIT. NEC210.52
  
 5) REVISE PANEL SCHEDULES TO INDICATE EACH CIRCIUT
 SHALL BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT,
 AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 6) CLARIFY THE USE AND PURPOSE OF THE SPECIAL AND
 GENERAL PURPOSE OUTLETS LOCATED IN THE FRONT FOYER COAT
 CLOSET.
  
 7) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 8) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE DESIGNATED CIRCUIT IN THE PANEL.
  
 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 10) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 REQUIRED FOR SWIMMING POOL, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, ETC...
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-02-04 Cont ID  
Sent By fmittner Date 2015-02-04 Time 10:49 Rev Time 0.00
Received By fmittner Date 2015-02-04 Time 10:49 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2014-10-10 Cont ID  
Sent By fmittner Date 2014-10-10 Time 15:45 Rev Time 0.00
Received By fmittner Date 2014-10-10 Time 15:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-03-24 Cont ID  
Sent By skennedy Date 2015-03-24 Time 11:47 Rev Time 0.00
Received By skennedy Date 2015-03-16 Time 14:30 Sent To  
Notes
2015-03-16 14:30:44TO SGRAHAM THEN BACK TO SAK PLEASE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-24 Cont ID  
Sent By skennedy Date 2015-02-24 Time 10:06 Rev Time 0.00
Received By skennedy Date 2015-01-13 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-26 Cont ID  
Sent By jgomez Date 2014-11-26 Time 14:39 Rev Time 0.00
Received By jgomez Date 2014-11-19 Time 07:48 Sent To  
Notes
2014-11-26 14:40:25IMPACT FEES SUBMITTAL ONLY. JG.
2014-11-19 07:48:21INCOMING SENT TO J. GOMEZ. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-07 Cont ID  
Sent By dhayes Date 2014-11-07 Time 16:31 Rev Time 0.00
Received By dhayes Date 2014-10-10 Time 16:51 Sent To  
Notes
2014-10-10 16:51:39INCOMING SENT TO R01BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-11-26 Cont ID  
Sent By jgomez Date 2014-11-26 Time 14:40 Rev Time 0.00
Received By jgomez Date 2014-11-26 Time 14:40 Sent To  
Notes
2014-11-26 14:41:41IMPACT FEES SUBMITTAL ONLY. PAID $10,003.08.
 MU-2014-024824. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-10-27 Cont ID  
Sent By jgomez Date 2014-10-27 Time 14:27 Rev Time 0.00
Received By jgomez Date 2014-10-27 Time 14:27 Sent To  
Notes
2014-10-27 14:27:331- BRING PLANS TO PALM BEACH COUNTY BUILDING (2300 N.
 JOG RD.) TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-03-24 Cont ID  
Sent By skennedy Date 2015-03-24 Time 11:47 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-24 Cont ID  
Sent By skennedy Date 2015-02-24 Time 08:50 Rev Time 0.00
Received By skennedy Date 2015-02-24 Time 07:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-11-06 Cont ID  
Sent By jgomez Date 2014-11-06 Time 11:27 Rev Time 0.00
Received By jgomez Date 2014-11-06 Time 11:00 Sent To  
Notes
2014-11-06 12:43:45NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SHEET M.1: SIZE OF TRANSFER DUCT IN THE MASTER
 BEDROOM DOESN'T COMPLY WITH BALANCED RETURN AIR SEC.
 M1602.4 OF 2010 FBC-RESIDENTIAL. REVISE SIZE AS
 REQUIRED TO COMPLY. REMEMBER THAT NEED TO CONSIDER ALL
 THE SUPPLY AIR INTO THE MASTER BEDROOM WHEN SIZING THE
 TRANSFER DUCT.
  
 2- PROVIDE EQUIPMENT SIZING CALCULATIONS THAT PROVIDE
 ALL THE INFORMATION AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC- ENERGY CONSERVATION. SEE COPY OF CODE SECTION
 BELOW:
  
 403.6.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES,
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF
 THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE
 SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN
 SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY
 FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER
 FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING
 CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL
 INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD
 KITCHEN AND BATHROOM EXHAUST SYSTEMS.
  
 3- ENGINEER DOING THE CALCULATIONS TO PROVIDE ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.
  
 4- EQUIPMENT LISTED ON SHEET M.1 TO MATCH EQUIPMENT
 LISTED IN THE REVISED EQUIPMENT SIZING CALCULATIONS.
 SEC. 107.3.5.3(10). CITY AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-02-03 Cont ID  
Sent By tklarge Date 2015-02-03 Time 11:05 Rev Time 0.00
Received By tklarge Date 2015-02-03 Time 11:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-30 Cont ID  
Sent By tklarge Date 2014-10-30 Time 08:18 Rev Time 0.00
Received By tklarge Date 2014-10-30 Time 07:58 Sent To  
Notes
2014-10-30 08:17:511) THE PLUMBING RISER HAS DRY VENTS FOR THE FIRST FLOOR
 SHOWER, THE SECOND FLOOR TUB, THE TOILET IN THE
 PLAYROOM, AND THE SHOWER IN THE STUDIO.DRY VENTS
 CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE
 THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. FL. BLDG.
 CODE, RESIDENTIAL, SEC.P3104.3.
 2) CLEANOUTS ARE REQD. IN THE BASE OF THE STACKS PER
 FBCR, SEC.P3005.2.6.
 3) SUBMIT A GAS RISER FOR THE GAS INSTALLATION AND
 SUBMIT MANUFACTURER SPECIFICATIONS /INSTALLATION
 INSTRUCTIONS FOR THE TANKLESS WATER HEATER AND THE GAS
 STOVE OR PLACE NOTE ON PLANS THAT GAS TO BE UNDER
 SEPARATE PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-02-24 Cont ID  
Sent By skennedy Date 2015-02-24 Time 08:44 Rev Time 0.00
Received By skennedy Date 2015-02-24 Time 08:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2014-11-06 Cont ID  
Sent By jgomez Date 2014-11-06 Time 11:02 Rev Time 0.00
Received By jgomez Date 2014-11-06 Time 11:02 Sent To  
Notes
2014-11-06 11:02:43NEW SINGLE FAMILY RESIDENCE (R3) ROOFING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- MODIFIED BITUMEN ROOF NOA 12-0716.18 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA AND RE-SUBMIT TWO COPIES.
 REQUIRED BY DCA RULE 9N-3.
  
 2- FLAT ROOF PRODUCT APPROVAL: FROM REVISED NOA
 SUBMITTED (SEE COMMENT # 1 ABOVE) CLEARLY IDENTIFY
 SPECIFIC APPROVED FLAT ROOF ASSEMBLY TO BE INSTALLED
 AND PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF THE
 NOA. NEED THE RAS 117 CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2015-03-24 Cont ID  
Sent By fmittner Date 2015-03-24 Time 10:04 Rev Time 0.00
Received By fmittner Date 2015-03-24 Time 10:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2015-02-04 Cont ID  
Sent By fmittner Date 2015-02-04 Time 10:49 Rev Time 0.00
Received By fmittner Date 2015-02-04 Time 10:49 Sent To  
Notes
2015-02-04 13:33:57DRIVEWAY TOO WIDE...10' MAX AND NEED 937 SF MIN OF
 GREENSPACE IN FRONT YARD.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-10-10 Cont ID  
Sent By fmittner Date 2014-10-10 Time 15:45 Rev Time 0.00
Received By fmittner Date 2014-10-10 Time 15:45 Sent To  
Notes
***NONE***