Plan Review Details - Permit 14100358
Plan Review Stops For Permit 14100358
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-23 Cont ID  
Sent By rlecky Date 2014-10-23 Time 13:40 Rev Time 0.00
Received By rlecky Date 2014-10-23 Time 12:43 Sent To  
Notes
2014-10-23 13:42:4314100358
 600 OKEECHOBEE BLVD.
 TEMPORARY SERVICE REVISION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 SHOW LOCATION ON SITE PLAN FOR THE FIRE PUMP AND
 FEEDERS. VERIFY THAT ALL FEEDERS ARE RATED AT 125% OF
 THE FULL LOAD CURRENTS. NEC 695.6
  
 PROVIDE SPECIFICATIONS ON THE FIRE PUMP CONTROLLER AND
 DISCONNECT. VERIFY THAT THE FIRE PUMP MAIN DISCONNECT
 IS SERVICE RATED. NEC 695.4
  
 VERIFY THAT SERVICE AND CIRCUIT CONDUCTORS ARE
 PROTECTED. NEC 695.6
  
 VERIFY THAT THE DISCONNECTING MEANS IS MARKED AND
 SUPERVISED IN THE CLOSED POSITON OR LOCKED IN THE
 CLOSED POSITION. NEC 695.4
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-21 Cont ID  
Sent By wjolin Date 2014-10-21 Time 15:11 Rev Time 0.00
Received By wjolin Date 2014-10-16 Time 15:25 Sent To E
Notes
2014-10-17 16:37:53600 OKEECHOBEE BOULEVARD
 TRACKING #14100358
 PERMIT #14090274
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN TITLEBLOCK INFORMATION.
  
 NO AUTOMATIC TRANSFER SWITCH PROVIDED WITH FIRE PUMP
 CONTROLLER.
  
 NO JOCKEP PUMP OR CONTROLLER PROVIDED TO PREVENT FIRE
 PUMP FROM CYCLING ON/OFF.
  
 WHERE IS THE SECONDARY POWER SUPPLY TO THE FIRE PUMP
 AND CONTROLLERS?
  
 HOW WILL THE FIRE PUMP CONDUCTORS BE PROTECTED?
 CONCRETE ENCASEMENT?
  
 FIRE PUMP, CONTROLLERS AND EQUIPMENT INSTALLATION WILL
 NEED TO COMPLY WITH NFPA 20 (DRAINAGE, LIGHTING,
 EMERGENCY LIGHTING, FIRE-RATED ENCLOSURE) AND BE
 INSPECTED, TESTED AND APPROVED WITH THE FIRE DEPARTMENT
 PRIOR TO PERMANENT OR TEMPORARY USAGE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-23 Cont ID  
Sent By rlecky Date 2014-10-23 Time 13:42 Rev Time 0.00
Received By rlecky Date 2014-10-10 Time 13:50 Sent To  
Notes
2014-10-10 13:50:50INCOMING SENT TO FIRE BOX. JW