Plan Review Details - Permit 14100349
Plan Review Stops For Permit 14100349
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-03-14 Cont ID  
Sent By shill Date 2015-03-14 Time 12:50 Rev Time 0.00
Received By shill Date 2015-03-14 Time 12:50 Sent To  
Notes
2015-03-14 13:06:20****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
 ****COPY OF CONTRACT REQUIRED PRIOR TO FIRST
 INSPECTION****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE LIGHT POLE CALCS. THIS LOCATION HAS A WIND
 SPEED OF 167MPH FOR RISK CATEGORY II, 150MPH FOR RISK
 CATEGORY I. ENGINEER HAS DESIGNED TO RISK CATEGORY II,
 160MPH. REVISE CALCS ACCORDINGLY, FBC 1609.
  
 2. PROVIDE A COPY OF THE CONTRACT PRIOR TO FIRST
 INSPECTION. CONTRACT TO BE SENT VIA EMAIL TO
 [email protected].
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-17 Cont ID  
Sent By S. Hill Date 2015-02-17 Time 07:55 Rev Time 0.00
Received By shill Date 2015-02-17 Time 07:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-15 Cont ID  
Sent By shill Date 2014-12-15 Time 17:13 Rev Time 0.00
Received By shill Date 2014-12-15 Time 17:13 Sent To E
Notes
2014-12-15 17:23:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHEET P1.0, SEE FAC61G15-23 FOR SEALS ACCEPTABLE TO
 THE BOARD. SEALS WITH THE WORD "CERTIFICATE" RATHER
 THAN "LICENSE" HAVE NOT BEEN IN USE FOR SEVERAL YEARS.
  
 2. SEE FAC61G15-23 FOR THE CORRECT FORMAT FOR CALCS
 (EITHER EITHER SHEET SIGNED/SEALED,OR AN INDEX SHEET
 USED, AND TITLE BLOCK IS LACKING). YOU CAN SEE THE
 SECTION AT WWW.FBPE.ORG, LEGAL, FLORIDA ADMINISTRATIVE
 CODE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-30 Cont ID  
Sent By dhayes Date 2014-12-30 Time 16:58 Rev Time 0.00
Received By dhayes Date 2014-12-30 Time 16:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-24 Cont ID  
Sent By misc2 Date 2014-10-24 Time 08:19 Rev Time 0.00
Received By dhayes Date 2014-10-24 Time 08:00 Sent To B
Notes
2014-10-24 08:24:0710/24/2014
 PROJECT: AUTOZONE
 PERMIT#: 14100349
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE WIND LOAD CALCULATIONS IN ACCORDANCE WITH
 THE FBC CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE
 PROVISIONS OF THE ALTERNATE ALL HEIGHTS METHOD IN THE
 FBC SECTION 1609.6.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-17 Cont ID  
Sent By shill Date 2015-02-17 Time 07:55 Rev Time 0.00
Received By shill Date 2015-01-30 Time   Sent To  
Notes
2015-01-30 15:23:45SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-30 Cont ID  
Sent By dhayes Date 2014-12-30 Time 16:58 Rev Time 0.00
Received By dhayes Date 2014-12-10 Time 08:52 Sent To Z
Notes
2014-12-15 17:25:2112/15 TO DAH DESK
  
2014-12-10 08:53:08SENT TO LLOUIE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-24 Cont ID  
Sent By dhayes Date 2014-10-24 Time 08:32 Rev Time 0.00
Received By dhayes Date 2014-10-09 Time 17:43 Sent To  
Notes
2014-10-09 17:43:50ELEC

Review Stop Z ZONING
Rev No 4 Status P Date 2015-03-13 Cont ID  
Sent By llouie Date 2015-03-13 Time   Rev Time 0.00
Received By llouie Date 2015-03-13 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2015-02-04 Cont ID  
Sent By L. Louie Date 2015-02-04 Time   Rev Time 0.00
Received By llouie Date 2015-02-04 Time   Sent To B
Notes
2015-02-04 15:02:56** ZONING FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CONDITIONS OF ISPR #13-12/Z13120013 HAVE NOT BEEN
 ADDRESSED. CONDITIONS NEED TO BE ADDRESSED PRIOR TO
 SUBMITTING FOR BUILDING PERMITS. (REPEAT COMMENT FROM
 10/22/14 AND 12/30/14)
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE
 ARE QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status F Date 2014-12-11 Cont ID  
Sent By dhayes Date 2014-12-30 Time 16:58 Rev Time 0.00
Received By llouie Date 2014-12-11 Time   Sent To E
Notes
2014-12-11 13:27:00** ZONING FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CONDITIONS OF ISPR #13-12/Z13120013 HAVE NOT BEEN
 ADDRESSED. CONDITIONS NEED TO BE ADDRESSED PRIOR TO
 SUBMITTING FOR BUILDING PERMITS. (REPEAT COMMENT FROM
 10/22/14)
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE
 ARE QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-11 Cont ID  
Sent By llouie Date 2014-10-22 Time   Rev Time 0.00
Received By llouie Date 2014-10-22 Time   Sent To E
Notes
2014-10-22 11:18:20** ZONING FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) CONDITIONS OF ISPR #13-12/Z13120013 HAVE NOT BEEN
 ADDRESSED. CONDITIONS NEED TO BE ADDRESSED PRIOR TO
 SUBMITTING FOR BUILDING PERMITS.
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE
 ARE QUESTIONS.
  