Plan Review Details - Permit 14100344
Plan Review Stops For Permit 14100344
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-11-08 Cont ID  
Sent By jwitmer Date 2014-11-08 Time 08:29 Rev Time 0.00
Received By jwitmer Date 2014-11-08 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-05 Cont ID  
Sent By jwitmer Date 2014-11-05 Time 09:05 Rev Time 0.00
Received By jwitmer Date 2014-11-05 Time 08:41 Sent To  
Notes
2014-11-05 09:05:41BUILDING PLAN REVIEW
 PERMIT: 14100344
 ADD: 525 OKEECHOBEE BLVD
 CONT: BUTLER
 TEL: (561)832-9700
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 05/ 2014
 ACTION: DENIED
  
 1) PLEASE REVIEW THE 2010 FBC-B 1008.1.9.11 DURING ITS
 SWING, ANY DOOR IN A MEANS OF EGRESS SHALL LEAVE
 UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED WIDTH OF
 AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING, NOR PROJECT
 MORE THAN 7 INCHES (178 MM) INTO THE REQUIRED WIDTH OF
 AN AISLE, CORRIDOR, PASSAGEWAY OR LANDING, WHEN FULLY
 OPEN. DOORS SHALL NOT OPEN IMMEDIATELY ONTO A STAIR
 WITHOUT A LANDING. THE LANDING SHALL HAVE A WIDTH AT
 LEAST EQUAL TO THE WIDTH OF THE DOOR. SEE SECTION 1031
 FOR DOOR SWING IN GROUP E OCCUPANCIES.
  
 1A) DOOR # 1673 THE ELECTRICAL DOOR DOES SWING OVER THE
 REQUIRED 1/2 OF THE REQUIRED EGRESS WIDTH. THE REQUIRED
 MINIMUM EGRESS WIDTH WITH OCCUPANT LOADS 50 AND GREATER
 ARE 44 INCHES, 1/2 OF THE REQUIRED EGRESS WIDTH WOULD
 BE 22 INCHES, THESE DOORS ONLY LEAVE AROUND 18 INCHES
 CLEAR.
  
 1B) DOOR # 1654 DOES NOT SWING OVER THE REQUIRED 50% OF
 THE REQUIRED EGRESS, THERE IS APPROXIMATELY 30-32
 INCHES CLEAR BUT IT POSSIBLY COULD BE A CONJESTED AREA.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-24 Cont ID  
Sent By dhayes Date 2014-10-24 Time 14:32 Rev Time 0.00
Received By dhayes Date 2014-10-24 Time 14:32 Sent To  
Notes
2014-10-24 14:47:3210/24/2014
 PROJECT: EDWARDS WILDMAN
 PERMIT#: 14100344
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) VERIFY PRODUCT APPROVAL ON FIRE RATED FLOOR BOX. AND
 PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21
  
 2) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 REQUIRED FOR ACCESS CONTROL SYSTEM.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-11-13 Cont ID  
Sent By pleduc Date 2014-11-13 Time   Rev Time 0.00
Received By pleduc Date 2014-11-13 Time 15:06 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-24 Cont ID  
Sent By pleduc Date 2014-10-24 Time   Rev Time 0.00
Received By pleduc Date 2014-10-23 Time 16:36 Sent To  
Notes
2014-10-24 10:25:47THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET A - 1.0, DOOR 1654 OPENS INTO AN EXIT CORRIDOR
 IMMEDIATELY NEXT TO THE EXIT DISCHARGE OF ANOTHER
 TENANT SPACE. DOOR LEAF ENCROACHMENT
 DURING ITS SWING, ANY DOOR LEAF IN A MEANS OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A
 LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT MORE
 THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN.
  
 THE ABOVE CODE REQUIREMENT DOES NOT ALLOW THE DOOR TO
 OPEN AS PROPOSED.
  
 PLEASE RESUBMIT WITH A CODE COMPLIANT DESIGN.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-13 Cont ID  
Sent By pleduc Date 2014-11-13 Time   Rev Time 0.00
Received By pleduc Date 2014-11-07 Time 06:58 Sent To  
Notes
2014-11-08 07:05:13B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-05 Cont ID  
Sent By jwitmer Date 2014-11-05 Time 09:06 Rev Time 0.00
Received By jwitmer Date 2014-10-09 Time 12:22 Sent To  
Notes
2014-10-10 06:43:15B16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-11-05 Cont ID  
Sent By jwitmer Date 2014-11-05 Time 09:05 Rev Time 0.00
Received By jwitmer Date 2014-11-05 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-10-24 Cont ID  
Sent By hmoser Date 2014-10-24 Time 14:06 Rev Time 0.00
Received By hmoser Date 2014-10-24 Time 14:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-10-25 Cont ID  
Sent By tklarge Date 2014-10-25 Time 04:27 Rev Time 0.00
Received By tklarge Date 2014-10-25 Time 04:27 Sent To  
Notes
***NONE***