Plan Review Details - Permit 14100274
Plan Review Stops For Permit 14100274
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-11-07 Cont ID  
Sent By jwitmer Date 2014-11-07 Time 13:41 Rev Time 0.00
Received By jwitmer Date 2014-11-07 Time 13:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-11 Cont ID  
Sent By jwitmer Date 2014-10-11 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2014-10-11 Time 10:14 Sent To  
Notes
2014-10-11 10:52:47BUILDING PLAN REVIEW
 PERMIT: 14100274
 ADD: 1615 FORUM PLACE/ 4TH FLOOR
 CONT: CONSTRUCTION SUPERVISORS CORP.
 TEL: (561)667-2175
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. OCT. 11/ 2014
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS,
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503). NOTE THIS IS A HIGH RISE CONTSTRUCTION
 FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL INCLUDE
 THE FOLLOWING COMPONENTS: TENANT SEPARATION WALLS
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 EARLY WARNING SMOKE EVACUATION SYSTEMS
 SCHEMATIC FIRE SPRINKLERS / PRE-ENGINEERED SYSTEMS
 LIFE SAFETY PLAN TO INCLUDE:
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES
 DRINKING FOUNTAINS
  
 2) THE EXISTING FLOOR PLAN VS THE PROPOSED FLOOR PLAN
 THE BOTTOM LEFT IT APPEARS WALLS ARE BEING REMOVED IN
 ANOTHER TENANT SPACE. THE BOTTOM LEFT EXISTING SHOWS A
 DOORWAY TO THE COMMON AREA, THE PROPOSED PLAN WHICH
 REMOVES 2 SMALL WALLS DOES NOT HAVE A ENTRY DOOR.
 PROVIDE A EXISTING BUILDING PLAN AND A NEW PROPOSED
 PLAN. THE SUBMITTED PLANS ARE CONFUSING TO WHERE THE
 WORK AREA IS LOCATED.
  
 3) ON THE PERMIT APPLICATION AS WELL AS PLANS IDENTIFY
 THE TENANT SUITE NUMBER WHERE WORK IS TO BE PREFORMED.
 THE APPLICATION INDICATES THE FOURTH FLOOR. IS THIS A
 NEW TENNANT SUITE BEING CARVED OUT OF ANOTHER SUITE?
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTSCONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED.F] 501.2 ADDRESS
 IDENTIFICATION.
  
 4) 1018.4 DEAD ENDS.
 WHERE MORE THAN ONE EXIT OR EXIT ACCESS DOORWAY IS
 REQUIRED, THE EXIT ACCESS SHALL BE ARRANGED SUCH THAT
 THERE ARE NO DEAD ENDS IN CORRIDORS MORE THAN 20 FEET
 (6096 MM) IN LENGTH.
 EXCEPTIONS:
 1. IN OCCUPANCIES IN GROUP I-3 OF OCCUPANCY CONDITION
 2, 3 OR 4 (SEE SECTION 308.4), THE DEAD END IN A
 CORRIDOR SHALL NOT EXCEED 50 FEET .
 2. IN OCCUPANCIES IN GROUPS B, E, F, I-1, M, R-1, R-2,
 R-4, S AND U, WHERE THE BUILDING IS EQUIPPED THROUGHOUT
 WITH AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 903.3.1.1, THE LENGTH OF THE DEAD-END CORRIDORS
 SHALL NOT EXCEED 50 FEET (15 240 MM).
 3. A DEAD-END CORRIDOR SHALL NOT BE LIMITED IN LENGTH
 WHERE THE LENGTH OF THE DEAD-END CORRIDOR IS LESS THAN
 2.5 TIMES THE LEAST WIDTH OF THE DEAD-END CORRIDOR.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-11-14 Cont ID  
Sent By dhayes Date 2014-11-14 Time 12:40 Rev Time 0.00
Received By dhayes Date 2014-11-14 Time 12:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-11-08 Cont ID  
Sent By PLeduc Date 2014-11-08 Time 12:10 Rev Time 0.00
Received By dhayes Date 2014-11-08 Time 11:32 Sent To FIRE
Notes
2014-11-08 11:44:0411/8/2014
 PROJECT: OFFICE RENNOVATION
 PERMIT#: 14100274
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM SO THAT THERE IS A MAIN
 OCPD AFTER THE METER, NOT BEFORE, AND INDICATE HOW THE
 FEEDER TO PANEL 4H IS PROTECTED.
  
 2) REVISE THE RISER DIAGRAM TO INDICATE HOW THE FEEDER
 FROM THE TRANSFORMER SECONDARY FEEDING PANEL 4L IS
 PROTECTED.
  
 3) REVISE THE RISER DIAGRAM TO INDICATE WHAT IS FEEDING
 PANEL 4L-1. IT IS INDICATED AS A 150AMP PANEL. THE
 RISER SHOWS EXISTING 4,#3 AND A #6 GROUND FROM PANEL 4L
 BUT NO BREAKER IN THE PANEL SCHEDULE 4L. REVISE PANEL
 SCHEDULE AND LOAD CALCULATION ACCORDINGLY.
  
 4) EMERGENCY LIGHTS WERE ADDED TO THE SHEET E-1.
 INDICATE WHICH ARE EXISTING OR NEW. THEY SHOULD BE
 PLACED TO ILLUMINATE THE PATH OF TRAVEL FOR THE MEANS
 OF EGRESS. A LIFE SAFETY PLAN HAS NOT BEEN INCLUDED.
 PLEASE PROVIDE A LIFE SAFETY PLAN WITH EMERGENCY AND
 EXIT LIGHTING INSTALLED TO ILLUMINATE THE MEANS OF
 EGRESS. NFPA 101 SECTION 7.10.1.5.1, NEC 700.12,
 700.16,
  
 5) INDICATE THE CIRCUIT THAT THE EXIT AND EMERGENCY
 LIGHHTING WILL BE CONNECTED TO. NEC 700.12(F)
  
 6) INDICATE AND PROVIDE THE LOCATION FOR THE ELECTRICAL
 SERVICE AND PANELS. VERIFY AND PROVIDE THE REQUIRED
 CLEARANCES AS PER THE NEC 110.26
  
 7) VERIFY THAT THE NEW PROPSED WORK STATIONS WILL NOT
 BOCK ACCESS TO THE EXISTING OR NEW OUTLETS OR JUNCTION
 BOXES. 110.26
  
 8) PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF
 USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D)
  
 9) PROVIDE THE MEANS TO DISCONNECT SIMULTANEOUSLY ALL
 UNGROUNDED CONDUCTORS AT THE PANELBOARD WHERE THE
 BRANCH CIRCUIT ORIGINATES. NEC 605.7
  
 10) PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE
 LIMITATIONS AND SEPARATION WITH BARRIERS REQUIRED FOR
 SWITCHES AND ADJACENT DEVICES. NEC 404.8
  
 11) PROVIDE A LIGHHTING PLAN AND INDICATE EXISTING AND
 NEW PLUS INDICATE HOW THE LIGHTING AND SWITCHING OF
 LIGHTING IS AFFECTED BY THE RENOVATION.
  
 12) INDICATE HOW THE LIGHTING COMPLIES WITH THE
 FBC-ENERGY SECTION 505.2 LIGHTING CONTROLS ARE
 MANDATORY IN BUILDINGS 5000SQUARE FEET OR LARGER. FBC-E
 505.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-14 Cont ID  
Sent By rlecky Date 2014-10-14 Time 13:17 Rev Time 0.00
Received By rlecky Date 2014-10-14 Time 12:54 Sent To  
Notes
2014-10-14 13:17:3814100274
 1615 FORUM PL. #4D
 INTERIOR ALTERATIONS
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS
  
 CONSTRUCTION DRAWINGS DO NOT HAVE SUFFICIENT CLARITY.
 INDICATE WHICH ELECTRICAL CIRCUITS ARE NEW AND WHICH
 ARE EXISTING. WPB/FBC 107.3.5
  
 ON THE ELECTRIC PLAN SHOW THE LOCATION OF TRANSFORMER
 AND PANELS. SHOW ALL REQUIRED ACCESS AND SAFE WORKING
 CLEARANCES FOR THE PANEL BOARDS. NEC 110.26
  
 PROVIDE A FIRE STOP DETAIL FOR ANY WALL OR FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE PANEL BOARDS AND DISCONNECTING MEANS. NEC
 110.22, 110.16, 110.22
  
 PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF
 USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D)
  
 PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE
 LIMITATIONS AND SEPARATION WITH BARRIERS REQUIRED FOR
 SWITCHES AND ADJACENT DEVICES. NEC 404.8
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE
 ALARM SYSTEMS, SECURITY AND DATA SYSTEMS.
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-11-13 Cont ID  
Sent By pleduc Date 2014-11-13 Time   Rev Time 0.00
Received By pleduc Date 2014-11-13 Time 11:08 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-10 Cont ID  
Sent By pleduc Date 2014-10-10 Time   Rev Time 0.00
Received By pleduc Date 2014-10-10 Time 12:48 Sent To  
Notes
2014-10-10 13:59:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE EXTENT OF THE REMODEL OR REVISION IS UNCLEAR AND
 DOES NOT INDICATE SUFFICIENT DETAIL TO ADDRESS LIFE
 SAFETY CONCERNS OF THE PROPOSED PROJECT.
  
 A DEAD-END COORIDOR IS BEING PROPOSED; HOWEVER, THE
 PROPOSED FLOOR PLAN DOES NOT INDICATE ANY DIMENSIONS.
  
 TWO ROOMS ARE SHOWING; HOWEVER, THERE IS NO DOORS
 INDICATED.
  
 A LIFE SAFETY PLAN IS NOT INCLUDED AND SHALL BE
 INCLUDING THE RE-SUBMITTAL. THE CCUPANY LOAD, EXIT
 PATHS, EXITS, EXIT SIGNS AND EMERGENCY LIGHTING SHALL
 BE INCLUDED.
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-14 Cont ID  
Sent By dhayes Date 2014-11-14 Time 12:40 Rev Time 0.00
Received By dhayes Date 2014-11-13 Time 16:33 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-13 Cont ID  
Sent By pleduc Date 2014-11-13 Time 14 Rev Time 0.00
Received By pleduc Date 2014-11-06 Time 13:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-14 Cont ID  
Sent By rlecky Date 2014-10-14 Time 13:18 Rev Time 0.00
Received By rlecky Date 2014-10-08 Time 13:32 Sent To  
Notes
2014-10-09 13:44:29EXPEDITED
 B15
  
  