Plan Review Details - Permit 14100194
Plan Review Stops For Permit 14100194
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-01-23 Cont ID  
Sent By jwitmer Date 2015-01-23 Time 08:38 Rev Time 0.00
Received By jwitmer Date 2015-01-20 Time 11:03 Sent To  
Notes
2015-01-20 11:59:45BUILDING PLAN REVIEW
 PERMIT: 14100194
 ADD: 3416 S. DIXIE HWY
 CONT: JACOB ERECTING
 TEL: (561)741-1818
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JAN 20/2015
 ACTION: BUILDING PROVISO
  
 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES NO SUB-SYSTEM
 HAS BEEN IDENTIFIED, ENHANCED FASTENING WILL BE
 REQUIRED FOR THE ROOF INSULATION AS WELL AS THE ROOFING
 SYSTEM, SEE IF LIMITATION #7 OR #9.
  
 ONCE THE CONTRACTOR PICKS WHICH ROOFING SUB-SYSTEM IS
 TO BE APPLIED TO THE ROOF DECK, THE PRODUCT APPROVAL
 MUST BE REVIEWED BY THE DESIGNER OF RECORD AND SHOP
 DRAWING STAMP OF APPROVAL APPLIED. RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-18 Cont ID  
Sent By jwitmer Date 2014-12-18 Time 13:06 Rev Time 0.00
Received By jwitmer Date 2014-12-18 Time 07:35 Sent To  
Notes
2014-12-18 11:15:47BUILDING PLAN REVIEW
 PERMIT: 14100194
 ADD: 3416 S. DIXIE HWY
 CONT: JACOB ERECTING
 TEL: (561)741-1818
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. DEC. 18/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SITE PLAN WITH THE PROPOSED
 LOCATION OF THE BUILDING ON THE LOT AND THE DISTANCE
 FROM PROPERTY LINES.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. SITE PLAN & REQUIREMENTS:
 PARKING : CITY MUNI CODE REQUIRES A DOUBLE STRIPE
 94-485.
 ACCESSIBLE EXITS
 THE LARGER OF THE 2 TENANTCIES REQUIRES 2 EXITS BECAUSE
 THE OCCUPANT LOAD IS OVER 50 OCCUPANTS (74 OCCUPANTS).
 THIS REQUIRES 2 EXITS FBC-B TABLE 1015.1. THE 2010 FBC-
 ACCESSIBILITY CODE 207.1 REFERS TO THE 2003 IBC-B 1007.
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS
 OF EGRESS. THE BACK EXIT DOES NOT SHOW AN ACCESIBLE
 EXIT DISCHARGE, YOU WOULD HAVE TO TRAVEL WITH A
 WHEELCHAIR BEHIND PARKED CARS THERE IS NO ACCESSIBLE
 WALKWAY TO TRAVEL ON TO GETTO THE PUBLIC WAY.
  
 2) COMPLIED. SOILS REPORT.
  
 3) COMPLIED. ENERGY CALCULATIONS WERE PROVIDED.
  
 4 2ND REQUEST WIND PRESSURES FOR COMPONENTS AND
 CLADDING. SHEET S1 LIST THE WIND DESIGN CRITERIA, WITH
 A C EXPOSURE. THE COMMENT RESPONSE INDICATED THE WINDOW
 & DOOR PRESSURES COULD NOW BE FOUND ON THE ELEVATION
 SHEET A-3.0.
  
 4A) THE PRESURES REPRESENTED ON THIS SHEET APPEAR TO BE
 TAKEN AS A B EXPOSURE AT 15 FT.
  
 4B) THE COMMENT RESPONSE ALSO INDICATED THE ROOFING
 PRESSURES ARE TO BE FOUND ON SHEET S2.1. THESE
 PRESSURES ALSO APPEAR TO BE LOW AS TAKEN AS A B
 EXPOSURE AT 15 FT. PLEASE ALSO NOTE THE PARAPET IS LESS
 THAN 3 FEET IN HEIGHT WHICH WILL MEAN THERE IS A ROOF
 CORNER ZONE AND HIGHER ASSOCIATED PRESSURES. THE
 ELEVATIONS SHOWN ON A-3.0 OF THE BAR JOIST, IS THE
 JOIST BEARING POINT. THE VERTICAL HEIGHT OF THE BAR
 JOIST, B-DECK, AND 6 INCHES OF INSULATION (ENERGY
 CALCS.) PUTS THE APPROX. MEAN FINISH ROOF HEIGHT AT
 18FT. 10 INCHES TO 18 FT. 11 IN., THE TOP OF PARAPET IS
 AT 21 FT. 4 IN. OR LESS THAN 3 FT OF PARAPET.
  
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES NO SUB-SYSTEM
 HAS BEEN IDENTIFIED, ENHANCED FASTENING WILL BE
 REQUIRED FOR THE ROOF INSULATION AS WELL AS THE ROOFING
 SYSTEM, SEE IF LIMITATION #7 OR #9.
 (G) PRE-ENGINEERED A/C STANDS/ ROOF TOP CURBS
  
 5A) WITH ROOF TOP A/C CONDENSORS THE M6.1 INDICATES THE
 USE OF ROOF TOP CURBS, THERE IS NO FRAMING DETAILS FOR
 THE ANCHORING OF THE ROOF TOP CURBS, NOR DOES THE PLANS
 PROVIDE THE AMOUNT OF FASTENERS, AND SIZE OF FASTENERS
 IT WILL TAKE TO ANCHOR THE CURB TO THE ROOF FRAMING.
 THE PLANS ALSO WILL NEED TO PROVIDE DETAILS OF THE
 ANCHORING THE ROOF TOP UNITS TO THE ROOF CURB.
  
 6) ROOFING APPROVAL ONCE THE SUB-SYSTEM IS
 IDENTIFIED.2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7-10) COMPLIED.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By jwitmer Date 2014-11-07 Time 09:22 Rev Time 0.00
Received By jwitmer Date 2014-11-07 Time 07:03 Sent To  
Notes
2014-11-07 09:22:43BUILDING PLAN REVIEW
 PERMIT: 14100194
 ADD: 3416 S. DIXIE HWY
 CONT: JACOB ERECTING
 TEL: (561)741-1818
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 07/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SITE PLAN WITH THE PROPOSED
 LOCATION OF THE BUILDING ON THE LOT AND THE DISTANCE
 FROM PROPERTY LINES.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 1. SITE PLAN & REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
  
 2) MISSING SOILS REPORT. PLEASE PROVIDE WHAT THE
 MINIMUM SAFE BEARING VALUE IS. 2010 FBC-B 1803.5.2
 QUESTIONABLE SOIL.WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 3) THIS IS A NEW BUILDING BUT NO ENERGY CALCULATIONS
 WERE PROVIDED. 2010 FBC- ENERGY 103.2/ TABLE 103.2.1 OR
 103.2.2.2.
  
 4) MISSING WIND PRESSURES FOR COMPONENTS AND CLADDING.
 SHEET S1 LIST THE WIND DESIN CRITERIA BUT THE PRESSURES
 FOR COMPONENTS AND CLADDING ARE MISSING FOR ROOF ZONES
 1,2, & 3 AS WELL AS WALL ZONES 4 & 5.
  
 5) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET LS-1.0 INDICATES A 1 HOUR TENANT SEPERATION
 WALL SEE A-5 DETAIL # 2. PLEASE NOTE THE DETAIL
 INDICATES FASTENING THE TOP TRACK TO THE ROOF DECK AND
 TO CAULK BOTH SIDES OF WALL WITH # HW-D-0200. PLEASE
 PROVIDE INFORMATION ON CAULK. THIS HAS TO BE A FLEXIBLE
 JOINT BEING A CONNECTION TO DISSIMILAR MATERIALS AND
 FLEXIBLE SINCE THE ROOF LOADING MAY CHANGE.
 2010 FBC-B
 714.1 GENERAL.
 JOINTS INSTALLED IN OR BETWEEN FIRE-RESISTANCE-RATED
 WALLS, FLOOR OR FLOOR/CEILING ASSEMBLIES AND ROOFS OR
 ROOF/CEILING ASSEMBLIES SHALL BE PROTECTED BY AN
 APPROVED FIRE-RESISTANT JOINT SYSTEM DESIGNED TO RESIST
 THE PASSAGE OF FIRE FOR A TIME PERIOD NOT LESS THAN THE
 REQUIRED FIRE-RESISTANCE RATING OF THE WALL, FLOOR OR
 ROOF IN OR BETWEEN WHICH IT IS INSTALLED.
 FIRE-RESISTANT JOINT SYSTEMS SHALL BE TESTED IN
 ACCORDANCE WITH SECTION 714.3. THE VOID CREATED AT THE
 INTERSECTION OF A FLOOR/CEILING ASSEMBLY AND AN
 EXTERIOR CURTAIN WALL ASSEMBLY SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 714.4.
  
 8) SHEET LS-1.0 THE 1-HOUR FIRE SEPARATION WALL WILL
 NEED LABELING SEEFBC-B 713.6. SUCH IDENTIFICATION SHALL
 BE ABOVE ANY DECORATIVE CEILING AND IN CONCEALED
 SPACES. SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS:
 ?FIRE AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 9) SHEET LS-1.0 THE LARGER OF THE TWO TENANT SPACES
 REFLECTS A OCCUPANT LOAD > THAN 49 REQUIRING 2 EXITS
 FBC TABLE 1015.1.). THE REAR EXIT OF THIS SPACE IS A
 REQUIRED EXIT WITH AN OCCUPANT LOAD APPROX. 81
 OCCUPANTS. NOTE THE PLANS INDICATE INSWING DOOR ,
 SECTION FBC-B 1008.1.2 REQUIRES DOORS SHALL SWING IN
 THE DIRECTION OF EGRESS TRAVEL WHERE SERVING AN
 OCCUPANT LOAD OF 50 OR MORE PERSONS OR A GROUP H
 OCCUPANCY.
 PLEASE ALSO NOTE, NOT HAVING A SITE PLAN EXTERIOR DOORS
 CAN NOT SWING OVER PROPERTY LINES. FBC-B 3202.2.
  
 10) LS-1.0 THE DESIGNER OF RECORD HAS ELECTED TO DESIGN
 THIS BUILING AS A IIIA TYPE BUILDING (PROTECTED),
 PLEASE PROVIDE THE 1 HOUR FIRE RATING OF THE PRIMARY
 STRUCTURAL FRAME, 2 HR EXTERIOR WALLS SEE FOOTNOTES F &
 G, AND 1 HOUR FOR ROOF CONSTRUCTION AND SECONDARY
 MEMBERS.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 TO REVIEW PERMIT STATUS OR ALL REVIEWS YOU MAY LOG ONTO
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STA
 TUS.ASPX FOR PERMIT STATUS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-01-29 Cont ID  
Sent By dhayes Date 2015-01-29 Time 16:46 Rev Time 0.00
Received By dhayes Date 2015-01-29 Time 16:45 Sent To  
Notes
2015-01-29 16:58:101/29/2015
 PROJECT: NEW RETAIL BUILDING
 PERMIT#: 14100194
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 1) ACCORDING TO THE ENGINEER OF RECORD, THE REQUIRED
 WIND LOAD CALCULATIONS ARE TO BE PROVIDED BY THE LIGHT
 POLE MANUFACTURER VIA THE CONTRACTOR. THESE
 CALCULATIONS SHALL BE PROVIDED TO THE INSPECTOR
 INSPECTOR ON SITE AND SUBMITTED TO DEVELOPMENT SERVICED
 DEPT AS A REVISION PRIOR TO FINAL INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-01-08 Cont ID  
Sent By dhayes Date 2015-01-08 Time 16:17 Rev Time 0.00
Received By dhayes Date 2015-01-08 Time 15:55 Sent To  
Notes
2015-01-08 16:06:571/8/2015
 PROJECT: NEW RETAIL BUILDING
 PERMIT#: 14100194
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH. A REFFERENCE IS MADE TO THE
 USE OF A TIMER AND A PHOTOCELL. PLEASE INDICATE ON THE
 PALNS THE LOACTION OF THE EQUIPMENT AND IDENTIFY ALL
 CIRCUIITS THEY OPERATE.
  
 2) 2010 FBC-BUILDING SECTION 1609
 PROVIDE WIND LOAD CALCULATIONS FOR ALL LIGHT POLES
 INCLUDING LUMINAIRE IN COMPLIANCE WITH THE FBC 1609
  
 3) SHEET E3.1
 OUTLETS INDICATED IN THE FIRE RATED TENANT SEPARATION
 WALL SHALL BE SEPARATED BY A MINIMUM ORF 24" OR
 PROTECTED BY A FIRE RATED MATERIAL APPROVED FOR THAT
 USE. FBC 713.3.1.2.
  
 4) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3), VERIFY
 THE REQUIRED OUTLETS ARE EXISTING OR INDICATE NEW
 OUTLETS INCLUDING THE CIRCUIT IN THE CORRESPONDING
 PANELBOARD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-22 Cont ID  
Sent By dhayes Date 2014-10-22 Time 16:26 Rev Time 0.00
Received By dhayes Date 2014-10-22 Time 09:23 Sent To  
Notes
2014-10-22 11:33:4710/22/2014
 PROJECT: 3416 S DIXIE HWY
 PERMIT#: 14100194
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SHEET E-1.1
 A) SITE LIGHTING. WIND LOADS ON EVERY BUILDING OR
 STRUCTURE SHALL BE DETERMINED IN ACCORDANCE WITH
 CHAPTERS 26 THROUGH 30 OF ASCE 7 OR THE PROVISIONS OF
 THE ALTERNATE ALL HEIGHTS METHOD IN SECTION 1609.6.
 WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL
 DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT
 NORMAL TO THE SURFACE CONSIDERED. PROVIDE WIND LOAD
 CALCULATIONS INCLUDING MANUFACTURER SPECIFICATIONS AND
 SUBMITTALS ON POLES AND LUMINAIRES.
 B) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 2) SHEET E3.1
 OUTLETS INDICATED IN THE FIRE RATED TENANT SEPARATION
 WALL SHALL BE SEPARATED BY A MINIMUM ORF 24" OR
 PROTECTED BY A FIRE RATED MATERIAL APPROVED FOR THAT
 USE. FBC 713.3.1.2.
  
 3) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3), VERIFY
 THE REQUIRED OUTLETS ARE EXISTING OR INDICATE NEW
 OUTLETS INCLUDING THE CIRCUIT IN THE CORRESPONDING
 PANELBOARD.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-12-15 Cont ID  
Sent By cranford Date 2014-12-15 Time 14:22 Rev Time 0.00
Received By cranford Date 2014-12-15 Time 14:22 Sent To  
Notes
2014-12-15 14:23:57ALSO APPROVED UNDER APPLICATION E14090021 (ENGINEERING
 DEVELOPMENT SERVICES)

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-11-19 Cont ID  
Sent By cranford Date 2014-11-19 Time 09:35 Rev Time 0.00
Received By cranford Date 2014-11-18 Time 15:40 Sent To I
Notes
2014-11-18 15:43:40ENGINEERING DEPT COMMENTS
  
 PAVING, GRADING AND DRAINAGE PLANS WERE NOT INCLUDED.
 DETAILS OF THE SITE DEVELOPMENT ARE ALSO BEING REVIEWED
 UNDER ENGINEERING APPLICATION E14090021.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-14 Cont ID  
Sent By wjolin Date 2014-10-14 Time 16:18 Rev Time 0.00
Received By wjolin Date 2014-10-14 Time 14:39 Sent To  
Notes
2014-10-14 15:08:213416 SOUTH DIXIE HIGHWAY
 PERMIT #14100194
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE A SITE PLAN.
  
 SHEET LS-1.0: REMOVE CODE REFERENCES TO THE 2006
 EDITION; UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET A-1.0: DOOR #101 SERVES MORE THAN 50 PERSONS AND
 WILL BE REQUIRED TO SWING IN THE DIRECTION OF EGRESS.
  
 SHEET A-1.0 TENANT SEPARATION WALL: PER SECTION
 8.3.2.4, EACH FIRE BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER. PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY
 SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 SHEET A-1.0 MAIN ENTRANCE DOOR: KEYED LOCKS OR
 THUMB-TURN LOCK TO BE EQUIPPED WITH AN ?OPEN/LOCKED?
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  
 SHEET A-3.0: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL
 BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES
 IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-29 Cont ID  
Sent By cpuell Date 2015-01-29 Time 17:08 Rev Time 0.00
Received By cpuell Date 2015-01-16 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-08 Cont ID  
Sent By cpuell Date 2015-01-08 Time 16:20 Rev Time 0.00
Received By cpuell Date 2014-12-05 Time 12:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-11-19 Cont ID  
Sent By cpuell Date 2014-11-19 Time 11:37 Rev Time 0.00
Received By cpuell Date 2014-10-06 Time 16:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2015-02-05 Cont ID  
Sent By jwitmer Date 2015-02-05 Time 13:24 Rev Time 0.00
Received By jwitmer Date 2015-02-05 Time   Sent To  
Notes
2015-02-05 13:25:09IMPACT FEE : MU-2014027791-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2015-01-20 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2015-01-20 11:34:36BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-12-18 Cont ID  
Sent By jwitmer Date 2014-12-18 Time 13:06 Rev Time 0.00
Received By jwitmer Date 2014-12-18 Time 13:06 Sent To  
Notes
2014-12-18 13:06:43BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-11-07 Cont ID  
Sent By jwitmer Date 2014-11-07 Time 09:23 Rev Time 0.00
Received By jwitmer Date 2014-11-07 Time 09:23 Sent To  
Notes
2014-11-07 09:23:19BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-10-09 Cont ID  
Sent By rbergsma Date 2014-10-09 Time   Rev Time 0.50
Received By rbergsma Date 2014-10-09 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-12-17 Cont ID  
Sent By tklarge Date 2014-12-17 Time 13:57 Rev Time 0.00
Received By tklarge Date 2014-12-17 Time 13:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-28 Cont ID  
Sent By tklarge Date 2014-10-28 Time 14:48 Rev Time 0.00
Received By tklarge Date 2014-10-28 Time 14:48 Sent To  
Notes
2014-10-28 14:48:29WPB AMEND. TO 2010 FBC SEC.107.2.1.
 1) SHOW THE SQUARE FOOTAGE FOR EACH TENANT SPACE ON THE
 PLAN AND THE OCCUPANT LOAD FOR EACH SPACE.
 2) ROOM #102 - THE SINK SHALL COMPLY WITH THE 2010 FL.
 ACCESSIBILITY CODE SECS. 212, & 606. A 30 INCH BY 48
 INCH CLEAR FLOOR SPACE COMPLYING WITH SEC. 305 SHALL BE
 POSITIONED FOR A FORWARD APPROACH, AND KNEE AND TOE
 CLEARANCES COMPLYING WITH SEC.306 SHALL BE PROVIDED.
 3) SHT. A-3.1 - SHOW THE DIMENSIONS OF THE CLEAR FLOOR
 SPACE FOR THE FIXTURES ON THE PLAN.COMPLY W/ FL.
 ACCESSIBILITY CODE SECS.305.3, 604.3.1,.
 4) THE TOILET ROOMS SHALL HAVE A TURNING SPACE
 COMPLYING WITH FL. ACCESS. CODE SECS.304, 304.3.1,
 304.3.2. ( EITHER A 60 INCH MINIMUM DIAMETER CIRCULAR
 SPACE OR A T-SHAPED SPACE WITHIN A 60 INCH SQUARE
 MINIMUM WITH ARMS AND BASE 36 INCHES WIDE MINIMUM.)
 5) SHT. A-2.1 - DETAIL #4 - DETAIL SHOWS THE HEIGHT OF
 THE SCUPPER AS 5 INCES YET IT ALSO STATES SCUPPER TO BE
 4 INCHES IN HEIGHT.CLARIFY.
 6) SHT.A-2.1 - DETAIL #7 REFERS TO DETAIL # 5/A-2.0 -
 THERE IS NO SUCH DETAIL ON A-2.0. CLARIFY.
 7) SHT. A-2.0 - ROOF DRAINAGE CALS CALLS OUT PRIMARY &
 SECONDARY SCUPPERS AS 4" X 8" YET DETAIL #4 ON SHT.
 A-2.1 SHOWS 4" X 12" SCUPPERS. DETAIL #6 ON SHT. A-2.1.
 SHOWS THE TYPICAL SCUPPER AS 4" X 12". CLARIFY.
 8) DRINKING FOUNTAINS MAY BE REQD. IN THE TENANT SPACES
 DEPENDING UPON THE OCCUPANT LOAD PER THE FL. PLUMBING
 CODE TABLE 403.1.
 9) SEPARATE SANITARY FACILITIES MAY BE REQD. FOR MALES
 AND FEMALES PER TABLE 403.1. THIS IS BASE ON SQUARE
 FOOTAGE OF THE FACILITY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-01-20 Cont ID  
Sent By jwitmer Date 2015-01-20 Time 12:02 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2015-01-20 12:02:39BUILDING PLAN REVIEW
 PERMIT: 14100194
 ADD: 3416 S. DIXIE HWY
 CONT: JACOB ERECTING
 TEL: (561)741-1818
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. JAN 20/2015
 ACTION: BUILDING PROVISO
  
 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING.FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES NO SUB-SYSTEM
 HAS BEEN IDENTIFIED, ENHANCED FASTENING WILL BE
 REQUIRED FOR THE ROOF INSULATION AS WELL AS THE ROOFING
 SYSTEM, SEE IF LIMITATION #7 OR #9.
  
 ONCE THE CONTRACTOR PICKS WHICH ROOFING SUB-SYSTEM IS
 TO BE APPLIED TO THE ROOF DECK, THE PRODUCT APPROVAL
 MUST BE REVIEWED BY THE DESIGNER OF RECORD AND SHOP
 DRAWING STAMP OF APPROVAL APPLIED. RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-02-09 Cont ID  
Sent By skennedy Date 2015-02-09 Time 11:13 Rev Time 0.00
Received By skennedy Date 2015-02-05 Time 13:02 Sent To  
Notes
2015-02-05 13:45:44IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-01-23 Cont ID  
Sent By llouie Date 2015-01-23 Time 14:44 Rev Time 0.00
Received By llouie Date 2015-01-23 Time 14:44 Sent To  
Notes
2015-01-23 14:44:48ZONING APPROVED FOR NEW RETAIL BUILDING ONLY. SEPARATE
 PERMITS REQUIRED FOR: LANDSCAPING, SIGNAGE AND PAVEMENT
 STRIPING.

Review Stop Z ZONING
Rev No 2 Status F Date 2014-12-15 Cont ID  
Sent By llouie Date 2014-12-15 Time 15:12 Rev Time 0.00
Received By llouie Date 2014-12-15 Time 15:12 Sent To  
Notes
2014-12-15 15:14:36** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) REPEAT COMMENT FROM 11/17/14: PERMIT PLANS
 INCOMPLETE. SET MISSING THE SITE PLAN WITH SITE DATA
 INFORMATION, PARKING CALCULATIONS, SITE DETAILS, ETC.
 PER THE APPROVED SITE PLAN. (REFERENCE ISPR 14-05)
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
  
 OTHER NOTES:
  
 1.) SEPARATE REVIEW AND PERMIT APPLICATIONS REQUIRED
 FOR: SIGNAGE, LANDSCAPING AND AWNINGS.
  
 2.) ALL OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE
 GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE
 AWAY FROM ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT
 RESIDENCES OR PUBLIC THOROUGHFARES. [ZLDR S.94-309(A)]
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2014-11-17 Cont ID  
Sent By llioue Date 2014-11-17 Time 15:51 Rev Time 0.00
Received By llouie Date 2014-11-17 Time 15:51 Sent To  
Notes
2014-11-17 15:52:41** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PERMIT PLANS INCOMPLETE. SET MISSING THE SITE PLAN
 WITH SITE DATA INFORMATION, PARKING CALCULATIONS, SITE
 DETAILS, ETC. PER THE APPROVED SITE PLAN. (REFERENCE
 ISPR 14-05)
  
 2.) PROVIDE DETAILS AND ILLUSTRATIONS SHOWING WHAT THE
 LIGHT FIXTURES WILL LOOK LIKE.
  
 3.) THE PROPERTY ABUTS A HISTORIC RESIDENTIAL DISTRICT.
 PLEASE ADDRESS HOW THE PROPOSED LIGHTING WILL COMPLY
 WITH THE FOLLOWING LIGHTING STANDARDS:
  
 - ALL OUTDOOR LIGHTING SHALL BE SHIELDED TO REDUCE
 GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE
 AWAY FROM ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT
 RESIDENCES OR PUBLIC THOROUGHFARES. [ZLDR S.94-309(A)]
  
 - ANY OPERATION OR ACTIVITY PRODUCING GLARE SHALL BE
 CONDUCTED SO THAT DIRECT OR INDIRECT LIGHT FROM THE
 SOURCE SHALL NOT CAUSE ILLUMINATION IN EXCESS OF 0.5
 FOOT CANDLES WHEN MEASURED IN A RESIDENTIAL DISTRICT.
 [ZLDR S.94-310(D)]
  
 4.) SEPARATE REVIEW AND PERMIT APPLICATIONS REQUIRED
 FOR: SIGNAGE, LANDSCAPING, AWNINGS, PARKING LOT
 STRIPING.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  
2014-10-09 14:50:1010/9/14