Plan Review Details - Permit 14100113
Plan Review Stops For Permit 14100113
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-27 Cont ID  
Sent By jwitmer Date 2014-10-27 Time 16:40 Rev Time 0.00
Received By jwitmer Date 2014-10-27 Time 15:20 Sent To  
Notes
2014-10-27 16:40:46 
 BUILDING PLAN REVIEW
 PERMIT: 14100113
 ADD: 701 S. OLIVE AVE. # 1519
 CONT: THE COTTAGE CO.
 TEL: (772)766-5800
  
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. OCT. 27/ 2014
  
 ACTION: BUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) PRODUCT SPECS FOR PROTECTO WHISPER MAT CS WERE
 SUBMITTED AS PART OF THE 2ND REVIEW. THIS PRODUCT DOES
 NOT PROVIDE TESTING MEETING THE SOUND REQUIREMENTS OR
 FLAME SPREAD & SMOKE DEVELOPMENT:
  
 1A) 2010 FBC-B 1207.3 STRUCTURE BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492--04.
 NO PRODUCT TESTING REPORTS WERE SUBMITTED, ONLY THE
 MANUFACTURERS SALES BROCHURE STATING IT MEETS THESE
 REQUIREMENTS.
  
 1B) THE SUBMITTED SALES BROCHURE STATES THIS PRODUCT IS
 CONSTRUCTED OF A CROSSED LINK POLY-OLEFIN FOAM SHEET
 COMBINED WITH AGGRESSIVE RUBBERIZED ADHESIVE & A
 POLYESTER MESH FABRIC. MUST MEET THESE FIRE AND SMOKE
 DEVELOPMENT TEST.
 THE 2010 FBC-B SECTION 603.1.1(3)
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26.
  
 2603.3 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM
 PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL
 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE
 TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND
 SMOKE-DEVELOPED INDEXES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-10-11 Cont ID  
Sent By jwitmer Date 2014-10-11 Time 13:02 Rev Time 0.00
Received By jwitmer Date 2014-10-11 Time 12:20 Sent To  
Notes
2014-10-11 13:02:08BUILDING PLAN REVIEW
 PERMIT: 14100113
 ADD: 701 S. OLIVE AVE. # 1519
 CONT: THE COTTAGE CO.
 TEL: (772)766-5800
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. OCT. 11/ 2014
 ACTION: BUILDING PROVISO
  
 1) SHEET D1 NOTE INDICATES NO WORK TO BE COMPLETED TO
 FLOOR FINISH. THERE ARE WALLS THAT ARE BEING REMOVED,
 IF ONLY REPAIRING OF FLOOR THEN NO FLOOR INSULATION IS
 REQUIRED. IF THE WHOLE BATHROOM FLOOR IS BEING REMOVED
 AND A NEW FLOOR INSTALLED, THEN DOCUMENTS FOR THE
 FOLLOWING CODE SECTIONS ARE REQUIRED:
 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 805.1.3 INSULATING BOARDS.
 COMBUSTIBLE INSULATING BOARDS NOT MORE THAN 1/2 INCH
 (12.7 MM) THICK AND COVERED WITH FINISH FLOORING ARE
 PERMITTED WHERE ATTACHED DIRECTLY TO A NONCOMBUSTIBLE
 FLOOR ASSEMBLY .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-10-27 Cont ID  
Sent By dhayes Date 2014-10-27 Time 09:59 Rev Time 0.00
Received By dhayes Date 2014-10-27 Time 09:59 Sent To  
Notes
2014-10-27 10:06:56TO TL'S DESK
  
  
2014-10-27 09:59:3610/27/2014
 PROJECT: INMAN RESIDENCE
 PERMIT#: 14100113
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PASS WITH EXCEPTION
  
 1) VERIFY THE REQUIRED MASTER BATHROOM CIRCUIT AND
 OUTLET LOCATIONS AND INDICATE WHETHER EXISTING OR NEW.
 AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED
 TO SUPPLY BATHROOM RECEPTACLE OUTLET(S) NEC210.11(C)(3)
  
 2) VERIFY THE ELECTRICAL SYSTEM VOLTAGE. THE PLAN
 INDICATES THE PANEL IS 120/208V 3 PHASE 4 WIRE BUT THE
 LOAD CALCULATION INDICATES A 120/208V 1 PHASE
 CALCULATION. WPB AMENDMENTS TO THE FBC.
  
 3) FBC 2704 BONDING METAL FRAMING MEMBERS:
 METAL FRAMING MEMBERS SHALL BE BONDED TO THE EQUIPMENT
 GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY ENERGIZE
 THE FRAMING AND BE SIZED IN ACCORDANCE WITH THE NEC
 TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, A
 GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING SHALL
 BE PERMITTED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-07 Cont ID  
Sent By dhayes Date 2014-10-07 Time 08:25 Rev Time 0.00
Received By dhayes Date 2014-10-07 Time 08:20 Sent To  
Notes
2014-10-07 10:05:2310/7/2014
 PROJECT: INMAN RESIDENCE
 PERMIT#: 14100113
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) PROVIDE RISER DIAGRAM AND LOAD CALCULATION
 INDICATING THE CAPACITY OF THE ELECTRICAL SERVICE AND
 PANEL TO SUPPORT THE ADDITIONAL LOAD. .
  
 2) INDICATE THE LOCATION OF THE ELECTRICAL SERVICE. WPB
 AMENDMENTS 107.3.2
  
 3) SHEET A2 DETAIL 5 "ELEVATION DEN" INDICATES AN 80"
 TV. IS THERE AN OUTLET REQUIRED THERE TO POWER THE TV?
 IS THERE A COAXIAL, CAT5(6) OR HDMI CABLE TO FEED THE
 SATALITE/CABLE/AV SIGNAL TO THE TV? IF SO FROM WHERE?
  
 4) NEC 210.11 (C) DWELLING UNITS.
 (1) SMALL-APPLIANCE BRANCH CIRCUITS. IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF
 THIS SECTION, TWO OR MORE 20-AMPERE SMALL-APPLIANCE
 BRANCH CIRCUITS SHALL BE PROVIDED FOR ALL RECEPTACLE
 OUTLETS SPECIFIED BY 210.52(B).
 (2) LAUNDRY BRANCH CIRCUITS. IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY
 RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS
 CIRCUIT SHALL HAVE NO OTHER OUTLETS.
 (3) BATHROOM BRANCH CIRCUITS. IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 PROVIDE AND INDICATE THE REQUIRED OUTLETS ON THE PLANS.
  
 5) 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL. (A) DWELLING UNITS. ALL 125-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES INSTALLED
 IN THE LOCATIONS SPECIFIED IN
 (1) THROUGH (8) SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. (1)
 BATHROOMS. PROVIDE AND INDICATE THE REQUIRED OUTLETS ON
 THE PLANS.
  
 6) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.1, 406.11 REVISE
 PLANS ACCORDINGLY.
  
 7) INDICATE SWITCHING FOR WALL SCONCES, RECESSED
 LIGHTS, AND JUNCTION BOXES.
  
 8) PROVIDE MANUFACTURER PRODUCT DATA SHEETS ON MASTER
 BATH FIXTURE. INDICATE ELEVATION OVER TUB FOR
 INSTALLATION OF FIXTURE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-06 Cont ID  
Sent By scaldero Date 2014-10-06 Time 14:09 Rev Time 0.00
Received By scaldero Date 2014-10-06 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-27 Cont ID  
Sent By jwitmer Date 2014-10-27 Time 16:41 Rev Time 0.00
Received By jwitmer Date 2014-10-24 Time 06:52 Sent To  
Notes
2014-10-25 06:53:29SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-17 Cont ID  
Sent By tklarge Date 2014-10-17 Time 12:22 Rev Time 0.00
Received By tklarge Date 2014-10-02 Time 17:25 Sent To  
Notes
2014-10-02 17:26:20B03

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-27 Cont ID  
Sent By tklarge Date 2014-10-27 Time 14:07 Rev Time 0.00
Received By tklarge Date 2014-10-27 Time 14:07 Sent To  
Notes
2014-10-27 14:08:46MANUF. SPECS FOR STEAM GENERATOR TO BE ON JOBSITE FOR
 INSP.

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-10-17 Cont ID  
Sent By tklarge Date 2014-10-17 Time 12:22 Rev Time 0.00
Received By tklarge Date 2014-10-17 Time 12:22 Sent To  
Notes
***NONE***