Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By rmcdouga Date 2014-10-03 Time 18:23 Rev Time 0.00
Received By rmcdouga Date 2014-10-03 Time 18:23 Sent To  
Notes
2014-10-03 18:24:012010 FBC
  
 REVISION DENIED
  
 1) FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS.
  
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
  
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1 INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE.
  
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
  
 THE 10" DIAMETER TRANSFER DUCT IS TOO SMALL. THERE ARE
 TWO 4" DIAMETER DUCTS, A 6"DIA. DUCT AND A 9" DIA. DUCT
 SUPPLYING THE MASTER SUITE. THIS IS A TOTAL CROSS
 SECTIONAL AREA OF 118 SQ. INCHES. THE AREA TIMES 1.5 IS
 177 SQ. INCHES AND REQUIRES A 15" DIAMETER TRANSFER
 DUCT WITH A 1" DOOR UNDERCUT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW