Plan Review Details - Permit 14100056
| Plan Review Stops For Permit 14100056 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-10-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-03 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-01 |
Time |
13:27 |
Sent To |
|
|
| Notes |
| 2014-10-03 13:27:21 | TO RM DESK | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-10-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-03 |
Time |
18:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-03 |
Time |
18:23 |
Sent To |
|
|
| Notes |
| 2014-10-03 18:24:01 | 2010 FBC | | | | | | REVISION DENIED | | | | | | 1) FBC-R-M 1602.4 PROVIDE BALANCED AIR RETURN AT | | | BEDROOMS. | | | | | | 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | | RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR | | | SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN | | | AIR BALANCE. | | | | | | 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF | | | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING | | | THROUGH-THE-WALL TRANSFER GRILLES AND USING AN | | | UNRESTRICTED 1 INCH UNDERCUTTING OF DOORS TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | | | | 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE | | | REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS, | | | EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL | | | BE INCLUDED. | | | | | | THE 10" DIAMETER TRANSFER DUCT IS TOO SMALL. THERE ARE | | | TWO 4" DIAMETER DUCTS, A 6"DIA. DUCT AND A 9" DIA. DUCT | | | SUPPLYING THE MASTER SUITE. THIS IS A TOTAL CROSS | | | SECTIONAL AREA OF 118 SQ. INCHES. THE AREA TIMES 1.5 IS | | | 177 SQ. INCHES AND REQUIRES A 15" DIAMETER TRANSFER | | | DUCT WITH A 1" DOOR UNDERCUT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |