Plan Review Details - Permit 14100055
Plan Review Stops For Permit 14100055
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-31 Cont ID  
Sent By shill Date 2014-10-31 Time 08:10 Rev Time 0.00
Received By shill Date 2014-10-31 Time 08:10 Sent To  
Notes
2014-10-31 08:27:05****PROVISO****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A LETTER OR A REVISED PLAN FROM DESIGN
 PROFESSIONAL (ARCHITECT OR ENGINEER) WHICH INCORPORATES
 MINIMUM ELEVATION OF 7'6" FOR THE NEW BAR.
  
 2. ELEVATION CERTIFICATE WHICH SHOWS THE NEW BAR AT
 7'6" TO BE PROVIDED PRIOR TO FINAL INSPECTION.
  
 3. ALL NEW MATERIALS BELOW 7'6" ARE TO COMPLY WITH FBC
 1612, FLOOD LOADS. ARCHITECT'S PLAN PROPOSES THAT
 IMPROVEMENTS WILL RESIST FLOOD LOADS AND FLOTATION, BUT
 THE PLAN DOES NOT ADDRESS FLOOD RESISTANT MATERIALS.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By shill Date   Time   Rev Time 0.00
Received By shill Date 2014-10-02 Time 15:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-16 Cont ID  
Sent By rlecky Date 2014-10-16 Time 13:11 Rev Time 0.00
Received By rlecky Date 2014-10-16 Time 13:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-10-20 Cont ID  
Sent By pleduc Date 2014-10-20 Time   Rev Time 0.00
Received By pleduc Date 2014-10-20 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-31 Cont ID  
Sent By shill Date 2014-10-31 Time 08:27 Rev Time 0.00
Received By shill Date 2014-10-09 Time 06:17 Sent To  
Notes
2014-10-03 09:14:11B1
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2014-10-30 Cont ID  
Sent By hmoser Date 2014-10-30 Time 13:09 Rev Time 0.00
Received By hmoser Date 2014-10-30 Time 13:09 Sent To  
Notes
2014-10-30 13:10:29NO MECHANICAL WORK AT THIS TIME. HM.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2014-10-31 Cont ID  
Sent By shill Date 2014-10-02 Time 15:18 Rev Time 0.00
Received By shill Date 2014-10-02 Time 15:18 Sent To  
Notes
2014-10-02 15:18:49NOT A SUBSTANTIAL IMPROVEMENT
 THEREFORE ONLY THE NEW PORTION (NEW BAR TO REPLACE
 EXISTING BAR) TO COMPLY WITH ELEVATION REQUIREMENT OF
 7'6"
 FBC 2010 EXISTING BUILDING 101.5(EXCEPTION); OK PER DH
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-10-29 Cont ID  
Sent By tklarge Date 2014-10-29 Time 05:53 Rev Time 0.00
Received By tklarge Date 2014-10-29 Time 05:53 Sent To  
Notes
***NONE***