| 2014-10-25 07:57:33 | 1) SHT.G102 - PLUMBING FIXTURE TABLE - INDICATE ON THE |
| | PLAN HOW YOU ARE COMPLYING WITH SEC. 410.1 OF THE 2010 |
| | FLORIDA PLUMBING CODE FOR THE REDUCTION OF THE REQUIRED |
| | NUMBER OF DRINKING FOUNTAINS. |
| | 2) PLEASE PROVIDE A NARRATIVE EXPLAINING THE BED |
| | TABULATION TABLE AND HOW TO READ IT. WPB AMEND. TO 2010 |
| | FBC SEC.107.2.1. WHAT DO THE LETTERS "P" & "SP" |
| | 3) SHT. E-A001 - MOUNTING HT. DETAILS SHOW VERTICAL |
| | GRAB BARS. GRAB BARS MUST BE INSTALLED IN THE |
| | HORIZONTAL POSITION PER THE 2010 FL. ACCESSIBILITY CODE |
| | SEC.609.4.VERTICAL GRABS BARS ARE NOT ACCEPTABLE. |
| | 4) SHT.E-A001. - THE LIP OF THE URINAL SHALL BE A MAX. |
| | OF 17" ABOVE THE FINISHED FLOOR PER THE 2010 FAC |
| | SEC.605.2. |
| | 5) SHT.E-A001 - THE ACCESSIBLE DRINKING FOUNTAINS SHALL |
| | COMPLY W/ THE FAC SECS. 306.2, 306.3, & 602 FOR KNEE & |
| | TOE CLEARANCES. SHOW THE CLEARANCES ON THE DETAIL. |
| | 6) SHT.E-A101 - TOILET ROOM #142 DOES NOT APPEAR TO |
| | MEET THE SIZE & FIXTURE CLEARANCES OF THE 2010 FL. |
| | ACCESSIBILITY CODE. PROVIDE DIMENSIONS AND CLEAR FLOOR |
| | SPACE FOR FIXTURES AND THE REQUIRED 5 FT TURNING |
| | DIAMETER OR T-TURN. |
| | 7) THE WASHERS & DRYERS IN THE LAUNDRY ROOMS SHALL |
| | COMPLY W/ SECS. 214 & 611 OF THE 2010 FAC. |
| | 8) PROVIDE A PLAN VIEW OF THE ACCESSIBLE SHOWERS. SHOW |
| | ALL DIMENSIONS AND DETAILS. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | 9) SHT. E-A001 - THE TOILET PAPAER DISPENSERS SHALL |
| | COMPLY W/ 2010 FAC. SEC.604.7. |
| | 10) SHT. E-A402 - DETAILS # 15, #16, & 17 - THE SINKS |
| | IN THESE AREAS SHALL COMPLY W/ 2010 FAC - SECS. 212 & |
| | 606. |
| | 11) SHT. E-A403 - NOURISHMENT RMS. #144 & 145 - THE |
| | SINKS AND OTHER ELEMENTS IN THIS ROOM SHALL COMPLY W/ |
| | 2010 FAC SECS.212 & 606, 804, 805. |
| | 12) THE ISLAND SINKS SHALL COMPLY W/ THE HEIGHT REQS. |
| | OF THE 2010 FAC SECS. 212.3 & 606. |
| | 13) SHT. E-A412 - ATLEAST ONE SINK IN THE SALON SHALL |
| | COMPLY W/ 2010 FAC SECS.212.3 & 606. SEE DETIALS #3 & # |
| | 7. |
| | 14) IDENTIFY THE AREAS ON THE PLANS WHERE THE BARRIER |
| | FREE SINKS WILL BE INSTALLED. WPB AMEND. TO 2010 FBC |
| | SEC. 107.2.1. |
| | 15) SHT. E-P501 - SIZE ALL SECTIONS OF THE DWV SYSTEM |
| | ON ALL THE RISERS. WPB AMEND. TO 2010 FBC SEC. 107.2.1 |
| | 16) SHT. E-P202 - RM. #245 - THE SANITARY RISER SHOWS |
| | PIPING FOR A PIECE OF EQUIPMENT WITH QUESTION MARKS FOR |
| | IT. CLARIFY THE PIECE OF EQUIPMENT. IF IT IS A PEDICURE |
| | CHAIR, SUBMIT THE MANUF. SPECIFICATIONS FOR THE |
| | ITEM.WPB AMEND. TO 2010 FBC SEC. 107.2.1 |
| | 17) SHT.E-P501 - RISER FOR RMS. 155 & 156 - AS |
| | DESIGNED, A URINAL IS ON A WET VENT. URINALS ARE NOT |
| | PERMITTED ON A WET VENT PER THE 2010 FPC SEC. 909.1. |
| | THE RISER ALSO SHOWS A DRY VENT NEXT TO FIXTURE L-3. |
| | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. 2010 FPC SEC.905.3. |
| | 18) SHT. E-P502 - IDENTIFY THE ROOM NUMBERS THAT |
| | CORRELATE WITH THE APPLICABLE WATER RISER. |
| | 19) IDENTIFY AND SIZE ALL LINES ON THE WATER RISERS |
| | INCLUDING THE EXISTING. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |