2014-09-30 18:34:06RESIDENTIAL (R3) ROOFING REVISION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- CLEARLY SPECIFY WHICH APPROVED ASSEMBLY FORM NOA
 13-0514.12 SUBMITTED IS GOING TO BE INSTALLED. IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117
 CALCULATIONS WILL BE REQUIRED BY GENERAL LIMITATION #7
 ON LAST PAGE OF NOA SUBMITTED. CALCULATIONS ARE
 REQUIRED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF
 2010 FBC-RESIDENTIAL.
  