| Plan Review Stops For Permit 14091010 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-12-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:21 |
Sent To |
|
|
| Notes |
| 2014-12-27 09:23:37 | APPROVED WITH EXCEPTIONS | | | - SUBMIT TWO COPIES OF THE CURRENT PRODUCT APPROVALS | | | FOR THE CAST-CRETE 8 INCH LINTELS THAT HAVE BEEN | | | REVIEWED AND APPROVED BYTHE DESIGNER OF RECORD. FBC | | | 107.3.4.1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-10-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-22 |
Time |
11:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-21 |
Time |
07:08 |
Sent To |
|
|
| Notes |
| 2014-10-22 11:14:23 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | BUILDING DENIED | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) NOTE 2 ON SHEETS A-1 AND A-2 INCORRECTLY REFERENCES | | | THE FBC 2007 / 2009 AMENDMENTS. THE CORRECT EDITION IS | | | THE FBC 2010. | | | | | | 2) IN THE DOOR SCHEDULE ON SHEETS A-1 AND A-2, FOR DOOR | | | #2 THE DESIGN OPENING PRESSURES ARE MORE THAN THE NOA | | | PRESSURES OF +/- 50 PSF. THE PRODUCT APPROVAL, FL# | | | 14665.1 HAS PRESSURES OF +/- 55 PSF. FBC-R 301.2.1 | | | | | | 3) THE WINDOW SCHEDULE APPEARS TO BE MISSING FROM THE | | | PLANS. FBC 107.2.1 AND FBC-R 301.2.1 | | | | | | 4) DESIGNATE THE EGRESS WINDOW IN THE MASTER BEDROOM OF | | | THE RIGHT UNIT. FBC-R310.1 | | | | | | 5) THE FOLLOWING MIAMI-DADE NOAS HAVE BEEN SUPERSEDED: | | | BORAL TILESEAL (NOA NO. 12-0417.06) AND CASTCRETE 8" | | | LINTELS (NOA NO. 12-0209.13). SUBMIT THE CURRENT NOAS. | | | DCA RULE 9N-3 | | | | | | 6) THE FLORIDA PRODUCT APPROVAL ( FL# 7170 )THAT WAS | | | SUBMITTED FOR THE AMARR SECTIONAL GARAGE DOOR IS FOR | | | THE 2007 FBC. SUBMIT THE PRODUCT APPROVAL THAT | | | REFERENCES THE 2010 FBC EDITION. | | | | | | 7) THE PRODUCT APPROVAL NUMBERS THAT ARE SPECIFIED IN | | | THE DOOR SCHEDULE ON THE PLANS FOR THE FIBERGLASS ENTRY | | | DOOR AND THE SLIDING GLASS DOOR DO NOT MATCH THE ONES | | | THAT WERE SUBMITTED. FBC 107.2.1 | | | | | | 8) THE NOA OPENING PRESSURE FOR THE SLIDING GLASS DOOR | | | IS +/- 80.0 PSF IN THE DOOR SCHEDULE AND +/- 60 PSF IN | | | THE PRODUCT APPROVAL THAT WAS SUBMITTED. FBC 107.2.1 | | | | | | 7) SPECIFY THE ROOF TILE (PROFILE), SIZE AND NUMBER OF | | | SCREWS THAT WILL BE USED TO PROVIDE WINDLOAD RESISTANCE | | | PER FRSA/TRI 07320/8-05. FBC-R 301.2.1 | | | | | | 8) FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF | | | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL | | | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL | | | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT | | | APPLICATION. ONLY ONE SET OF PLANS WERE SUBMITTED FOR | | | "BUILDING C". THERE ARE TWO OTHER PLANS WITH THIS | | | SUBMITTAL BUT ONE IS FOR THE 6-UNIT WORK FORCE HOUSING | | | BUILDING AND THE OTHER IS FOR THE 7-UNIT WORK FORCE | | | HOUSING BUILDING. | | | | | | 9) IT APPEARS THAT THE ENERGY CALCULATIONS HAVE THE | | | ADDRESSES FOR THE RIGHT AND LEFT UNITS REVERSED. SUBMIT | | | CORRECTED FORMS. FBC 107.2 | | | | | | 10) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | | ADDRESSED. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-12-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-10-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-22 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-22 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2014-10-22 15:46:28 | PLAN REVIEW COMMENTS | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | ELECTRIC DENIED | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF | | | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL | | | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL | | | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT | | | APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE | | | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE | | | REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15 | | | FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA | | | STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE | | | SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS | | | AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS | | | TO BE PREPARED BY A REGISTERED DESIGN PROFESSIONAL. | | | ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN | | | REQUIRED BY THE BUILDING OFFICIAL, AND MAY REQUIRE ONLY | | | ONE SET OF SUBMITTALS. ONLY ONE SET OF PLANS WAS | | | SUBMITTED FOR THE TWO UNIT TOWNHOUSE. | | | | | | 2) THE PLANS REFERENCE THE 2009 NEC IN SEVERAL PLACES. | | | THE 2008 NEC IS THE APPLICABLE CODE EDITION FOR THIS | | | PROJECT. | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-12-31 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-12-31 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-12-19 |
Time |
09:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-11-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-30 |
Time |
18:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-09-29 |
Time |
07:08 |
Sent To |
|
|
| Notes |
| 2014-09-29 07:09:13 | INCOMING SENT TO R-13. JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
P |
Date |
2015-01-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-01-05 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-01-05 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2015-01-05 12:42:01 | MU2014-2257, 2377 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2014-12-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2014-12-27 09:24:25 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2014-10-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-21 |
Time |
07:06 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-21 |
Time |
07:06 |
Sent To |
|
|
| Notes |
| 2014-10-21 07:07:58 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL ONE | | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2014-12-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2014-10-07 |
|
|
Cont ID |
|
| Sent By |
rbergsma |
Date |
2014-10-07 |
Time |
|
Rev Time |
0.50 |
| Received By |
rbergsma |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2014-10-07 14:42:49 | DRAWINGS APPROVED AS NOTED, DRYER EXHAUST MUST BE 26 | | | GAUGE AS PER --FBC-M 504.6 , | | | DRAWINGS SPEC 30 GAUGE |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-12-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-12-27 |
Time |
09:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2014-10-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-21 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-21 |
Time |
06:58 |
Sent To |
|
|
| Notes |
| 2014-10-22 15:47:13 | APPROVED PENDING THE SUBMITTAL OF AN ADDITIONAL SET OF | | | PLANS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2014-12-31 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-12-31 |
Time |
10:51 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2014-12-31 |
Time |
10:51 |
Sent To |
PC |
|
| Notes |
| 2014-12-31 10:51:30 | 1) A SEPARATE LANDSCAPE AND IRRIGATION PERMIT AND THEIR | | | INSTALLATION IS REQUIRED PRIOR TO CO. | | | | | | 2) SCREEN ENCLOSURE REQUIRES SEPARATE PERMIT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2014-10-29 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-10-29 |
Time |
09:31 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2014-10-29 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2014-10-29 10:18:14 | FAILED | | | | | | 1) ONLY ONE SET OF PLANS WAS SUBMITTED WITH THIS | | | APPLICATION. PLEASE PROVIDE THE SECOND SET OF PLANS. | | | | | | 2) PLANS COMPLY WITH ZONING REQUIREMENTS. | | | | | | 3) A SEPARATE LANDSCAPE AND IRRIGATION PERMIT AND THEIR | | | INSTALLATION IS REQUIRED PRIOR TO CO. | | | | | | 4) SCREEN ENCLOSURE REQUIRES SEPARATE PERMIT. | | 2014-10-09 15:00:25 | 10/9/14 |
|
|