| 2014-10-03 17:18:34 | ENERGY CALCULATIONS SUBMITTED WERE NOT REQUESTED OR |
| | REQUIRED FOR THIS JOB. IT MAY BE A SUBMITTAL TO ADDRESS |
| | MECHANICAL REVIEW PROVISO. NEVERTHELESS, IT WAS NOT |
| | WHAT IT WAS REQUESTED ON ROBERT MCDOUGAL'S PROVISO. |
| | SENT TO ROBERT'S DESK FOR REVIEW. JG. |
| | |
| | *** REMAINDER TO CONTRACTOR: |
| | THERE WAS A BUILDING PROVISO DATED 8/7/14. INFORMATION |
| | REQUESTED IN THIS PROVISO NEED TO BE ADDRESSED. SEE |
| | COPY OF PROVISO BELOW: |
| | |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF COVER. GENERAL NOTES ON COVER SHEET INDICATES |
| | NEW ROOF AS PART OF THE SCOPE OF WORK. |
| | B) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED |
| | ON PLANS, DETAILS AND SPECIFICATIONS. |
| | C) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. |
| | D) ROUND CASEMENT WINDOW AS SHOWN ON PLANS. |
| | E) NEW ALUMINUM CASEMENT NOA 12-0216.04 WAS SUBMITTED. |
| | NEED TO PROVIDE TWO COPIES. |
| | F) NEW FRENCH DOORS FLORIDA PRODUCT APPROVAL FL14504 |
| | WAS SUBMITTED. NEED TO PROVIDE TWO COPIES. |
| | 2- ARCHITECT TO REVIEW AND APPROVE ABOVE PRODUCT |
| | APPROVALS. SEC. 107.3.4.1 OF CITY AMENDMENTS. |
| | 3- SHEET A-2: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR INTERIOR HANDRAIL TO BE REPLACED. |
| | TABLE R301.5 AND SEC. R311.7.7. |
| | 4- SHEET A-4: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR NEW MASTER BATHROOM BALCONY. TABLE |
| | R301.5 AND SEC. R312. |
| | 5- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR NEW ARCHED OPENINGS IN THE REBUILT DEN AREA ON |
| | FIRST FLOOR. SEC. R301. |
| | 6- SHEET A-9: REVISE ALL THE DOOR STRUCTURAL BUCK |
| | DETAILS. BUCK NEED TO PROVIDE FULL SUPPORT TO THE DOOR |
| | FRAME. SEC. R612.10.2.1. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |