Plan Review Details - Permit 14090954
Plan Review Stops For Permit 14090954
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-16 Cont ID  
Sent By jgomez Date 2014-10-16 Time 09:52 Rev Time 0.00
Received By jgomez Date 2014-10-16 Time 09:45 Sent To  
Notes
2014-10-16 09:53:34NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO CHECK IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROJECT INFORMATION & DESIGN CRITERIA ON SHEET A-1:
 A) SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY TABLE
 R301.5 OF 2010 FBC-RESIDENTIAL.
  
 B) REVISE THE ROOF PITCH TO MATCH PLANS. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 C) THE INFORMATION SHOWN ON THE DESIGN LOADS UNDER THE
 FOOTING NOTES DON'T MATCH THE INFORMATION SHOWN ON THE
 PROJECT INFORMATION & DESIGN CRITERIA. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY SEC. R401.3 OF
 2010 FBC-RESIDENTIAL.
  
 3- WALL DETAIL ON SHEET A-2:
 A) SPECIFY FIREBLOCKING AS REQUIRED BY SEC. R302.11 OF
 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE DETAIL AND SPECIFICATIONS
 (INCLUDING SIZE AND LOCATION) FOR THE ROOF VENTILATION
 AS REQUIRED BY SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 C) PROVIDE MANUFACTURER'S SPECS FOR R-7 FOIL BACKED
 INSULATION AS SPECIFIED ON THE WALL DETAIL AND THE
 ENERGY CALCULATIONS SUBMITTED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 4- SHEET A-3:
 A) PROVIDE COMPLETE AREA TABULATION: GARAGE, PORCHES
 AND LIVING AREA. SEC. 107.2.1 CITY AMENDMENTS.
  
 B) NEED TO PROVIDE AT LEAST ONE BATHROOM LOCATED WITH
 MAXIMUM PRIVACY WITH A DOOR THAT PROVIDES AT LEAST 29"
 CLEAR OPENING AS REQUIRED BY SEC. R320 OF 2010
 FBC-RESIDENTIAL. REVISE PLANS AS REQUIRED.
  
 C) REVISE SIZE OF ATTIC ACCESS (TWO LOCATIONS SHOWN ON
 PLAN) TO COMPLY WITH SEC. R807 OF 2010 FBC-RESIDENTIAL.
  
 D) REVISE EXTERIOR DOOR STRUCTURAL BUCK DETAILS AND
 SPECIFICATIONS. STRUCTURAL BUCK NEEDS TO PROVIDE FULL
 SUPPORT TO THE DOOR FRAME AS REQUIRED BY SEC.
 R612.10.2.1 OF 2010 FBC-RESIDENTIAL. REVISE THE BUCK
 SIZE AND PROVIDE LEGIBLE SPECS FOR THE TAPCON SIZE.
  
 5- SHEET A-4:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR ALL
 BEAMS AND LINTELS. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE TRUSS ANCHOR SCHEDULE. SEC. R301 OF 2010 FBC
 RESIDENTIAL.
  
 6- ROOF SHEATHING SPECIFICATIONS ON SHEET A-4:
 A) SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL REQUIRES 8D
 RING SHANK NAILS. REVISE NAIL TYPE SPECS ON THE FLOOR &
 ROOF SHEATHING FASTENER DETAIL AND ROOF SHEATHING
 DETAIL ON SHEET A-4. OTHERWISE, PROVIDE CALCULATIONS
 SHOWING THAT THE PROPOSED NAIL WILL PROVIDE EQUAL OR
 BETTER VALUES THAN THE 8D RING SHANK NAIL. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 B) COORDINATE INFORMATION ON ROOF SHEATHING DETAIL AND
 FLOOR & ROOF SHEATHING FASTENER DETAIL TO MATCH. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 7- SHEET A-5:
 A) PROVIDE COMPLETE DRAWINGS, DETAILS AND
 SPECIFICATIONS FOR THE SCREEN PORCH OR PROVIDE COMPLETE
 INFORMATION UNDER A SEPARATE PERMIT. SEC. 107.2.1 CITY
 AMENDMENTS AND SEC. R301 OF 2010 FBC RESIDENTIAL.
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 "FIELD STONE" VENEER INSTALLATION AS SHOWN ON THE FRONT
 ELEVATION. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 8- PLANS TO SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED
 BY SEC. R315 OF 2010 FBC-RESIDENTIAL.
  
 9- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS AND CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 C) FIXED WINDOWS AS SHOWN ON PLANS.
  
 D) ENTRY DOORS AS SHOWN ON PLANS.
  
 E) OVERHEAD GARAGE DOOR. PROVIDE 2 COPIES. ONLY ONE WAS
 SUBMITTED.
  
 F) SIDE GARAGE EXTERIOR DOOR.
  
 G) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WILL BE UPDATED ONCE THE ENGINEER
 PROVIDES THE AREA TABULATION AS REQUESTED ON ITEM #4(A)
 ABOVE.
  
 12- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) COMPLETE INFORMATION ON TOP OF FORM, INCLUDING THE
 CONTRACTOR'S NAME.
  
 C) REVISE DOOR TYPE ON PAGE 3 OF 5. THERE ARE NOT WOOD
 DOORS. SEE PLANS AND PRODUCT APPROVAL SUBMITTED.
  
 ***PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ALL REVISED SHEETS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-17 Cont ID  
Sent By dhayes Date 2014-10-17 Time 15:41 Rev Time 0.00
Received By dhayes Date 2014-10-17 Time 15:30 Sent To  
Notes
2014-10-17 16:29:2010/17/2014
 PROJECT: 1578 6TH ST
 PERMIT#: 14090954
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE ALL KITCHEN COUNTER TOP RECEPTACLES TO BE
 GFCI PROTECTED. NEC 210.8
  
 2) IN KITCHENS, AND SIMILAR AREAS OF DWELLING UNITS,
 RECEPTACLE OUTLETS FOR COUNTERTOP SPACES SHALL BE
 INSTALLED IN ACCORDANCE WITH NEC 210.52(C)(1) THROUGH
 (C)(5).
  
 3) AT LEAST ONE RECEPTACLE SHALL BE INSTALLED AT EACH
 ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF 12" OR
 GREATER AND A SHORT DIMENSION OF 12" OR GREATER. NEC
 210.52 (C)(2)
  
 4) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOMS. NEC 210.11 (C)(3)
  
 5) THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR AT THE
 SERVICE, AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED
 BY A FEEDER(S) OR BRANCH CIRCUIT(S), OR AT A SEPARATELY
 DERIVED SYSTEM OF A GROUNDED OR UNGROUNDED AC SYSTEM
 SHALL NOT BE LESS THAN GIVEN IN TABLE 250.66, EXCEPT AS
 PERMITTED IN NEC 250.66(A) THROUGH (C).
  
 6) ALL GROUNDING ELECTRODES AS DESCRIBED IN
 250.52(A)(1) THROUGH (A)(7) THAT ARE PRESENT AT EACH
 BUILDING OR STRUCTURE SERVED SHALL BE BONDED TOGETHER
 TO FORM THE GROUNDING ELECTRODE SYSTEM. WHERE NONE OF
 THESE GROUNDING ELECTRODES EXIST, ONE OR MORE OF THE
 GROUNDING ELECTRODES SPECIFIED IN 250.52(A)(4) THROUGH
 (A)(8) SHALL BE INSTALLED AND USED. NEC 250.50
  
 7) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND
 (B).
  
 8) INDICATE CIRCUITRY ON PLANS TO CORRESPOND TO
 CIRCUITS ON PANEL SCHEDULE. WPB AMENDMENTS TO FBC
 107.2.1
  
 9) CLARIFY THE INDICATION AND USE FOR THE "100AMP
 BREAKER FOR "LT" SHOWN ON THE ELECTRICAL RISER DIAGRAM.
 WPB AMENDMENTS TO FBC 107.2.1
  
 10) SMOKE DETECTORS ARE REQUIRED PER FBC-R 314 IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC-R
 R315
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-17 Cont ID  
Sent By dhayes Date 2014-10-17 Time 16:52 Rev Time 0.00
Received By dhayes Date 2014-09-25 Time 06:32 Sent To  
Notes
2014-09-26 06:33:20R04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-10-16 Cont ID  
Sent By jgomez Date 2014-10-16 Time 09:46 Rev Time 0.00
Received By jgomez Date 2014-10-16 Time 09:46 Sent To  
Notes
2014-10-16 09:52:221- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO CHECK IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-10-08 Cont ID  
Sent By rbergsma Date 2014-10-08 Time   Rev Time 0.50
Received By rbergsma Date 2014-10-08 Time   Sent To  
Notes
2014-10-08 10:26:54SELECT AC UNIT TO MEET ENERGY & LOAD CALCS
 SHOW AC DUCT INSULATION R-VALUE ON PLANS
 AS PER ENERGY CALC'S- COMPLY WITH FBC-EC 403.2.2.1.1
 SEE MARKED UP SET AND SUPPLY REQUESTED INFORMATION
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2014-10-06 Cont ID  
Sent By tklarge Date 2014-10-06 Time 04:17 Rev Time 0.00
Received By tklarge Date 2014-10-06 Time 04:17 Sent To  
Notes
2014-10-06 04:19:23****PROVISO****
 1) SUBMIT A SANITARY RISER DIAGRAM FOR REVIEW AND
 APPROVAL PRIOR TO ROUGH PLUMBING INSPECTION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-10-16 Cont ID  
Sent By jgomez Date 2014-10-16 Time 15:17 Rev Time 0.00
Received By jgomez Date 2014-10-16 Time 12:32 Sent To  
Notes
2014-10-16 15:18:14SHINGLES NOA 12-0309.01 SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-26 Cont ID  
Sent By sgraham Date 2014-09-26 Time 15:29 Rev Time 0.00
Received By sgraham Date 2014-09-26 Time 15:29 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved