| 2014-10-01 12:18:23 | BUILDING PLAN REVIEW |
| | PERMIT: 14090929 |
| | ADD: 222 LAKEVIEW AVE. SUITE # 120 |
| | CONT: GREEN CORPORATION |
| | TEL: (305)670-1000 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: WED. OCT. 01/2014 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-04 INDICATES THE (2) ELEVATORS AND MACHINE |
| | ROOM AS EXISTING, PLEASE CORRECT PLANS. THEY ARE UNDER |
| | REVIEW PERMIT # 14081026. |
| | THIS IS A HIGHRISE BUILDING, THE 2010 FBC-B 708.14.1 |
| | REQUIRES ELEVATOR LOBBIES EVEN IF THIS PORTION OF THE |
| | BUILDING IS ONLY 5 STORIES TALL OR MEET ONE OF THE |
| | SEVEN EXCEPTIONS, THIS IS CONSIDERED NEW WORK. 2010 |
| | EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. THE M3 SHEET |
| | DOES SHOW SF-1 FAN PRESSURIZING THE ELEVATOR SHAFTWAY. |
| | THE SHEET M2 NOTE2 ONCE THE SMOKE ALARM CLOSES VANT # |
| | 1, THE VENTS LABELED # 2 WILL OPEN ON ACTUATION OF |
| | SMOKE ALARM OTHERWISE THEY ARE SET AND OPERATE AS A |
| | BAROMETER PRESSURE SENSOR. |
| | |
| | 2) THE HOISTWAY WALLS AND ELEVATOR MACHINE ROOM WILL |
| | REQUIRE 2 HOUR FIRE RATED WALLS, UNDER THE SHAFTWAY |
| | PERMIT, THE ELEVATOR MACHINE ROOM DOOR IDENTIFIED AS |
| | DOOR (H) WILL NEED TO HAVE 1 1/2 HOUR OPENING |
| | PROTECTIVE. 2010 FBC-B 3006.4 MACHINE ROOMS AND |
| | MACHINERY SPACES & |
| | TABLE 715.4 OPENING PROTECTIVE TABLE 715.4. |
| | |
| | 3) A LETTER FROM THE QUALIFIER OF BOTH THE ELEVATOR |
| | SHAFT CONTRACTOR (FASTRACK CORPORATION) AND TENANT |
| | BUILD-OUT CONTRACTOR MUST BE PROVIDED 7) BEFORE TENANT |
| | BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE ELEVATOR |
| | SHAFT HAS RECEIVED A CERTIFICATE OF COMPLETION, |
| | AGREEING THEY WILL WORK TOGETHER TO ACHIEVE CODE |
| | COMPLIANCE. THESE DOCUMENTS WILL NEED TO BE SIGNED BY |
| | THE QUALIFIER . PLEASE PROVIDE THE PERMIT NUMBER, |
| | ADDRESS WITH SUITE NUMBER WITHIN THE DOCUMENT. |
| | |
| | 4) THE MAIN DOUBLE ENTRY DOORS TO THIS TENANT SPACE ARE |
| | WITHIN AN ATRIUM AND WILL NEED TO BE 1 HOUR FIRE RATED |
| | DOORS. 2010 FBC-B 404.6 ENCLOSURE OF ATRIUMS. ATRIUM |
| | SPACES SHALL BE SEPARATED FROM ADJACENT SPACES BY A |
| | 1-HOUR FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 707 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN |
| | ACCORDANCE WITH SECTION 712, OR BOTH. PLEASE SEE |
| | EXCEPTION # 3 FOR AN ACTIVE SMOKE CONTROL SYSTEM FOR |
| | THE ATRIUM. |
| | |
| | 5A) THE A-04 SHEET DOES NOT DECLARE: 2010 WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRATION |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| | EXAMINATION OF THE DOCUMENTS BY THE |
| | BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM |
| | CRITERIA AND DOCUMENTS: |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE |
| | TABLE 503). |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | |
| | 5B) CLOSET # 105 DOOR (D) IS A 3'-0" WIDE DOOR AND |
| | LOCATED IN A CORRIDOR 5'-0" WIDE, PLEASE SEE 2010 FBC-B |
| | 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A MEANS OF |
| | EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF |
| | THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, |
| | OR LANDING, NOR PROJECT MORE THAN 7 INCHES (178 MM) |
| | INTO THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, |
| | PASSAGEWAY OR LANDING, WHEN FULLY OPEN. DOORS SHALL NOT |
| | OPEN IMMEDIATELY ONTO A STAIR WITHOUT A LANDING. |
| | 36"+18"(<50 OCC)= 4'-6" |
| | 44"+22"(>50 OCC)= 5'-6" |
| | |
| | 6) EGRESS DOOR LABELED (I) IS INDICATED AS A "B" LABEL |
| | DOOR IN SCHEDULE, PLEASE REFER TO 2010 FBC-B TABLE |
| | 715.4 IN HOURS AND MINUTES & 715.4.3. |
| | |
| | 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |