Plan Review Details - Permit 14090911
| Plan Review Stops For Permit 14090911 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2014-12-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-12-11 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-12-11 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2014-12-11 16:48:48 | SEE MASTER PERMIT # 14090960, DAVID HAYES PASSED PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-09-25 |
|
|
Cont ID |
|
| Sent By |
sciard |
Date |
2014-09-25 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
sciard |
Date |
2014-09-25 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2014-09-25 14:08:37 | B13 | | | | | | | | 2014-09-25 13:31:21 | 9/25/2014. PLEASE ADDRESS COMMENTS: | | | 1. REVISE FOLLOWING ITEMS: LOAD CALCULATION, PANEL | | | SCHEDULE DOES NOT ADDRESS ALL LOADS. | | | 2. PANEL SCHEDULE OVERCURRENT PROTECTIVE DEVICES PASTRY | | | WARMER,LARGE FREEZER (PANEL SCHEDULE SHOWS 15 KW LOAD | | | WITH 20 AMPERE OCPD, PASTRY WARMER NO LOAD WITH 2#8 ON | | | 20 AMPERE OCPD. | | | 3.SERVICE RISER DIAGRAM SHOWS 3#1/0 AWG WITH 200 AMPERE | | | OCPD. | | | 4. FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING | | | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE | | | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, | | | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, | | | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, | | | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY | | | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST | | | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY | | | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT | | | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-12-11 |
|
|
Cont ID |
|
| Sent By |
sciard |
Date |
2014-12-11 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-09-25 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2014-09-25 14:13:22 | ROUTED TO B13 | | 2014-09-25 09:58:36 | ROUTED TO ELECTRICAL $5000 & UNDER |
|
|
|