| | PROJECT: POWDER RM |
| | PERMIT#: 14090896 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | ELECTRICAL PLAN REVIEW |
| | ACTION: |
| | |
| | 1) PROVIDE A SITE PLAN OR FLOOR PLAN TO INDICATE THE |
| | LOCATION OF THE NEW POWDER ROOM. IS IT INSIDE THE |
| | EXISTING CONDITIONED SPACE UNDER ROOF? OR IS THERE AN |
| | ADDITION BEING BUILT TO ADD THE NEW SPACE? |
| | |
| | 1) PROVIDE ELECTRICAL PLANS TO INDICATE THE FOLLOWING: |
| | A. NEC 210.52(C)(3) BATHROOM BRANCH CIRCUITS. IN |
| | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE |
| | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM |
| | RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER |
| | OUTLETS. |
| | B. 210.70 LIGHTING OUTLETS REQUIRED. LIGHTING OUTLETS |
| | SHALL BE INSTALLED WHERE SPECIFIED IN 210.70(A), (B), |
| | AND (C). |
| | (A) DWELLING UNITS. IN DWELLING UNITS, LIGHTING OUTLETS |
| | SHALL BE INSTALLED IN ACCORDANCE WITH 210.70(A)(1), |
| | (A)(2), AND (A)(3). |
| | (1) HABITABLE ROOMS. AT LEAST ONE WALL |
| | SWITCH?CONTROLLED LIGHTING OUTLET SHALL BE INSTALLED IN |
| | EVERY HABITABLE ROOM AND BATHROOM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |