 |
Plan Review Details - Permit 14090842
| Plan Review Stops For Permit 14090842 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2015-02-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-02-03 |
Time |
07:01 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-02-03 |
Time |
06:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2014-12-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-12-02 |
Time |
06:53 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-12-02 |
Time |
06:01 |
Sent To |
|
|
| Notes |
| 2014-12-02 06:52:59 | BUILDING PLAN REVIEW | | | PERMIT: 14090842 | | | ADD: 431 BUNKER RD | | | CONT: SULLIVAN BUILDERS OF FL. | | | TEL: (561) 310-1899 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | ***********NOTICE**********:CHAPTER 553.80(2)(B) | | | FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL | | | IMPOSE A FEE OF FOUR TIMES THE FEE FOR | | | PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES | | | FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. | | | | | | 3RD REVIEW | | | DATE: TUES. DEC. 02/ 2014 | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | COVER SHEET INDICATES THIS OCCUPANCY TO BE STORAGE AND | | | BUSINESS PLEASE PROVIDE THE BREAKDOWN IN SQUARE FEET | | | THE OCCUPANCY AND OCCUPANCY LOAD FOR EACH AREA. | | | | | | 2) COMPLIED. OCCUPANCY S-1 | | | | | | 3) COMPLIED. OCCUPANCY S-1 7815/300= 27 NOT 26. | | | | | | 4) #RD REQUEST. THE DESIGNER OF RECORD HAS DECALRED | | | THIS TO BE A LEVEL 2 ALTERATION. PLEASE REVIEW SECTION | | | 2010 FBC-EXST. 703.2.3 SUPPLEMENTAL STAIRWAY ENCLOSURE | | | REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS | | | 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS THAT ARE PART | | | OF THE MEANS OF EGRESS SERVING THE WORK AREA SHALL, AT | | | A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT CONSTRUCTION ON | | | THE HIGHEST WORK AREA FLOOR AND ALL FLOORS BELOW. | | | EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY | | | THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE | | | PREVENTION CODE. | | | PLEASE PROVIDE FOR A SECOND FLOOR HOW THE CODES ALLOW | | | FOR A OPEN STAIRWAY. NOTE THIS IS A NON-SPRINKLERED | | | BUILDING, OVER 33% OF FLOOR AREA NOT CONSIDERED A | | | MEZZANINE BUT A 2ND FLOOR. 2010 FBC-B 1014.3. THE FLOOR | | | AREA OF THE 2ND FLOOR IS 48% OF THE 1ST FLOOR. | | | | | | NOTE; THE REMOVAL OF STIAR ENCLOSURES CREATES A | | | NON-CONFORMITY, UNDER PERMIT # 13060708 PLANS SHOWED AN | | | EXISTING STAIR ENCLOSURE. A NEW EXTERIOR DOOR WAS TO BE | | | INSTALLED IN THE EXTERIOR WALL SO THE 2ND FLOOR TENANTS | | | WOULD BE ABLE TO EXIT THE ENCLOSURE WITHOUT GOING | | | THROUGH THE OTHER TENANTCY. | | | | | | 5 ) 3RD REQUEST. COVER SHEET. COMMON PATH OF TRAVEL | | | FROM THE MOST REMOTE POINT UPSTAIRS IN THE STORAGE AREA | | | TO AN EXIT CAN BE UP TO 100 FT FOR STORAGE NON | | | SPRINKLERRED BUILDING WITH AN OCCUPANT LOAD OF LESS | | | THAN 30. (FBC-B 1014.3EXC. # 2) . THE TRAVEL DISTANCE | | | FROM THE MOST REMOTE POINT APPROX. 105 FT. | | | | | | 6) COMPLIED. | | | PLEASE PROVIDE A SITE PLAN SHOWING AN ACCESSIBLE | | | ENTRANCE, THE ENTRY ON A 45 DEGREE ANGLE SHOWS STEPS. | | | 206.4 ENTRANCES. | | | ENTRANCES SHALL BE PROVIDED IN ACCORDANCE WITH 206.4. | | | ENTRANCE DOORS, DOORWAYS, AND GATES SHALL COMPLY WITH | | | 404 AND SHALL BE ON AN ACCESSIBLE ROUTE COMPLYING WITH | | | 402. | | | | | | 7) COMPLIED. | | | SHOWING LIFT DISPROPORTIONATE. PLEASE SHOW COMPLIANCE | | | WITH AN ACCESSIBLE ROUTE TO THE 2ND FLOOR. 2010 | | | FBC-ACC. CODE | | | 206.7 PLATFORM LIFTS. PLATFORM LIFTS SHALL COMPLY WITH | | | 410. PLATFORM LIFTS SHALL BE PERMITTED AS A COMPONENT | | | OF AN ACCESSIBLE ROUTE IN NEW CONSTRUCTION IN | | | ACCORDANCE WITH 206.7. PLATFORM LIFTS SHALL BE | | | PERMITTED AS A COMPONENT OF AN ACCESSIBLE ROUTE IN AN | | | EXISTING BUILDING OR FACILITY. | | | 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS | | | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR | | | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY | | | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE | | | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL | | | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE | | | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE | | | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH | | | BUILDING, STRUCTURE OR FACILITY, | | | | | | | | | | | | 8) COMPLIED | | | . SHOWING LIFT IS DISPROPORTIONATE. PLEASE PROVIDE | | | COMPLIANCE WITH 2010 FL ACC. CODE 202.4.1 | | | DISPROPORTIONATE COST. THE CONTRACTOR IS TO CREATE ON | | | THEIR OWN LETTER HEAD AN ITEMIZED LIST WHERE $14,000.00 | | | IN ACCESSIBLE UPGRADES IN THE LISTED ORDER BELOW. | | | 2010 FL ACC. CODE 202.4.1 DISPROPORTIONATE COST. | | | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF | | | TRAVEL TO THE ALTERED AREA WILL BE DEEMED | | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE | | | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS | | | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF | | | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING | | | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | | AN INACCESSIBLE DRINKING FOUNTAIN. | | | | | | 9)COMPLIED. | | | PLANS MAY NEED TO BE SUBMITED TO PALM BEACH COUNTY FOR | | | IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO CONSTRUCT, | | | MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED | | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025 | | | FOR MORE INFORMATION. | | | | | | 10) THE PRODUCT APPROVALS SUBMITTED WERE NOT REVIEWED | | | BY THE DESIGNER OF RECORD, NO SHOP DRAWING STAMP OF | | | APPROVAL. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-11-05 |
|
|
Cont ID |
|
| Sent By |
JWITMER |
Date |
2014-11-05 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-11-05 |
Time |
07:03 |
Sent To |
|
|
| Notes |
| 2014-11-05 08:38:33 | BUILDING PLAN REVIEW | | | PERMIT: 14090842 | | | ADD: 431 BUNKER RD | | | CONT: SULLIVAN BUILDERS OF FL. | | | TEL: (561) 310-1899 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE: WED.NOV. 05/ 2014 | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | COVER SHEET INDICATES THIS OCCUPANCY TO BE STORAGE AND | | | BUSINESS PLEASE PROVIDE THE BREAKDOWN IN SQUARE FEET | | | THE OCCUPANCY AND OCCUPANCY LOAD FOR EACH AREA. | | | | | | 2) COMPLIED. OCCUPANCY S-1 | | | | | | 3) COMPLIED. OCCUPANCY S-1 7815/300= 27 NOT 26. | | | | | | 4) 2ND REQUEST. THE DESIGNER OF RECORD HAS DECLRED THIS | | | TO BE A LEVEL 2 ALTERATION. PLEASE REVIEW SECTION 2010 | | | FBC-EXST. 703.2.3 SUPPLEMENTAL STAIRWAY ENCLOSURE | | | REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS | | | 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS THAT ARE PART | | | OF THE MEANS OF EGRESS SERVING THE WORK AREA SHALL, AT | | | A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT CONSTRUCTION ON | | | THE HIGHEST WORK AREA FLOOR AND ALL FLOORS BELOW. | | | EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY | | | THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE | | | PREVENTION CODE. | | | PLEASE PROVIDE FOR A SECOND FLOOR HOW THE CODES ALLOW | | | FOR A OPEN STAIRWAY. NOTE THIS IS A NON-SPRINKLERED | | | BUILDING, OVER 33% OF FLOOR AREA NOT CONSIDERED A | | | MEZZANINE BUT A 2ND FLOOR. 2010 FBC-B 1014.3. THE FLOOR | | | AREA OF THE 2ND FLOOR IS 48% OF THE 1ST FLOOR. | | | | | | 5 ) 2ND REQUEST. COVER SHEET. COMMON PATH OF TRAVEL | | | FROM THE MOST REMOTE POINT UPSTAIRS IN THE STORAGE AREA | | | TO AN EXIT CAN BE UP TO 100 FT FOR STORAGE NON | | | SPRINKLERRED BUILDING WITH AN OCCUPANT LOAD OF LESS | | | THAN 30. (FBC-B 1014.3EXC. # 2) . THE TRAVEL DISTANCE | | | FROM THE MOST REMOTE POINT APPROX. 105 FT. | | | | | | 6) COMPLIED. | | | PLEASE PROVIDE A SITE PLAN SHOWING AN ACCESSIBLE | | | ENTRANCE, THE ENTRY ON A 45 DEGREE ANGLE SHOWS STEPS. | | | 206.4 ENTRANCES. | | | ENTRANCES SHALL BE PROVIDED IN ACCORDANCE WITH 206.4. | | | ENTRANCE DOORS, DOORWAYS, AND GATES SHALL COMPLY WITH | | | 404 AND SHALL BE ON AN ACCESSIBLE ROUTE COMPLYING WITH | | | 402. | | | | | | 7) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH AN | | | ACCESSIBLE ROUTE TO THE 2ND FLOOR. 2010 FBC-ACC. CODE | | | 206.7 PLATFORM LIFTS. PLATFORM LIFTS SHALL COMPLY WITH | | | 410. PLATFORM LIFTS SHALL BE PERMITTED AS A COMPONENT | | | OF AN ACCESSIBLE ROUTE IN NEW CONSTRUCTION IN | | | ACCORDANCE WITH 206.7. PLATFORM LIFTS SHALL BE | | | PERMITTED AS A COMPONENT OF AN ACCESSIBLE ROUTE IN AN | | | EXISTING BUILDING OR FACILITY. | | | 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS | | | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR | | | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY | | | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE | | | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL | | | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE | | | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE | | | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH | | | BUILDING, STRUCTURE OR FACILITY, | | | | | | THE OWNER HAS 3 OPTIONS; | | | 7A) INSTALL A LULA LIFT | | | 7B) THE CONTRACTOR ON THEIR LETTERHEAD PROVIDE THE | | | LETTER SHOWING DISPROPORTIONATE COST. THE PERMIT VALUE | | | OF $14,000 X 20%= $14,000.00 IN ACCESSIBLE UPGRADES IN | | | THE ORDER LISTED BELOW. | | | 7C) APPLY TO THE STATE FOR A WAIVER SINCE THIS STORAGE | | | OCCUPANCY IS NOT GOING TO BE OPEN TO THE PUBLIC. | | | | | | 8) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2010 FL | | | ACC. CODE 202.4.1 DISPROPORTIONATE COST. THE CONTRACTOR | | | IS TO CREATE ON THEIR OWN LETTER HEAD AN ITEMIZED LIST | | | WHERE $14,000.00 IN ACCESSIBLE UPGRADES IN THE LISTED | | | ORDER BELOW. | | | 2010 FL ACC. CODE 202.4.1 DISPROPORTIONATE COST. | | | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF | | | TRAVEL TO THE ALTERED AREA WILL BE DEEMED | | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE | | | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS | | | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF | | | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING | | | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | | AN INACCESSIBLE DRINKING FOUNTAIN. | | | | | | 9)COMPLIED. | | | PLANS MAY NEED TO BE SUBMITED TO PALM BEACH COUNTY FOR | | | IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO CONSTRUCT, | | | MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH | | | COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED | | | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED | | | TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025 | | | FOR MORE INFORMATION. | | | | | | 10) THE PRODUCT APPROVALS SUBMITTED WERE NOT REVIEWED | | | BY THE DESIGNER OF RECORD, NO SHOP DRAWING STAMP OF | | | APPROVAL. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-10-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-10-01 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-10-01 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2014-10-01 08:42:50 | BUILDING PLAN REVIEW | | | PERMIT: 14090842 | | | ADD: 431 BUNKER RD | | | CONT: SULLIVAN BUILDERS OF FL. | | | TEL: (561) 310-1899 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: WED. OCT. 1/ 2014 | | | ACTION: DENIED | | | | | | 1) COVER SHEET INDICATES THIS OCCUPANCY TO BE STORAGE | | | AND BUSINESS PLEASE PROVIDE THE BREAKDOWN IN SQUARE | | | FEET THE OCCUPANCY AND OCCUPANCY LOAD FOR EACH AREA. | | | | | | 2) THE COVER SHEET DOES NOT INDICATE THE TYPE OF | | | STORAGE OCCUPANCY THIS WILL BE S1 OR S2, DECLARE | | | OCCUPANCY AND WHAT TYPE OF ARTICLES ARE GOING TO BE | | | STORED. WILL THE PUBLIC BE ALLOWED INTO THE STORAGE | | | AREA, OR WILL THE PUBLIC ONLY BE ALLOWED IN THE OFFICE/ | | | BUSINESS AREA. OFFICE AREA IS NOT DEFINED ON THE PLAN. | | | IS THIS SEPARARTED OR NON-SEPARATED USE? THIS APPEARS | | | TO BE SET UP AS A ART GALLERY WHICH IS NOT CONSIDERED A | | | STORAGE OCCUPANCY BUT AN A3 USAGE.2010 FBC-B TABLE | | | 508.4, 508.2 508.2.4, 508.3, 508.3.3 & 303.1- A3. | | | | | | 3) THE COVER SHEET INDICATES THE STORAGE OCCUPANCY AT | | | 500 FT /OCCUPANT. PLOEASE SEE TABLE 1004.1.1 STORAGE IS | | | 300 GROSS, WAREHOUSE IS 500 GROSS, PLEASE PROVIDE | | | ADDITIONAL INFORMATION HOW THE CLIENT INTENDS TO USE | | | THIS SPACE, IT APPEARS TO BE SET UP AS A ART GALLERY. | | | 2010 FBC-B TABLE 1004.1.1. | | | | | | 4) THE DESIGNER OF RECORD HAS DECLRED THIS TO BE A | | | LEVEL 2 ALTERATION. PLEASE REVIEW SECTION 2010 | | | FBC-EXST. 703.2.3 SUPPLEMENTAL STAIRWAY ENCLOSURE | | | REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS | | | 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS THAT ARE PART | | | OF THE MEANS OF EGRESS SERVING THE WORK AREA SHALL, AT | | | A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT CONSTRUCTION ON | | | THE HIGHEST WORK AREA FLOOR AND ALL FLOORS BELOW. | | | EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY | | | THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE | | | PREVENTION CODE. | | | PLEASE PROVIDE FOR A SECOND FLOOR HOW THE CODES ALLOW | | | FOR A OPEN STAIRWAY. NOTE THIS IS A NON-SPRINKLERED | | | BUILDING, OVER 33% OF FLOOR AREA NOT CONSIDERED A | | | MEZZANINE BUT A 2ND FLOOR. 2010 FBC-B 1014.3. | | | | | | 5 )COVER SHEET. COMMON PATH OF TRAVEL FROM THE MOST | | | REMOTE POINT UPSTAIRS IN THE STORAGE AREA TO AN EXIT | | | CAN BE UP TO 100 FT FOR STORAGE NON SPRINKLERRED | | | BUILDING WITH AN OCCUPANT LOAD OF LESS THAN 30. (FBC-B | | | 1014.3EXC. # 2) . THE ISSUE IS GOING TO BE THE OCCUPANT | | | LOADING IF TAKEN AT 500 SQ. FT. VERSES THE 300 SQ. FT. | | | VERSES IF THIS IS GOING TO BE SET UP AS A ART GALLERY. | | | | | | 6) PLEASE PROVIDE A SITE PLAN SHOWING AN ACCESSIBLE | | | ENTRANCE, THE ENTRY ON A 45 DEGREE ANGLE SHOWS STEPS. | | | 206.4 ENTRANCES. | | | ENTRANCES SHALL BE PROVIDED IN ACCORDANCE WITH 206.4. | | | ENTRANCE DOORS, DOORWAYS, AND GATES SHALL COMPLY WITH | | | 404 AND SHALL BE ON AN ACCESSIBLE ROUTE COMPLYING WITH | | | 402. | | | | | | 7) PLEASE SHOW COMPLIANCE WITH AN ACCESSIBLE ROUTE TO | | | THE 2ND FLOOR. 2010 FBC-ACC. CODE | | | 206.7 PLATFORM LIFTS. PLATFORM LIFTS SHALL COMPLY WITH | | | 410. PLATFORM LIFTS SHALL BE PERMITTED AS A COMPONENT | | | OF AN ACCESSIBLE ROUTE IN NEW CONSTRUCTION IN | | | ACCORDANCE WITH 206.7. PLATFORM LIFTS SHALL BE | | | PERMITTED AS A COMPONENT OF AN ACCESSIBLE ROUTE IN AN | | | EXISTING BUILDING OR FACILITY. | | | 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS | | | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR | | | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY | | | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE | | | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL | | | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE | | | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE | | | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH | | | BUILDING, STRUCTURE OR FACILITY, | | | | | | 8) PLEASE PROVIDE COMPLIANCE WITH 2010 FL ACC. CODE | | | 202.4.1 DISPROPORTIONATE COST. THE CONTRACTOR IS TO | | | CREATE ON THEIR OWN LETTER HEAD AN ITEMIZED LIST WHERE | | | $14,000.00 IN ACCESSIBLE UPGRADES IN THE LISTED ORDER | | | BELOW. | | | 2010 FL ACC. CODE 202.4.1 DISPROPORTIONATE COST. | | | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF | | | TRAVEL TO THE ALTERED AREA WILL BE DEEMED | | | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE | | | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE | | | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS | | | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF | | | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING | | | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE | | | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING | | | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, | | | ENLARGING TOILET STALLS, INSULATING PIPES, OR | | | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS | | | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH | | | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, | | | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT | | | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING | | | AN INACCESSIBLE DRINKING FOUNTAIN. | | | | | | 9) PLANS MAY NEED TO BE SUBMITED TO PALM BEACH COUNTY | | | FOR IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO | | | CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST | | | BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID | | | RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL | | | (561)233-5025 FOR MORE INFORMATION. | | | | | | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE | | | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2015-01-31 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-01-31 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-01-31 |
Time |
14:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2014-12-02 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-12-02 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-12-02 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2014-12-02 15:24:25 | DATE: 12/2/2014 | | | PROJECT: DUPONT RENNOVATION | | | PERMIT#: 14090842 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 3RD ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED. | | | | | | 1) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE | | | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND | | | SPECIFIC PURPOSE OR USE. THE IDENTIFICATIO SHALL | | | INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | | DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT | | | CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE | | | DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE | | | INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE | | | FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A | | | PANELBOARD, AND LOCATED AT EACH SWITCH ON A | | | SWITCHBOARD. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER | | | THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY. | | | REVICE PANEL SCHEDULE TO INDICATE WHICH ARE NEW AND | | | WHICH ARE EXISTING CIRCUITS THROUGHOUT. AND PROVIDE | | | EACH CIRCUIT WITH IT'S CLEAR EVIDENT AND SPECIFIC | | | PURPOSE. SEE NEC 408.4 | | | | | | 2) INDICATE THE LOCATION OF THE A/C CONDENSING UNITS ON | | | THE FLOOR PLAN WITH THEIR CORRESPONDING ELECTRICAL | | | CIRCUIT. REVISE THE PANEL SCHEDULE TO INDICATE ALL A/C | | | CONDESNSING UNITS CIRCUITS | | | | | | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. NEC 110.9 PROVIDE A FAULT CURRENT | | | CALCULATION. | | | | | | 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.16, 110.22 | | | | | | 5) CLARIFICATION REQUIRED FOR THE OPERATION OF THE | | | OCCUPANCY SENSOR SWITCHES ON THE PROPOSED 1ST FL | | | ELECTRICAL PLAN. PLEASE INDICATE HOW THE OSS IS | | | PROPOSED TO CONTROL THE MULTIPLE LIGHTING CIRCUITS | | | INDICATED ON THE FLOOR PLAN. FBC 505.2. | | | | | | 6) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | IS REQUIRED FOR SECURITY, CCTV, NETWORK, DATA, | | | COMMUNICATION, FIRE ALARM, GENERATORS, AND/OR ACCESS | | | CONTROL SYSTEM. | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-11-19 |
|
|
Cont ID |
|
| Sent By |
DHAYES |
Date |
2014-11-19 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-11-19 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2014-11-19 11:58:34 | DATE: 11/19/2014 | | | PROJECT: DUPONT RENNOVATION | | | PERMIT#: 14090842 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE | | | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND | | | SPECIFIC PURPOSE OR USE. THE IDENTIFICATIO SHALL | | | INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE | | | DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT | | | CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE | | | DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE | | | INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE | | | FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A | | | PANELBOARD, AND LOCATED AT EACH SWITCH ON A | | | SWITCHBOARD. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER | | | THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY. | | | REVICE PANEL SCHEDULE TO INDICATE WHICH ARE NEW AND | | | WHICH ARE EXISTING CIRCUITS THROUGHOUT. NEC 408.4 | | | | | | 2) INDICATE THE LOCATION OF THE A/C CONDENSING UNITS ON | | | THE FLOOR PLAN WITH THEIR CORRESPONDING ELECTRICAL | | | CIRCUIT. REVISE THE PANEL SCHEDULE TO INDICATE ALL A/C | | | CONDESNSING UNITS CIRCUITS | | | | | | 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. NEC 110.9 PROVIDE A FAULT CURRENT | | | CALCULATION. | | | | | | 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.16, 110.22 | | | | | | 5) CLARIFICATION REQUIRED FOR THE SYMBOL IDENTIFIED AS | | | AN OCCUPANCY SENSOR SWITCH THAT IS SHOWN AT THE EGRESS | | | DOORS ON THE PROPOSED 1ST FL ELECTRICAL PLAN. THERE ARE | | | ALSO 3WAY SWITCHES INDICATING THE CONTROL OF THE | | | LIGHTING FOR THE SPACE. PLEASE INDICATE COMPLIANCE TO | | | THE FBC 505.2.4 LIGHTING SYSTEMS SHALL BE PROVIDED WITH | | | CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2, | | | 505.2.3 AND 505.2.4. | | | | | | 6) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | IS REQUIRED FOR SECURITY, CCTV, NETWORK, DATA, | | | COMMUNICATION, FIRE ALARM, GENERATORS, AND/OR ACCESS | | | CONTROL SYSTEM. | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-09-24 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-09-24 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-09-24 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2014-09-24 10:35:18 | DATE: 9/24/2014 | | | PROJECT: DUPONT RENNOVATION | | | PERMIT#: 14090842 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) REVISE PANEL SCHEDULES TO INCLUDE ALL A/C UNITS AND | | | AND RECEPTACLE CIRCUITS THROUGHOUT. | | | | | | 2) REVISE LOAD CALCULATION TO INCLUDE LOADS FOR ALL | | | CIRCUITS IN REVISED PANEL SCHEDULES INCLUDING ALL A/C | | | AND HEATING LOADS. | | | | | | 3) REVISE RISER DIAGRAM TO INCLUDE THE GROUNDING | | | ELECTRODE SYSTEM DETAIL, AS WELL AS CONDUIT AND WIRE | | | SIZES AND TYPES. | | | | | | 4) REVISE FLOOR PLAN TO INCLUDE CIRCUITING FOR OUTLETS, | | | LIGHTING AND EQUIPMENT TO CORESPOND TO REVISED PANEL | | | SCHEDULES. | | | | | | 5) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL | | | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT | | | SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. | | | EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT | | | EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL | | | BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND | | | BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC | | | 700.12(F) CIRCUIT THE EMERGENCY AND EXIT LIGHTING TO BE | | | WIRED AHEAD OF ANY SWITCHING AND ON THE SAME CIRCUIT | | | AND THE GENERAL LIGHTING IN THE AREA THEY SERVE. NEC | | | 700.12(F) | | | B.)EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED | | | MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND | | | ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE | | | REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL | | | BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY | | | INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF | | | A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT | | | REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 ADDITIONAL | | | EMERGENCY FIXTURES WILL BE REQUIRED TO ACCOMPLISH THIS. | | | SEE AREAS AT STAIRWELL AND AREAS BETWEEN NEW | | | PARTITIONS. NEC 700.16 | | | | | | 6) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN | | | SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY | | | CODE REQUIREMENTS. FBC - ENERGY 505.3 | | | | | | 7) LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS | | | REQUIRED IN FBC - ENERGY 505.2.1, 505.2.2, 505.2.3 AND | | | 505.2.4. | | | BUILDINGS LARGER THAN 5,000 SQUARE FEET (465 M2) SHALL | | | BE EQUIPPED WITH AN AUTOMATIC CONTROL DEVICE TO SHUT | | | OFF LIGHTING IN THOSE AREAS. FBC 505.2.2. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2015-02-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-02-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-02-10 |
Time |
14:54 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2014-12-10 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-12-10 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-12-10 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2014-12-10 16:18:42 | PREVIOUS PLAN REVIEW COMMENTS NOT ADDRESSED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2014-11-07 |
|
|
Cont ID |
|
| Sent By |
PLEDUC |
Date |
2014-11-07 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-11-05 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2014-11-07 10:51:08 | 431 BUNKER ROAD | | | PERMIT #14090842 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | COMMON PATH OF TRAVEL EXCEEDS FOR 50FT FOR A | | | NON-SPRINKLERED BUILDING. | | | | | | MEZZANINE EXCEEDS MORE THAN ONE-THIRD OF FLOOR AREA. | | | THIS UPPER LEVEL WILL BE TREATED AS A SECOND FLOOR. | | | | | | PROVIDE WRITTTEN BUSINESS DESCRIPTION TO VERIFY | | | OCCUPANCY WIL BE USED AS STORAGE OCCUPANCY ANDL NOT BE | | | USED AS MERCANTILE OCCUPANCY WHERE A TRANSACTION OF | | | BUSINESS OCCURS. | | | | | | PROVIDE HANDRAIL/GUARD RAIL DETAILS FOR ALL STEP DOWN | | | SHOWN ON PLANS. | | | | | | INDICATE HOW STORAGE WILL BE MAINTAINED TO PROVIDE 24" | | | FROM THE CEILING. | | | | | | ROY LINDOW | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-10-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2014-10-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2014-10-03 |
Time |
12:37 |
Sent To |
Z |
|
| Notes |
| 2014-10-03 13:24:56 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | A STORAGE OCCUPANCY SHALL COMPLY WITH NFPA 101, FLORIDA | | | LIFE SAFETY CODE, FLORIDA 2010 EDITION. | | | | | | SHEET 1 OF 3 INDICATES THAT THE PREVIOUS OCCUPANCY AND | | | PROPOSED OCCUPANCY AS BUSINESS/STORAGE. HOWEVER, SHEET | | | 2 OF 3 DOES NOT INDICATE ANY BUSINESS SPACES. PLEASE | | | INDICATE AND/OR IDENTIFY THE OCCUPANY BUSINESS INTENT | | | AND THE AREAS OF BUSINESS WITHIN THE OCCUPANY. | | | | | | IF THIS IS A MIXED OCCUPANY, PLEASE INDICATE SUCH AND | | | THE PROPOSED CHAPTER/PROVISION YOU ARE COMPLYING WITH. | | | | | | IDENTIFY THE PROPOSED STORAGE TYPE AND | | | COMMODITY/MATERIAL BEING STORED. | | | | | | SHEET 2 OF 3 INDICATES THE MAX NUMBER OF EMPLOYEES PER | | | SHIFT = 2. WHAT CONSTITUTES A SHIFT? WILL THERE BE | | | MANUFACTURING OR WORK BEING PRODUCED? WILL THE GENERAL | | | PUBLIC BE VISITING OR PATRONIZING THIS STORAGE | | | OCCUPANCY? | | | | | | | | | IDENTIFY THE EXISTING AND PROPOSED LIFE SAFETY FEATURES | | | AND SYSTEMS FOR THE BUILDING. | | | | | | SHEET 2 OF 3 INDICATES THE ADDITON OF ADDITIONAL | | | INTERIOR WALLS. SHEET 3 OF 3 INDICATES 1 EXIT EMERGENCY | | | LIGHT AND 1 EMERGENCY LIGHT ON THE 1ST FLOOR. | | | ADDITIONAL EXIT SIGNAGE EMERGENCY LIGHTING IS REQUIRED | | | TO ILLUMINATE THE THE EXIT PASSAGE FROM THE REST ROOM | | | AREA AND THE INTERIOR DOOR BY THE REST ROOM. | | | | | | SHEET 2 OF 3 DOES NOT INDICATE AN EMERGENCY LIGHT | | | ILLUMINATING THE EXIT STAIR. | | | | | | BASED ON THE STORAGE AND COMMODITY TYPE YOU WILL BE | | | PROVIDING THE COMMON PATH OF TRAVEL FROM THE SECOND | | | FLOOR AND AND THE FIRST FLOOR BATHROOM AREA MAY EXCEED | | | THE 50FT MAXIMUM OF ORDINARY HAZARD STORAGE. | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2015-02-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-02-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-01-29 |
Time |
07:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-12-10 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-12-10 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-11-26 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2014-11-26 17:23:17 | RE-SUBMITTAL SENT TO B10 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-11-19 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-11-19 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-10-31 |
Time |
06:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-10-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2014-10-10 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2014-09-23 |
Time |
09:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
N |
Date |
2014-11-05 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-11-05 |
Time |
08:12 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-11-05 |
Time |
08:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2014-10-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-10-01 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-10-01 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2014-10-01 08:43:33 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2014-12-03 |
|
|
Cont ID |
|
| Sent By |
rbergsma |
Date |
2014-12-03 |
Time |
|
Rev Time |
0.50 |
| Received By |
rbergsma |
Date |
2014-12-03 |
Time |
|
Sent To |
|
|
| Notes |
| 2014-12-03 15:17:28 | PREVIOUS COMMENTS ADDRESSED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2014-11-18 |
|
|
Cont ID |
|
| Sent By |
HMOSER |
Date |
2014-11-18 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2014-11-18 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2014-11-18 13:01:22 | PLAN DENIED | | | | | | 1) PROVIDE THE SIGNATURE AND LICENSE NUMBER OF WHO EVER | | | DREW THE PLANS | | | ON THE PLAN. | | | 2) PROVIDE A DETAIL FROM A ENGINEER ON THE CONDENSER | | | STAND TIE DOWN TO | | | THE ROOF, AND CONDENSER TO STAND TIE DOWN. PER SECTION | | | 301.12 | | | WIND RESISTANCE 2010 FBC (M) | | | 3) SHOW ROOF ACCESS ON PLAN PER SECTION 306.5 EQUIPMENT | | | AND APPLIANCES ON ROOF OR ELEVATED STRUCTURES. 2010 FBC | | | (M) | | | 4) REFER TO SECTION 304.11 GUARDS. | | | 5) AIR HANDLER DETAIL SHOWS CLOSET TO BE A RETURN AIR | | | PLENUM. | | | REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-09-26 |
|
|
Cont ID |
|
| Sent By |
rbergsma |
Date |
2014-09-26 |
Time |
|
Rev Time |
0.50 |
| Received By |
rbergsma |
Date |
|
Time |
|
Sent To |
P |
|
| Notes |
| 2014-09-26 12:59:09 | PLEASE REVIEW; | | | ON THE FIRST FLOOR THE BATH ROOM AND A/H AREA ARE NOT | | | IN THE SAME LOCATION AS THE MASTER PLAN | | | IS THE CONDENSER STAND ON THE ROOF LARGE ENOUGH FOR THE | | | 2 UNITS SPECIFIED (3 AND 4), THERE APPEARS TO BE | | | ONLY ONE THERE NOW, DETAIL NEW STANDS IF REQUIRED | | | ROOF ACCESS | | | EQUIPMENT CFM | | | O/A LOAD BASED ON HOW MANY OCCUPANTS | | | ENERGY, AIR BALANCE DETAIL | | | AIR HANDLER, LINE SET ROUTE AND CONDENSATE DRAIN | | | DETAILS | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2014-12-05 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-12-05 |
Time |
04:18 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-12-04 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2014-11-15 |
|
|
Cont ID |
|
| Sent By |
TKLARGE |
Date |
2014-11-15 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-11-15 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2014-11-15 10:48:24 | 1) SHT.2 OF 3 - SANITARY ISOMETRIC - THE FIRST FLOOR | | | WATER CLOSET CANNOT BE VERTICALLY WET VENTED BY THE | | | SECOND FLOOR SOIL STACK/BATHROOM GROUP PERR SEC.909.1.1 | | | OF THE 2010 FLORIDA PLUMBING CODE. THE CONNECTION FOR | | | THE 2ND FLR. SHALL CONNECT EITHER UPSTREAM OR | | | DOWNSTREAM FROM THE LAV/DRINKING FOUNTAIN CONNECTION | | | POINT TO THE 4" BUILDING DRAIN BUT CANNOT CONNECT AT | | | THE SAME POINT AS DRAWN. | | | 2) CLEANOUTS ARE REQD. IN THE BASE OF THE SOIL STACKTO | | | THE SECOND FLOOR PER FPC SEC.708.3.4. | | | 3)CLEARLY SHOW ON THE PLANS THAT THE DRINKING FOUNTAIN | | | COMPLIES WITH THE FAC SECS.602.1 THROUGH 602.7. | | | 4)THE CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAINS | | | SHALL BE CENTERED ON EACH UNIT.THE PLANS SHOW THE CLEAR | | | FLOOR SPACE CENTERED ON BOTH UNITS. COMPLY W/ 2010 FAC | | | SEC. 602.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-09-27 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-09-27 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-09-27 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2014-09-27 09:55:00 | 1) SHT.2 OF 3 - SANITARY ISOMETRIC - THE FIRST FLOOR | | | WATER CLOSET CANNOT BE VERTICALLY WET VENTED BY THE | | | SECOND FLOOR SOIL STACK/BATHROOM GROUP PERR SEC.909.1.1 | | | OF THE 2010 FLORIDA PLUMBING CODE. | | | 2) SIZE THE VENT FOR THE 1ST. FLR LAVATORY. | | | 3) SIZE THE VENT FOR THE DRINKING FOUNTAIN. | | | 4) CLEANOUTS ARE REQD. IN THE BASE OF THE WASTE/SOIL | | | STACKS PER SEC.708.3.4. | | | 4) SHOW THE REQUIRED TOE CLEARANCES FOR THE LAVATORY | | | AND DRINKING FOUNTAINS PER THE 2010 FL. ACCESS. CODE. | | | SEC.306.2. | | | 5) SHOW THE REQUIRED KNEE CLEARANCES FOR THE LAVATORY | | | AND DRINKING FOUNTAINS PER THE 2010 FAC SEC. 306.3. | | | 6) CLEARLY SHOW ON THE PLANS THAT THE DRINKING FOUNTAIN | | | COMPLIES WITH THE FAC SECS.602.1 THROUGH 602.7. | | | 7) THE CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAINS | | | SHALL BE CENTERED ON EACH UNIT.THE PLANS SHOW THE CLEAR | | | FLOOR SPACE CENTERED ON BOTH UNITS. COMPLY W/ 2010 FAC | | | SEC. 602.2. | | | 8) SUBMIT ENLARGED HANDICAPPED BATHROOM AND DRINKING | | | FOUNTAIN PLAN THAT CLEARLY SHOWS THE REQUIRED CLEAR | | | FLOOR SPACE DIMENSIONS AND ALSO THE LOCATION OF THE | | | GRAB BARS. THE DETAILS ON THE PLAN ARE NOT | | | CLEAR/LEGIBLE. THE GRAB BARS SHALL BE LOCATED PER SECS. | | | 604.5.1 & 604.5.2 OF THE 2010 FAC. | | | 9) A SHUT OFF VALVE IS REQD. ON THE WATER PIPE RISER TO | | | THE 2ND FLOOR BATH PER THE 2010 FPC SEC. 606.1 (4). | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2014-10-09 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2014-10-09 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2014-10-09 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2014-09-26 15:18:56 | 9/26/14 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |