Plan Review Details - Permit 14090842
Plan Review Stops For Permit 14090842
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-02-03 Cont ID  
Sent By jwitmer Date 2015-02-03 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2015-02-03 Time 06:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-12-02 Cont ID  
Sent By jwitmer Date 2014-12-02 Time 06:53 Rev Time 0.00
Received By jwitmer Date 2014-12-02 Time 06:01 Sent To  
Notes
2014-12-02 06:52:59BUILDING PLAN REVIEW
 PERMIT: 14090842
 ADD: 431 BUNKER RD
 CONT: SULLIVAN BUILDERS OF FL.
 TEL: (561) 310-1899
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 ***********NOTICE**********:CHAPTER 553.80(2)(B)
 FLORIDA STATUTES STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 3RD REVIEW
 DATE: TUES. DEC. 02/ 2014
 ACTION: DENIED
  
 1) COMPLIED.
 COVER SHEET INDICATES THIS OCCUPANCY TO BE STORAGE AND
 BUSINESS PLEASE PROVIDE THE BREAKDOWN IN SQUARE FEET
 THE OCCUPANCY AND OCCUPANCY LOAD FOR EACH AREA.
  
 2) COMPLIED. OCCUPANCY S-1
  
 3) COMPLIED. OCCUPANCY S-1 7815/300= 27 NOT 26.
  
 4) #RD REQUEST. THE DESIGNER OF RECORD HAS DECALRED
 THIS TO BE A LEVEL 2 ALTERATION. PLEASE REVIEW SECTION
 2010 FBC-EXST. 703.2.3 SUPPLEMENTAL STAIRWAY ENCLOSURE
 REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS THAT ARE PART
 OF THE MEANS OF EGRESS SERVING THE WORK AREA SHALL, AT
 A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT CONSTRUCTION ON
 THE HIGHEST WORK AREA FLOOR AND ALL FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
 PLEASE PROVIDE FOR A SECOND FLOOR HOW THE CODES ALLOW
 FOR A OPEN STAIRWAY. NOTE THIS IS A NON-SPRINKLERED
 BUILDING, OVER 33% OF FLOOR AREA NOT CONSIDERED A
 MEZZANINE BUT A 2ND FLOOR. 2010 FBC-B 1014.3. THE FLOOR
 AREA OF THE 2ND FLOOR IS 48% OF THE 1ST FLOOR.
  
 NOTE; THE REMOVAL OF STIAR ENCLOSURES CREATES A
 NON-CONFORMITY, UNDER PERMIT # 13060708 PLANS SHOWED AN
 EXISTING STAIR ENCLOSURE. A NEW EXTERIOR DOOR WAS TO BE
 INSTALLED IN THE EXTERIOR WALL SO THE 2ND FLOOR TENANTS
 WOULD BE ABLE TO EXIT THE ENCLOSURE WITHOUT GOING
 THROUGH THE OTHER TENANTCY.
  
 5 ) 3RD REQUEST. COVER SHEET. COMMON PATH OF TRAVEL
 FROM THE MOST REMOTE POINT UPSTAIRS IN THE STORAGE AREA
 TO AN EXIT CAN BE UP TO 100 FT FOR STORAGE NON
 SPRINKLERRED BUILDING WITH AN OCCUPANT LOAD OF LESS
 THAN 30. (FBC-B 1014.3EXC. # 2) . THE TRAVEL DISTANCE
 FROM THE MOST REMOTE POINT APPROX. 105 FT.
  
 6) COMPLIED.
 PLEASE PROVIDE A SITE PLAN SHOWING AN ACCESSIBLE
 ENTRANCE, THE ENTRY ON A 45 DEGREE ANGLE SHOWS STEPS.
 206.4 ENTRANCES.
 ENTRANCES SHALL BE PROVIDED IN ACCORDANCE WITH 206.4.
 ENTRANCE DOORS, DOORWAYS, AND GATES SHALL COMPLY WITH
 404 AND SHALL BE ON AN ACCESSIBLE ROUTE COMPLYING WITH
 402.
  
 7) COMPLIED.
 SHOWING LIFT DISPROPORTIONATE. PLEASE SHOW COMPLIANCE
 WITH AN ACCESSIBLE ROUTE TO THE 2ND FLOOR. 2010
 FBC-ACC. CODE
 206.7 PLATFORM LIFTS. PLATFORM LIFTS SHALL COMPLY WITH
 410. PLATFORM LIFTS SHALL BE PERMITTED AS A COMPONENT
 OF AN ACCESSIBLE ROUTE IN NEW CONSTRUCTION IN
 ACCORDANCE WITH 206.7. PLATFORM LIFTS SHALL BE
 PERMITTED AS A COMPONENT OF AN ACCESSIBLE ROUTE IN AN
 EXISTING BUILDING OR FACILITY.
 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY,
  
  
  
 8) COMPLIED
 . SHOWING LIFT IS DISPROPORTIONATE. PLEASE PROVIDE
 COMPLIANCE WITH 2010 FL ACC. CODE 202.4.1
 DISPROPORTIONATE COST. THE CONTRACTOR IS TO CREATE ON
 THEIR OWN LETTER HEAD AN ITEMIZED LIST WHERE $14,000.00
 IN ACCESSIBLE UPGRADES IN THE LISTED ORDER BELOW.
 2010 FL ACC. CODE 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 9)COMPLIED.
 PLANS MAY NEED TO BE SUBMITED TO PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 10) THE PRODUCT APPROVALS SUBMITTED WERE NOT REVIEWED
 BY THE DESIGNER OF RECORD, NO SHOP DRAWING STAMP OF
 APPROVAL. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-11-05 Cont ID  
Sent By JWITMER Date 2014-11-05 Time 08:11 Rev Time 0.00
Received By jwitmer Date 2014-11-05 Time 07:03 Sent To  
Notes
2014-11-05 08:38:33BUILDING PLAN REVIEW
 PERMIT: 14090842
 ADD: 431 BUNKER RD
 CONT: SULLIVAN BUILDERS OF FL.
 TEL: (561) 310-1899
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED.NOV. 05/ 2014
 ACTION: DENIED
  
 1) COMPLIED.
 COVER SHEET INDICATES THIS OCCUPANCY TO BE STORAGE AND
 BUSINESS PLEASE PROVIDE THE BREAKDOWN IN SQUARE FEET
 THE OCCUPANCY AND OCCUPANCY LOAD FOR EACH AREA.
  
 2) COMPLIED. OCCUPANCY S-1
  
 3) COMPLIED. OCCUPANCY S-1 7815/300= 27 NOT 26.
  
 4) 2ND REQUEST. THE DESIGNER OF RECORD HAS DECLRED THIS
 TO BE A LEVEL 2 ALTERATION. PLEASE REVIEW SECTION 2010
 FBC-EXST. 703.2.3 SUPPLEMENTAL STAIRWAY ENCLOSURE
 REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS THAT ARE PART
 OF THE MEANS OF EGRESS SERVING THE WORK AREA SHALL, AT
 A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT CONSTRUCTION ON
 THE HIGHEST WORK AREA FLOOR AND ALL FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
 PLEASE PROVIDE FOR A SECOND FLOOR HOW THE CODES ALLOW
 FOR A OPEN STAIRWAY. NOTE THIS IS A NON-SPRINKLERED
 BUILDING, OVER 33% OF FLOOR AREA NOT CONSIDERED A
 MEZZANINE BUT A 2ND FLOOR. 2010 FBC-B 1014.3. THE FLOOR
 AREA OF THE 2ND FLOOR IS 48% OF THE 1ST FLOOR.
  
 5 ) 2ND REQUEST. COVER SHEET. COMMON PATH OF TRAVEL
 FROM THE MOST REMOTE POINT UPSTAIRS IN THE STORAGE AREA
 TO AN EXIT CAN BE UP TO 100 FT FOR STORAGE NON
 SPRINKLERRED BUILDING WITH AN OCCUPANT LOAD OF LESS
 THAN 30. (FBC-B 1014.3EXC. # 2) . THE TRAVEL DISTANCE
 FROM THE MOST REMOTE POINT APPROX. 105 FT.
  
 6) COMPLIED.
 PLEASE PROVIDE A SITE PLAN SHOWING AN ACCESSIBLE
 ENTRANCE, THE ENTRY ON A 45 DEGREE ANGLE SHOWS STEPS.
 206.4 ENTRANCES.
 ENTRANCES SHALL BE PROVIDED IN ACCORDANCE WITH 206.4.
 ENTRANCE DOORS, DOORWAYS, AND GATES SHALL COMPLY WITH
 404 AND SHALL BE ON AN ACCESSIBLE ROUTE COMPLYING WITH
 402.
  
 7) 2ND REQUEST. PLEASE SHOW COMPLIANCE WITH AN
 ACCESSIBLE ROUTE TO THE 2ND FLOOR. 2010 FBC-ACC. CODE
 206.7 PLATFORM LIFTS. PLATFORM LIFTS SHALL COMPLY WITH
 410. PLATFORM LIFTS SHALL BE PERMITTED AS A COMPONENT
 OF AN ACCESSIBLE ROUTE IN NEW CONSTRUCTION IN
 ACCORDANCE WITH 206.7. PLATFORM LIFTS SHALL BE
 PERMITTED AS A COMPONENT OF AN ACCESSIBLE ROUTE IN AN
 EXISTING BUILDING OR FACILITY.
 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY,
  
 THE OWNER HAS 3 OPTIONS;
 7A) INSTALL A LULA LIFT
 7B) THE CONTRACTOR ON THEIR LETTERHEAD PROVIDE THE
 LETTER SHOWING DISPROPORTIONATE COST. THE PERMIT VALUE
 OF $14,000 X 20%= $14,000.00 IN ACCESSIBLE UPGRADES IN
 THE ORDER LISTED BELOW.
 7C) APPLY TO THE STATE FOR A WAIVER SINCE THIS STORAGE
 OCCUPANCY IS NOT GOING TO BE OPEN TO THE PUBLIC.
  
 8) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2010 FL
 ACC. CODE 202.4.1 DISPROPORTIONATE COST. THE CONTRACTOR
 IS TO CREATE ON THEIR OWN LETTER HEAD AN ITEMIZED LIST
 WHERE $14,000.00 IN ACCESSIBLE UPGRADES IN THE LISTED
 ORDER BELOW.
 2010 FL ACC. CODE 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 9)COMPLIED.
 PLANS MAY NEED TO BE SUBMITED TO PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED
 TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025
 FOR MORE INFORMATION.
  
 10) THE PRODUCT APPROVALS SUBMITTED WERE NOT REVIEWED
 BY THE DESIGNER OF RECORD, NO SHOP DRAWING STAMP OF
 APPROVAL. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-01 Cont ID  
Sent By jwitmer Date 2014-10-01 Time 08:42 Rev Time 0.00
Received By jwitmer Date 2014-10-01 Time 07:30 Sent To  
Notes
2014-10-01 08:42:50BUILDING PLAN REVIEW
 PERMIT: 14090842
 ADD: 431 BUNKER RD
 CONT: SULLIVAN BUILDERS OF FL.
 TEL: (561) 310-1899
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 1/ 2014
 ACTION: DENIED
  
 1) COVER SHEET INDICATES THIS OCCUPANCY TO BE STORAGE
 AND BUSINESS PLEASE PROVIDE THE BREAKDOWN IN SQUARE
 FEET THE OCCUPANCY AND OCCUPANCY LOAD FOR EACH AREA.
  
 2) THE COVER SHEET DOES NOT INDICATE THE TYPE OF
 STORAGE OCCUPANCY THIS WILL BE S1 OR S2, DECLARE
 OCCUPANCY AND WHAT TYPE OF ARTICLES ARE GOING TO BE
 STORED. WILL THE PUBLIC BE ALLOWED INTO THE STORAGE
 AREA, OR WILL THE PUBLIC ONLY BE ALLOWED IN THE OFFICE/
 BUSINESS AREA. OFFICE AREA IS NOT DEFINED ON THE PLAN.
 IS THIS SEPARARTED OR NON-SEPARATED USE? THIS APPEARS
 TO BE SET UP AS A ART GALLERY WHICH IS NOT CONSIDERED A
 STORAGE OCCUPANCY BUT AN A3 USAGE.2010 FBC-B TABLE
 508.4, 508.2 508.2.4, 508.3, 508.3.3 & 303.1- A3.
  
 3) THE COVER SHEET INDICATES THE STORAGE OCCUPANCY AT
 500 FT /OCCUPANT. PLOEASE SEE TABLE 1004.1.1 STORAGE IS
 300 GROSS, WAREHOUSE IS 500 GROSS, PLEASE PROVIDE
 ADDITIONAL INFORMATION HOW THE CLIENT INTENDS TO USE
 THIS SPACE, IT APPEARS TO BE SET UP AS A ART GALLERY.
 2010 FBC-B TABLE 1004.1.1.
  
 4) THE DESIGNER OF RECORD HAS DECLRED THIS TO BE A
 LEVEL 2 ALTERATION. PLEASE REVIEW SECTION 2010
 FBC-EXST. 703.2.3 SUPPLEMENTAL STAIRWAY ENCLOSURE
 REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS THAT ARE PART
 OF THE MEANS OF EGRESS SERVING THE WORK AREA SHALL, AT
 A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT CONSTRUCTION ON
 THE HIGHEST WORK AREA FLOOR AND ALL FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
 PLEASE PROVIDE FOR A SECOND FLOOR HOW THE CODES ALLOW
 FOR A OPEN STAIRWAY. NOTE THIS IS A NON-SPRINKLERED
 BUILDING, OVER 33% OF FLOOR AREA NOT CONSIDERED A
 MEZZANINE BUT A 2ND FLOOR. 2010 FBC-B 1014.3.
  
 5 )COVER SHEET. COMMON PATH OF TRAVEL FROM THE MOST
 REMOTE POINT UPSTAIRS IN THE STORAGE AREA TO AN EXIT
 CAN BE UP TO 100 FT FOR STORAGE NON SPRINKLERRED
 BUILDING WITH AN OCCUPANT LOAD OF LESS THAN 30. (FBC-B
 1014.3EXC. # 2) . THE ISSUE IS GOING TO BE THE OCCUPANT
 LOADING IF TAKEN AT 500 SQ. FT. VERSES THE 300 SQ. FT.
 VERSES IF THIS IS GOING TO BE SET UP AS A ART GALLERY.
  
 6) PLEASE PROVIDE A SITE PLAN SHOWING AN ACCESSIBLE
 ENTRANCE, THE ENTRY ON A 45 DEGREE ANGLE SHOWS STEPS.
 206.4 ENTRANCES.
 ENTRANCES SHALL BE PROVIDED IN ACCORDANCE WITH 206.4.
 ENTRANCE DOORS, DOORWAYS, AND GATES SHALL COMPLY WITH
 404 AND SHALL BE ON AN ACCESSIBLE ROUTE COMPLYING WITH
 402.
  
 7) PLEASE SHOW COMPLIANCE WITH AN ACCESSIBLE ROUTE TO
 THE 2ND FLOOR. 2010 FBC-ACC. CODE
 206.7 PLATFORM LIFTS. PLATFORM LIFTS SHALL COMPLY WITH
 410. PLATFORM LIFTS SHALL BE PERMITTED AS A COMPONENT
 OF AN ACCESSIBLE ROUTE IN NEW CONSTRUCTION IN
 ACCORDANCE WITH 206.7. PLATFORM LIFTS SHALL BE
 PERMITTED AS A COMPONENT OF AN ACCESSIBLE ROUTE IN AN
 EXISTING BUILDING OR FACILITY.
 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS
 553.501-553.513, F.S., AND THE ADA STANDARDS FOR
 ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY,
  
 8) PLEASE PROVIDE COMPLIANCE WITH 2010 FL ACC. CODE
 202.4.1 DISPROPORTIONATE COST. THE CONTRACTOR IS TO
 CREATE ON THEIR OWN LETTER HEAD AN ITEMIZED LIST WHERE
 $14,000.00 IN ACCESSIBLE UPGRADES IN THE LISTED ORDER
 BELOW.
 2010 FL ACC. CODE 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 9) PLANS MAY NEED TO BE SUBMITED TO PALM BEACH COUNTY
 FOR IMPACT FEE ASSESSMENT. BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-01-31 Cont ID  
Sent By dhayes Date 2015-01-31 Time 14:49 Rev Time 0.00
Received By dhayes Date 2015-01-31 Time 14:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-12-02 Cont ID  
Sent By dhayes Date 2014-12-02 Time 15:16 Rev Time 0.00
Received By dhayes Date 2014-12-02 Time 15:16 Sent To  
Notes
2014-12-02 15:24:25DATE: 12/2/2014
 PROJECT: DUPONT RENNOVATION
 PERMIT#: 14090842
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PREVIOUS COMMENTS HAVE NOT BEEN ADDRESSED.
  
 1) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATIO SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER
 THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.
 REVICE PANEL SCHEDULE TO INDICATE WHICH ARE NEW AND
 WHICH ARE EXISTING CIRCUITS THROUGHOUT. AND PROVIDE
 EACH CIRCUIT WITH IT'S CLEAR EVIDENT AND SPECIFIC
 PURPOSE. SEE NEC 408.4
  
 2) INDICATE THE LOCATION OF THE A/C CONDENSING UNITS ON
 THE FLOOR PLAN WITH THEIR CORRESPONDING ELECTRICAL
 CIRCUIT. REVISE THE PANEL SCHEDULE TO INDICATE ALL A/C
 CONDESNSING UNITS CIRCUITS
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 PROVIDE A FAULT CURRENT
 CALCULATION.
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) CLARIFICATION REQUIRED FOR THE OPERATION OF THE
 OCCUPANCY SENSOR SWITCHES ON THE PROPOSED 1ST FL
 ELECTRICAL PLAN. PLEASE INDICATE HOW THE OSS IS
 PROPOSED TO CONTROL THE MULTIPLE LIGHTING CIRCUITS
 INDICATED ON THE FLOOR PLAN. FBC 505.2.
  
 6) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR SECURITY, CCTV, NETWORK, DATA,
 COMMUNICATION, FIRE ALARM, GENERATORS, AND/OR ACCESS
 CONTROL SYSTEM.
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-11-19 Cont ID  
Sent By DHAYES Date 2014-11-19 Time 11:13 Rev Time 0.00
Received By dhayes Date 2014-11-19 Time 11:13 Sent To  
Notes
2014-11-19 11:58:34DATE: 11/19/2014
 PROJECT: DUPONT RENNOVATION
 PERMIT#: 14090842
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. THE IDENTIFICATIO SHALL
 INCLUDE SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS. SPARE POSITIONS THAT
 CONTAIN UNUSED OVERCURRENT DEVICES OR SWITCHES SHALL BE
 DESCRIBED ACCORDINGLY. THE IDENTIFICATION SHALL BE
 INCLUDED IN A CIRCUIT DIRECTORY THAT IS LOCATED ON THE
 FACE OR INSIDE OF THE PANEL DOOR IN THE CASE OF A
 PANELBOARD, AND LOCATED AT EACH SWITCH ON A
 SWITCHBOARD. NO CIRCUIT SHALL BE DESCRIBED IN A MANNER
 THAT DEPENDS ON TRANSIENT CONDITIONS OF OCCUPANCY.
 REVICE PANEL SCHEDULE TO INDICATE WHICH ARE NEW AND
 WHICH ARE EXISTING CIRCUITS THROUGHOUT. NEC 408.4
  
 2) INDICATE THE LOCATION OF THE A/C CONDENSING UNITS ON
 THE FLOOR PLAN WITH THEIR CORRESPONDING ELECTRICAL
 CIRCUIT. REVISE THE PANEL SCHEDULE TO INDICATE ALL A/C
 CONDESNSING UNITS CIRCUITS
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9 PROVIDE A FAULT CURRENT
 CALCULATION.
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) CLARIFICATION REQUIRED FOR THE SYMBOL IDENTIFIED AS
 AN OCCUPANCY SENSOR SWITCH THAT IS SHOWN AT THE EGRESS
 DOORS ON THE PROPOSED 1ST FL ELECTRICAL PLAN. THERE ARE
 ALSO 3WAY SWITCHES INDICATING THE CONTROL OF THE
 LIGHTING FOR THE SPACE. PLEASE INDICATE COMPLIANCE TO
 THE FBC 505.2.4 LIGHTING SYSTEMS SHALL BE PROVIDED WITH
 CONTROLS AS REQUIRED IN SECTIONS 505.2.1, 505.2.2,
 505.2.3 AND 505.2.4.
  
 6) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR SECURITY, CCTV, NETWORK, DATA,
 COMMUNICATION, FIRE ALARM, GENERATORS, AND/OR ACCESS
 CONTROL SYSTEM.
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-24 Cont ID  
Sent By dhayes Date 2014-09-24 Time 09:38 Rev Time 0.00
Received By dhayes Date 2014-09-24 Time 09:36 Sent To  
Notes
2014-09-24 10:35:18DATE: 9/24/2014
 PROJECT: DUPONT RENNOVATION
 PERMIT#: 14090842
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE PANEL SCHEDULES TO INCLUDE ALL A/C UNITS AND
 AND RECEPTACLE CIRCUITS THROUGHOUT.
  
 2) REVISE LOAD CALCULATION TO INCLUDE LOADS FOR ALL
 CIRCUITS IN REVISED PANEL SCHEDULES INCLUDING ALL A/C
 AND HEATING LOADS.
  
 3) REVISE RISER DIAGRAM TO INCLUDE THE GROUNDING
 ELECTRODE SYSTEM DETAIL, AS WELL AS CONDUIT AND WIRE
 SIZES AND TYPES.
  
 4) REVISE FLOOR PLAN TO INCLUDE CIRCUITING FOR OUTLETS,
 LIGHTING AND EQUIPMENT TO CORESPOND TO REVISED PANEL
 SCHEDULES.
  
 5) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF CHAPTER 3. NEC
 700.12(F) CIRCUIT THE EMERGENCY AND EXIT LIGHTING TO BE
 WIRED AHEAD OF ANY SWITCHING AND ON THE SAME CIRCUIT
 AND THE GENERAL LIGHTING IN THE AREA THEY SERVE. NEC
 700.12(F)
 B.)EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 ADDITIONAL
 EMERGENCY FIXTURES WILL BE REQUIRED TO ACCOMPLISH THIS.
 SEE AREAS AT STAIRWELL AND AREAS BETWEEN NEW
 PARTITIONS. NEC 700.16
  
 6) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC - ENERGY 505.3
  
 7) LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN FBC - ENERGY 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
 BUILDINGS LARGER THAN 5,000 SQUARE FEET (465 M2) SHALL
 BE EQUIPPED WITH AN AUTOMATIC CONTROL DEVICE TO SHUT
 OFF LIGHTING IN THOSE AREAS. FBC 505.2.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2015-02-10 Cont ID  
Sent By pleduc Date 2015-02-10 Time   Rev Time 0.00
Received By pleduc Date 2015-02-10 Time 14:54 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2014-12-10 Cont ID  
Sent By wjolin Date 2014-12-10 Time 16:18 Rev Time 0.00
Received By wjolin Date 2014-12-10 Time 16:18 Sent To  
Notes
2014-12-10 16:18:42PREVIOUS PLAN REVIEW COMMENTS NOT ADDRESSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-11-07 Cont ID  
Sent By PLEDUC Date 2014-11-07 Time 10:56 Rev Time 0.00
Received By wjolin Date 2014-11-05 Time 11:53 Sent To  
Notes
2014-11-07 10:51:08431 BUNKER ROAD
 PERMIT #14090842
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COMMON PATH OF TRAVEL EXCEEDS FOR 50FT FOR A
 NON-SPRINKLERED BUILDING.
  
 MEZZANINE EXCEEDS MORE THAN ONE-THIRD OF FLOOR AREA.
 THIS UPPER LEVEL WILL BE TREATED AS A SECOND FLOOR.
  
 PROVIDE WRITTTEN BUSINESS DESCRIPTION TO VERIFY
 OCCUPANCY WIL BE USED AS STORAGE OCCUPANCY ANDL NOT BE
 USED AS MERCANTILE OCCUPANCY WHERE A TRANSACTION OF
 BUSINESS OCCURS.
  
 PROVIDE HANDRAIL/GUARD RAIL DETAILS FOR ALL STEP DOWN
 SHOWN ON PLANS.
  
 INDICATE HOW STORAGE WILL BE MAINTAINED TO PROVIDE 24"
 FROM THE CEILING.
  
 ROY LINDOW
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By pleduc Date 2014-10-03 Time   Rev Time 0.00
Received By pleduc Date 2014-10-03 Time 12:37 Sent To Z
Notes
2014-10-03 13:24:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 A STORAGE OCCUPANCY SHALL COMPLY WITH NFPA 101, FLORIDA
 LIFE SAFETY CODE, FLORIDA 2010 EDITION.
  
 SHEET 1 OF 3 INDICATES THAT THE PREVIOUS OCCUPANCY AND
 PROPOSED OCCUPANCY AS BUSINESS/STORAGE. HOWEVER, SHEET
 2 OF 3 DOES NOT INDICATE ANY BUSINESS SPACES. PLEASE
 INDICATE AND/OR IDENTIFY THE OCCUPANY BUSINESS INTENT
 AND THE AREAS OF BUSINESS WITHIN THE OCCUPANY.
  
 IF THIS IS A MIXED OCCUPANY, PLEASE INDICATE SUCH AND
 THE PROPOSED CHAPTER/PROVISION YOU ARE COMPLYING WITH.
  
 IDENTIFY THE PROPOSED STORAGE TYPE AND
 COMMODITY/MATERIAL BEING STORED.
  
 SHEET 2 OF 3 INDICATES THE MAX NUMBER OF EMPLOYEES PER
 SHIFT = 2. WHAT CONSTITUTES A SHIFT? WILL THERE BE
 MANUFACTURING OR WORK BEING PRODUCED? WILL THE GENERAL
 PUBLIC BE VISITING OR PATRONIZING THIS STORAGE
 OCCUPANCY?
  
  
 IDENTIFY THE EXISTING AND PROPOSED LIFE SAFETY FEATURES
 AND SYSTEMS FOR THE BUILDING.
  
 SHEET 2 OF 3 INDICATES THE ADDITON OF ADDITIONAL
 INTERIOR WALLS. SHEET 3 OF 3 INDICATES 1 EXIT EMERGENCY
 LIGHT AND 1 EMERGENCY LIGHT ON THE 1ST FLOOR.
 ADDITIONAL EXIT SIGNAGE EMERGENCY LIGHTING IS REQUIRED
 TO ILLUMINATE THE THE EXIT PASSAGE FROM THE REST ROOM
 AREA AND THE INTERIOR DOOR BY THE REST ROOM.
  
 SHEET 2 OF 3 DOES NOT INDICATE AN EMERGENCY LIGHT
 ILLUMINATING THE EXIT STAIR.
  
 BASED ON THE STORAGE AND COMMODITY TYPE YOU WILL BE
 PROVIDING THE COMMON PATH OF TRAVEL FROM THE SECOND
 FLOOR AND AND THE FIRST FLOOR BATHROOM AREA MAY EXCEED
 THE 50FT MAXIMUM OF ORDINARY HAZARD STORAGE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-02-10 Cont ID  
Sent By pleduc Date 2015-02-10 Time   Rev Time 0.00
Received By pleduc Date 2015-01-29 Time 07:11 Sent To  
Notes
2015-01-31 07:17:54B14

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-12-10 Cont ID  
Sent By wjolin Date 2014-12-10 Time 16:22 Rev Time 0.00
Received By wjolin Date 2014-11-26 Time 17:22 Sent To  
Notes
2014-11-26 17:23:17RE-SUBMITTAL SENT TO B10 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-11-19 Cont ID  
Sent By dhayes Date 2014-11-19 Time 12:20 Rev Time 0.00
Received By dhayes Date 2014-10-31 Time 06:34 Sent To  
Notes
2014-11-01 06:35:02B07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-10 Cont ID  
Sent By skennedy Date 2014-10-10 Time 13:47 Rev Time 0.00
Received By skennedy Date 2014-09-23 Time 09:34 Sent To  
Notes
2014-09-24 09:36:09B04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-11-05 Cont ID  
Sent By jwitmer Date 2014-11-05 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2014-11-05 Time 08:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-10-01 Cont ID  
Sent By jwitmer Date 2014-10-01 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2014-10-01 Time 08:43 Sent To  
Notes
2014-10-01 08:43:33BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-12-03 Cont ID  
Sent By rbergsma Date 2014-12-03 Time   Rev Time 0.50
Received By rbergsma Date 2014-12-03 Time   Sent To  
Notes
2014-12-03 15:17:28PREVIOUS COMMENTS ADDRESSED

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-11-18 Cont ID  
Sent By HMOSER Date 2014-11-18 Time 13:01 Rev Time 0.00
Received By hmoser Date 2014-11-18 Time 10:26 Sent To  
Notes
2014-11-18 13:01:22PLAN DENIED
  
 1) PROVIDE THE SIGNATURE AND LICENSE NUMBER OF WHO EVER
 DREW THE PLANS
 ON THE PLAN.
 2) PROVIDE A DETAIL FROM A ENGINEER ON THE CONDENSER
 STAND TIE DOWN TO
 THE ROOF, AND CONDENSER TO STAND TIE DOWN. PER SECTION
 301.12
 WIND RESISTANCE 2010 FBC (M)
 3) SHOW ROOF ACCESS ON PLAN PER SECTION 306.5 EQUIPMENT
 AND APPLIANCES ON ROOF OR ELEVATED STRUCTURES. 2010 FBC
 (M)
 4) REFER TO SECTION 304.11 GUARDS.
 5) AIR HANDLER DETAIL SHOWS CLOSET TO BE A RETURN AIR
 PLENUM.
 REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-09-26 Cont ID  
Sent By rbergsma Date 2014-09-26 Time   Rev Time 0.50
Received By rbergsma Date   Time   Sent To P
Notes
2014-09-26 12:59:09PLEASE REVIEW;
 ON THE FIRST FLOOR THE BATH ROOM AND A/H AREA ARE NOT
 IN THE SAME LOCATION AS THE MASTER PLAN
 IS THE CONDENSER STAND ON THE ROOF LARGE ENOUGH FOR THE
 2 UNITS SPECIFIED (3 AND 4), THERE APPEARS TO BE
 ONLY ONE THERE NOW, DETAIL NEW STANDS IF REQUIRED
 ROOF ACCESS
 EQUIPMENT CFM
 O/A LOAD BASED ON HOW MANY OCCUPANTS
 ENERGY, AIR BALANCE DETAIL
 AIR HANDLER, LINE SET ROUTE AND CONDENSATE DRAIN
 DETAILS
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-12-05 Cont ID  
Sent By tklarge Date 2014-12-05 Time 04:18 Rev Time 0.00
Received By tklarge Date 2014-12-04 Time 15:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-11-15 Cont ID  
Sent By TKLARGE Date 2014-11-15 Time 10:48 Rev Time 0.00
Received By tklarge Date 2014-11-15 Time 10:26 Sent To  
Notes
2014-11-15 10:48:241) SHT.2 OF 3 - SANITARY ISOMETRIC - THE FIRST FLOOR
 WATER CLOSET CANNOT BE VERTICALLY WET VENTED BY THE
 SECOND FLOOR SOIL STACK/BATHROOM GROUP PERR SEC.909.1.1
 OF THE 2010 FLORIDA PLUMBING CODE. THE CONNECTION FOR
 THE 2ND FLR. SHALL CONNECT EITHER UPSTREAM OR
 DOWNSTREAM FROM THE LAV/DRINKING FOUNTAIN CONNECTION
 POINT TO THE 4" BUILDING DRAIN BUT CANNOT CONNECT AT
 THE SAME POINT AS DRAWN.
 2) CLEANOUTS ARE REQD. IN THE BASE OF THE SOIL STACKTO
 THE SECOND FLOOR PER FPC SEC.708.3.4.
 3)CLEARLY SHOW ON THE PLANS THAT THE DRINKING FOUNTAIN
 COMPLIES WITH THE FAC SECS.602.1 THROUGH 602.7.
 4)THE CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAINS
 SHALL BE CENTERED ON EACH UNIT.THE PLANS SHOW THE CLEAR
 FLOOR SPACE CENTERED ON BOTH UNITS. COMPLY W/ 2010 FAC
 SEC. 602.2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-27 Cont ID  
Sent By tklarge Date 2014-09-27 Time 09:55 Rev Time 0.00
Received By tklarge Date 2014-09-27 Time 09:36 Sent To  
Notes
2014-09-27 09:55:001) SHT.2 OF 3 - SANITARY ISOMETRIC - THE FIRST FLOOR
 WATER CLOSET CANNOT BE VERTICALLY WET VENTED BY THE
 SECOND FLOOR SOIL STACK/BATHROOM GROUP PERR SEC.909.1.1
 OF THE 2010 FLORIDA PLUMBING CODE.
 2) SIZE THE VENT FOR THE 1ST. FLR LAVATORY.
 3) SIZE THE VENT FOR THE DRINKING FOUNTAIN.
 4) CLEANOUTS ARE REQD. IN THE BASE OF THE WASTE/SOIL
 STACKS PER SEC.708.3.4.
 4) SHOW THE REQUIRED TOE CLEARANCES FOR THE LAVATORY
 AND DRINKING FOUNTAINS PER THE 2010 FL. ACCESS. CODE.
 SEC.306.2.
 5) SHOW THE REQUIRED KNEE CLEARANCES FOR THE LAVATORY
 AND DRINKING FOUNTAINS PER THE 2010 FAC SEC. 306.3.
 6) CLEARLY SHOW ON THE PLANS THAT THE DRINKING FOUNTAIN
 COMPLIES WITH THE FAC SECS.602.1 THROUGH 602.7.
 7) THE CLEAR FLOOR SPACE FOR THE DRINKING FOUNTAINS
 SHALL BE CENTERED ON EACH UNIT.THE PLANS SHOW THE CLEAR
 FLOOR SPACE CENTERED ON BOTH UNITS. COMPLY W/ 2010 FAC
 SEC. 602.2.
 8) SUBMIT ENLARGED HANDICAPPED BATHROOM AND DRINKING
 FOUNTAIN PLAN THAT CLEARLY SHOWS THE REQUIRED CLEAR
 FLOOR SPACE DIMENSIONS AND ALSO THE LOCATION OF THE
 GRAB BARS. THE DETAILS ON THE PLAN ARE NOT
 CLEAR/LEGIBLE. THE GRAB BARS SHALL BE LOCATED PER SECS.
 604.5.1 & 604.5.2 OF THE 2010 FAC.
 9) A SHUT OFF VALVE IS REQD. ON THE WATER PIPE RISER TO
 THE 2ND FLOOR BATH PER THE 2010 FPC SEC. 606.1 (4).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-10-09 Cont ID  
Sent By sgraham Date 2014-10-09 Time 16:02 Rev Time 0.00
Received By sgraham Date 2014-10-09 Time 16:02 Sent To  
Notes
2014-09-26 15:18:569/26/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved