Plan Review Details - Permit 14090818
Plan Review Stops For Permit 14090818
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-09 Cont ID  
Sent By sciard Date 2014-12-09 Time 14:35 Rev Time 0.00
Received By sciard Date 2014-12-09 Time 14:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-02 Cont ID  
Sent By dhayes Date 2014-10-02 Time 12:00 Rev Time 0.00
Received By dhayes Date 2014-10-02 Time 12:00 Sent To  
Notes
2014-10-02 12:16:1510/2/2014
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1 DUPLICATE COMMENTS AS FIRE REVIEW. PROVIDE PLOOR PLAN
 WITH LOCATION AND SUPPORTING DOCUMENTATION THAT THIS
 PANEL IS COMPATIBLE WITH EXISTING SYSTEM AND CIRCUIT
 FEEDING SAME. PROVIDE ELECTRICAL PERMIT FOR
 INSTALLATION CONNECTION OR RE-CONNECTION OF THE 110V
 DEDICATED CIRCUIT WITH BREAKER LOCK PER THE PROVISIONS
 OF THE NEC ARTICLE 760.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-11-25 Cont ID  
Sent By pleduc Date 2014-11-25 Time   Rev Time 0.00
Received By pleduc Date 2014-11-25 Time 14:47 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-09-29 Cont ID  
Sent By pleduc Date 2014-09-29 Time   Rev Time 0.00
Received By pleduc Date 2014-09-29 Time 13:40 Sent To E
Notes
2014-09-29 13:48:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVIDE A SITE FLOOR PLAN WITH LOCATION.
  
 PROVIDE VOLTAGE CALC'S.
  
 PROVIDE WORDING TO INSTALL PER NFPA WITH THIRD PARTY
 CERTIFICATIONS.
  
 PROVIDE WORDING THAT SYSTEM TO BE TESTED WITH
 CERTIFICATE OF COMPLETION ON FINAL INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-09 Cont ID  
Sent By sciard Date 2014-12-09 Time 14:35 Rev Time 0.00
Received By sciard Date 2014-11-25 Time 07:13 Sent To  
Notes
2014-11-25 07:13:26SENT TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-02 Cont ID  
Sent By dhayes Date 2014-10-02 Time 12:16 Rev Time  
Received By dhayes Date   Time   Sent To  
Notes
2014-09-23 12:05:13ROUTED TO FIRE