Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-13 Cont ID  
Sent By tklarge Date 2014-10-13 Time 06:36 Rev Time 0.00
Received By tklarge Date 2014-10-13 Time 06:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By tklarge Date 2014-09-27 Time 05:51 Rev Time 0.00
Received By tklarge Date 2014-09-27 Time 08:37 Sent To  
Notes
2014-09-27 08:45:551) THE DOCUMENT FROM FLORIDA SEPTIC TANK REFERS TO THE
 2007 FLORIDA PLUMBING CODE. THE PLUMBING CODE IN EFFECT
 IS THE 2010 FLORIDA PLUMBING CODE. THE INTERCEPTOR
 SHALL COMPLY W/ THE 2010 CODE.
 2) THE INLET INVERT SHALL DISCHARGE A MINIMUM 2 1/2
 INCHES ABOVE THE LIQUID LEVEL LINE AND THE OUTLET PIPE
 SHALL HAVE A TEE WITH A MINIMUM DIAMETER OF 4 INCHES
 THAT EXTENDS TO WITHIN 8 INCHES OF THE BOTTOM OF THE
 TANK. THE TEE SHALL BE INSTALLED WITH THE RUN IN THE
 VERTICAL DIRECTION PER SEC. 1003.5.3 OF THE 2010 FL.
 PLUMBING CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  