2014-09-26 12:04:42BUILDING PLAN REVIEW
 PERMIT: 14090761
 ADD: 2401 MERCER AVE BUILDING B
 CONT: GREENVIEW CONTRACTOR
 TEL: (561) 727-5013
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. SEPT. 26/ 2014
 ACTION: DENIED
  
 1) SHEET A-2 INDICATES UNDER THE HEADING CODE SUMMARY
 THIS BUILDING O BE A TYPE IV BUILDING WHICH IS HEAVY
 TIMBER CONSTRUCTION. PLEASE VERIFY TYPE OF
 CONSTRUCTION. 2010 FBC-B TABLE 601.
  
 2) THE DESIGNER OF RECORD HAS NOT DECLARED UNDER THE
 2010 FL EXISTING BUILDING CODE AS TO WHICH OF THE
 COMPLIANCE METHODS THE RENOVATION WAS DESIGNED. 2010 FL
 EXST BLDG CODE 101.5. FOR THE PURPOSE OF THIS REVIEW, I
 AM GOING TO REVIEW UNDER THE WORK AREA METHOD AS A
 LEVEL II ALTERATION. 2010 EXISTING BUILDING CODE LEVEL
 II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3) THE DESIGNER OF RECORD HAS INDICATED ON SHEET A-2
 THE AREA NOT TO BE INCLUDED IN THE WORK AREA AS N.I.C.
 THE REST OF THE BUILDING WILL BE REVIEWED AS THE AREA
 OF WORK TO BE COMPLETED AND IS TO BE REVIEWED FOR CODE
 COMPLIANCE.
  
 3A) THE CODE SUMMARY INDICATES THIS OCCUPANCY AS A
 EDUCATIONAL OCCUPANCY, NON-SPRINKLERED, THE PLANS FAIL
 TO INDICATE THE CORRIDOR WALLS TO BE 1 HOUR FIRE RATED
 WITH FIRE RATED DOORS SEE TABLE 715.4 AND TABLE 1018.1.
  
 3B) THE PLANS DO NOT INDICATE ANY DOOR SCHEDULE NOR
 HARDWARE FOR EGRESS DOORS. SHOW COMPLIANCE FOR
 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A
 GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES
 WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E
 OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
 UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 4C) THE OTHER ISSUE IS THIS IS A NON-SPRINKLERED
 BUILDING, EDUCATIONAL OCCUPANCY AND COMPLIANCE WITH
 SECTION 2010 FBC-B 1029.4.1
 EVERY ROOM OR SPACE GREATER THAN 250 SQUARE FEET (23.2
 M2) IN EDUCATIONAL OCCUPANCIES USED FOR CLASSROOM OR
 OTHER EDUCATIONAL PURPOSES OR NORMALLY SUBJECT TO
 STUDENT OCCUPANCY AND EVERY ROOM OR SPACE NORMALLY
 SUBJECT TO CLIENT OCCUPANCY, OTHER THAN BATHROOMS.
 1. SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20
 INCHES (508 MM) IN WIDTH, 24 INCHES (610 MM) IN HEIGHT,
 AND 5.7 SQUARE FEET (0.53 M2) IN AREA.
 2. THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 INCHES (1118 MM) ABOVE THE FLOOR, AND ANY LATCHING
 DEVICE SHALL BE CAPABLE
 OF BEING OPERATED FROM NOT MORE THAN 54 INCHES (1372
 MM) ABOVE THE FINISHED FLOOR.
  
 4D) NOTE AT THIS TIME NO MECHANICAL PLANS WERE PROVIDED
 TO VERIFY CODE COMPLIANCE WITH 2010 FBC-B 716.1.1 DUCTS
 THAT PENETRATE FIRE-RESISTANCE-RATED ASSEMBLIES WITHOUT
 DAMPERS. DUCTS THAT PENETRATE FIRE-RESISTANCE-RATED
 ASSEMBLIES AND ARE NOT REQUIRED BY THIS SECTION TO HAVE
 DAMPERS SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS
 713.2 THROUGH 713.3.3. DUCTS THAT PENETRATE HORIZONTAL
 ASSEMBLIES NOT REQUIRED TO BE CONTAINED WITHIN A SHAFT
 AND NOT REQUIRED BY THIS SECTION TO HAVE DAMPERS SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTIONS 713.4 THROUGH
 713.4.2.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-23 Cont ID  
Sent By rlecky Date 2014-09-23 Time 13:02 Rev Time 0.00
Received By rlecky Date 2014-09-23 Time 13:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By pleduc Date 2014-10-03 Time   Rev Time 0.00
Received By pleduc Date 2014-10-03 Time 13:28 Sent To  
Notes
2014-10-03 13:55:40THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PROPOSED EXITING FROM THE PROPOSED INTERIOR
 CLASSROOM DOES NOT HAVE AN EXIT TO THE EXTERIOR AND
 DOES NOT MEET THE REQUIREMENT FOR AN UNSPRINKLERED
 EDUCATIONAL OCCUPANCY.
  
 THE COORIDOR WALLS DO NOT INDICATE ANY RATING AND DOES
 NOT MEET THE REQUIREMENTS OF AN EDUCATIONAL OCCUPANCY.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-08 Cont ID  
Sent By tklarge Date 2014-10-08 Time 05:13 Rev Time 0.00
Received By tklarge Date 2014-10-08 Time 05:13 Sent To  
Notes
2014-09-22 17:31:04SENT TO B15 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-09-26 Cont ID  
Sent By jwitmer Date 2014-09-26 Time 09:57 Rev Time 0.00
Received By jwitmer Date 2014-09-26 Time 09:10 Sent To  
Notes
2014-09-26 12:05:47I CHECKED WITH MICHELLE AT PBC IMPACT FEE OFFICE NO
 FEES DUE, NEED NOT GET PLANS STAMPED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-08 Cont ID  
Sent By tklarge Date 2014-10-08 Time 05:10 Rev Time 0.00
Received By tklarge Date 2014-10-08 Time 05:10 Sent To  
Notes
2014-10-08 05:12:541) TABLE 403.1 REQUIRES A SERVICE SINK IN EDUCATIONAL
 OCCUPANCIES. SHOW THE LOCATION OF THE REQUIRED SERVICE
 SINK ON THE PLANS. THE SEVICE SINK IS LISTED ON THE
 PLUMBING SCHEDULE ON SHT.A-2.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-26 Cont ID  
Sent By ajones Date 2014-09-26 Time 16:05 Rev Time 0.00
Received By ajones Date 2014-09-26 Time 16:05 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved