Plan Review Details - Permit 14090756
Plan Review Stops For Permit 14090756
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-04-20 Cont ID  
Sent By rmcdouga Date 2015-04-20 Time 15:23 Rev Time 0.00
Received By rmcdouga Date 2015-04-20 Time 13:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-03-27 Cont ID  
Sent By rmcdouga Date 2015-03-27 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2015-03-27 Time 14:12 Sent To  
Notes
2015-03-27 15:05:22PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) REVISE COMPONENT AND CLADDING PRESSURES FOR THE
 WINDOWS AND DOORS TO CORRESPOND WITH THE INCREASED
 PRESSURES FOR EXPOSURE D. FBC - R301.2.1 THE EXPOSURE
 CATEGORY WAS CHANGED FROM C TO D, BUT THE PRESSURES
 WERE NOT CHANGED.
  
 2) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405. (ENERGY CALCS.) THE PLANS SPECIFY THAT THE
 AIR HANDLER FOR THE ADDITION IS LOCATED IN THE ATTIC.
 ENERGY FORM 402 CAN NOT BE USED WHEN THE AIR HANDLER IS
 LOCATED IN THE ATTIC.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE SUBMITTALS
 FOR THE ASPHALT SHINGLE ROOFING.
  
 4) FBC R704 IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM). THE
 STUCCO STOP / WEEP SCREED IS REQUIRED TO BE 6 INCHES
 ABOVE FINAL EXTERIOR GRADE.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-02 Cont ID  
Sent By rmcdouga Date 2015-02-02 Time 10:18 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 06:49 Sent To E
Notes
2015-02-02 09:52:19PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THIS STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTRACOASTAL WATERWAY WHICH IS EXPOSURE D, THEREFORE,
 THIS STRUCTURE IS EXPOSURE CATEGORY D. PLEASE CORRECT
 SHEET S-1 AND REVISE THE COMPONENT AND CLADDING
 PRESSURES ACCORDINGLY.
 R301.2.1.4.3 EXPOSURE CATEGORIES.
 AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE
 WITH THE FOLLOWING:
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE BUILDING
 HEIGHT, WHICHEVER IS GREATER, FROM AN EXPOSURE D
 CONDITION AS DEFINED IN THE PREVIOUS SENTENCE.
  
 2) REVISE COMPONENT AND CLADDING PRESSURES FOR THE
 WINDOWS AND DOORS TO CORRESPOND WITH THE INCREASED
 PRESSURES FOR EXPOSURE D. FBC - R301.2.1
  
 3) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405. (ENERGY CALCS.)
  
 4) FBC 107.3.5.3 - INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
  
 5) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. SHOW THAT THE
 ENTIRE DWELLING WILL COMPLY.
  
 6) THE WOOD BEAM AND RAFTERS FOR THE PERGOLA THAT ARE
 EXPOSED TO THE WEATHER ARE REQUIRED TO BE PRESSURE
 TREATED OR OF APPROVED WOOD OF NATURAL DECAY
 RESISTANCE. R317.1.3 IN GEOGRAPHICAL AREAS WHERE
 EXPERIENCE HAS DEMONSTRATED A SPECIFIC NEED, APPROVED
 NATURALLY DURABLE OR PRESSURE-PRESERVATIVE-TREATED WOOD
 SHALL BE USED FOR THOSE PORTIONS OF WOOD MEMBERS THAT
 FORM THE STRUCTURAL SUPPORTS OF BUILDINGS, BALCONIES,
 PORCHES OR SIMILAR PERMANENT BUILDING APPURTENANCES
 WHEN THOSE MEMBERS ARE EXPOSED TO THE WEATHER WITHOUT
 ADEQUATE PROTECTION FROM A ROOF, EAVE, OVERHANG OR
 OTHER COVERING THAT WOULD PREVENT MOISTURE OR WATER
 ACCUMULATION ON THE SURFACE OR AT JOINTS BETWEEN
 MEMBERS.
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE SUBMITTALS
 FOR THE ASPHALT SHINGLE ROOFING.
  
 8) FBC R704 IN ORDER TO PROVIDE FOR INSPECTION FOR
 TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL
 COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM). THE
 STUCCO STOP IS REQUIRED TO BE 6 INCHES ABOVE FINAL
 EXTERIOR GRADE.
  
 9) THERE IS A CONFLICT BETWEEN THE BOTTOM PLATE ANCHORS
 FOR THE EXTERIOR WALLS ON SHEETS S-1 AND S-2. ON S-1
 THE ANCHORS SPECIFIED ARE 3/8" X 7-1/2" @ 24"O.C. AND
 3/4" X 6" @ 16" O.C. PLEASE CORRECT. FBC 107.2.1
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-16 Cont ID  
Sent By rmcdouga Date 2014-10-16 Time 17:30 Rev Time 0.00
Received By rmcdouga Date 2014-10-16 Time 07:03 Sent To  
Notes
2014-10-16 12:12:02PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 NOTE : ONLY THE STRUCTURAL SHEETS S-1 THROUGH S-4 WERE
 SUBMITTED. THERE IS REQUIRED INFORMATION THAT IS
 MISSING FROM THE SUBMITTAL THAT MAY BE ON THE
 ARCHITECTURAL DRAWINGS THAT WERE NOT SUBMITTED.
  
 1) SUBMIT TWO COPIES OF A SURVEY/SITE PLAN THAT SHOWS
 THE LOCATION OF THE ADDITION AND THE DISTANCES TO
 PROPERTY LINES AND OTHER STRUCTURES ON THE SAME
 PROPERTY.
 FIRE-RESISTANT CONSTRUCTION R302.1 EXTERIOR WALLS.
 CONSTRUCTION, PROJECTIONS, OPENINGS AND PENETRATIONS OF
 EXTERIOR WALLS OF DWELLINGS AND ACCESSORY BUILDINGS
 SHALL COMPLY WITH TABLE R302.1.
  
 2) THIS STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTRACOASTAL WATERWAY WHICH IS EXPOSURE D, THEREFORE,
 THIS STRUCTURE IS EXPOSURE CATEGORY D. PLEASE CORRECT
 SHEET S-1 AND REVISE THE COMPONENT AND CLADDING
 PRESSURES ACCORDINGLY.
 R301.2.1.4.3 EXPOSURE CATEGORIES.
 AN EXPOSURE CATEGORY SHALL BE DETERMINED IN ACCORDANCE
 WITH THE FOLLOWING:
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWIND DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE BUILDING
 HEIGHT, WHICHEVER IS GREATER, FROM AN EXPOSURE D
 CONDITION AS DEFINED IN THE PREVIOUS SENTENCE.
  
 3) SHOW COMPLIANCE WITH 2010 FBC ENERGY CONSERVATION
 SECT. 101.4.3 & 103.2 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
  
 4) SPECIFY THE CEILING INSULATION ON THE PLANS. FBC
 107.2.1
  
 5) THE NOTE ON S-1 SPECIFIES FBC 2009 AND ASCE 7 - 11
 WHICH DO NOT EXIST. CHANGE TO 2010 FBC AND ASCE 7 -10.
  
 6) IN THE COMPONENT AND CLADDING NOTES ON S-1, ZONES
 1,2 AND 3 ARE LISTED UNDER WALL PRESSURE LOADS. THESE
 ARE ROOF ZONES. ALSO, THE PRESSURES FOR ZONE 3 ARE
 LISTED AS N/A AND SHOULD BE SPECIFIED. PLEASE CORRECT.
 FBC-R301.2.1 BUILDINGS AND PORTIONS THEREOF SHALL BE
 LIMITED BY WIND SPEED, AS DEFINED IN TABLE R301.2(1)
 AND CONSTRUCTION METHODS IN ACCORDANCE WITH THIS CODE.
 SEE FIGURE R301.2(7)
  
 7) FBC 107.3.5.3 - INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
  
 8) PROVIDE TWO SETS OF FLOOR PLANS WITH DIMENSIONS TO
 INDICATE THE LOCATIONS OF THE WINDOWS, EXTERIOR AND
 INTERIOR DOORS, THE LOCATION OF THE BATHROOM FIXTURES,
 SIZE OF INTERIOR DOORS AND OPENINGS. FBC-R 107.2.1
  
 9) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 10) ON SHEET S-3, IT IS SPECIFIED THAT THE BOTTOM PLATE
 OF THE EXTERIOR WALL IS TAPCON-ED TO THE SLAB. THIS IS
 NOT AN ACCEPTABLE EXTERIOR WALL TO SLAB ATTACHMENT.
 PLEASE CORRECT. FBC-R 301.1 BUILDINGS AND STRUCTURES,
 AND ALL PARTS THEREOF, SHALL BE CONSTRUCTED TO SAFELY
 SUPPORT ALL LOADS, INCLUDING DEAD LOADS, LIVE LOADS,
 ROOF LOADS, FLOOD LOADS, AND WIND LOADS AS PRESCRIBED
 BY THIS CODE. THE CONSTRUCTION OF BUILDINGS AND
 STRUCTURES IN ACCORDANCE WITH THE PROVISIONS OF THIS
 CODE SHALL RESULT IN A SYSTEM THAT PROVIDES A COMPLETE
 LOAD PATH THAT MEETS ALL REQUIREMENTS FOR THE TRANSFER
 OF ALL LOADS FROM THEIR POINT OF ORIGIN THROUGH THE
 LOAD-RESISTING ELEMENTS TO THE FOUNDATION.
  
 11) SPECIFY HOW THE TOP PLATES OF THE 2 X 4 STRUCTURAL
 WALL ON TOP OF THE EXISTING CBS WALL WILL BE ATTACHED
 TO THE 2 X 4 CATS BETWEEN THE RAFTERS AND TRUSSES. FBC
 107.2.1
  
 12) SPECIFY THE SLOPE OF THE ROOF ON THE PLANS. FBC -
 R905.2.2 SLOPE.
 ASPHALT SHINGLES SHALL ONLY BE USED ON ROOF SLOPES OF
 TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR
 GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12
 UNITS HORIZONTAL (2:12) UP TO FOUR UNITS VERTICAL IN 12
 UNITS HORIZONTAL (4:12), TWO LAYERS OF UNDERLAYMENT
 COMPLYING WITH ASTM D 226, TYPE I OR TYPE II, ASTM D
 4869, TYPE I OR TYPE II OR ASTM D 6757 IS REQUIRED IN
 ACCORDANCE WITH SECTION R905.2.7.
  
 13) PROVIDE DETAILS FOR THE DOUBLE RIDGE BEAM. SPECIFY
 THE LUMBER TYPE, SIZE, HOW THE TWO ARE PUT TOGETHER,
 HOW IT WILL ATTACH TO THE EXISTING TRUSS ROOF AND HOW
 THE ENDS WILL BE SUPPORTED. FBC 107.2.1 AND FBC-R 301.1
  
 14) IT APPEARS THAT THE ADDITION WILL HAVE A SINGLE
 ASSEMBLY SLOPED ROOF SYSTEM WITHOUT A HORIZONTAL
 CEILING DIAPHRAGM TO PROVIDE LATERAL WIND LOAD
 RESISTANCE. THE RIDGE WILL NEED TO BE DESIGNED TO
 ACCOUNT FOR SOME OF THE LATERAL LOADS SO THAT THE WALLS
 WON'T SPLAY OUTWARDS FROM THE ROOF LOADS. SUBMIT
 CALCULATIONS AND DETAILED DRAWINGS FROM THE ENGINEER
 THAT DESCRIBE IN DETAIL HOW THESE LATERAL FORCES WILL
 BE ADDRESSED. FBC 107.2.1.3 & FBC 606.3.2
  
 15) THE INFORMATION ON THE PLANS IS REQUIRED TO BE
 SPECIFIC PER FBC 107.2.1. SPECIFY THE REQUIRED LAP FOR
 THE FOUNDATION CORNER BARS ON THE PLANS.
  
 16) PROVIDE DIMENSIONS ON THE DRAWINGS TO THE LOCATIONS
 OF THE 4 X 4 POSTS AT THE PATIO AND THE SPANS OF THE 2
 X 6 JOISTS. FBC 107.2.1
  
 17) THE 4 X 4 POSTS, THE BEAM AND RAFTERS FOR THE PATIO
 THAT ARE EXPOSED TO THE WEATHER ARE REQUIRED TO BE
 PRESSURE TREATED OR OF APPROVED WOOD OF NATURAL DECAY
 RESISTANCE. R317.1.3 IN GEOGRAPHICAL AREAS WHERE
 EXPERIENCE HAS DEMONSTRATED A SPECIFIC NEED, APPROVED
 NATURALLY DURABLE OR PRESSURE-PRESERVATIVE-TREATED WOOD
 SHALL BE USED FOR THOSE PORTIONS OF WOOD MEMBERS THAT
 FORM THE STRUCTURAL SUPPORTS OF BUILDINGS, BALCONIES,
 PORCHES OR SIMILAR PERMANENT BUILDING APPURTENANCES
 WHEN THOSE MEMBERS ARE EXPOSED TO THE WEATHER WITHOUT
 ADEQUATE PROTECTION FROM A ROOF, EAVE, OVERHANG OR
 OTHER COVERING THAT WOULD PREVENT MOISTURE OR WATER
 ACCUMULATION ON THE SURFACE OR AT JOINTS BETWEEN
 MEMBERS.
  
 18) FBC-R703.6.3 WHERE CEMENT PLASTER (STUCCO) IS TO BE
 APPLIED TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL
 BE TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER
 AND THE WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE
 PROVIDED BETWEEN THE WATER-RESISTIVE BARRIER AND THE
 CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE
 FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER
 MATERIAL; OR
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP; OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 19) FBC-R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATION OPENINGS SHALL HAVE A
 LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4
 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS HAVING A
 LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM) SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH SCREENING,
 HARDWARE CLOTH, OR SIMILAR MATERIAL WITH OPENINGS
 HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING
 MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF SECTION
 R802.7.
 EXCEPTION: ATTIC SPACES, DESIGNED BY A PROFESSIONAL
 ENGINEER OR ARCHITECT LICENSED TO PRACTICE IN THE
 STATE, DESIGNED TO ELIMINATE THE ATTIC VENTING.
  
 20) FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 21) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 22) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW, AND DOOR SUBMITTALS.
  
 23) PRODUCT APPROVALS WERE SUBMITTED FOR A NON-IMPACT
 RATED FRENCH DOOR. IMPACT PROTECTION OF GLAZED OPENINGS
 IS REQUIRED BY FBC-R301.2.1.2. SUBMIT TWO COPIES OF THE
 PRODUCT APPROVALS FOR THE STORM PANELS AND TWO COPIES
 OF AN INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE OPENING SIZE, THE WIND PRESSURES,
 TYPE OF ANCHOR, ANCHOR SPACING, EDGE DISTANCE, PANEL
 LENGTH, PANEL SPAN, SEPARATION DISTANCE FROM PANEL TO
 GLASS AND THE APPLICABLE SECTION NUMBER FROM THE
 INSTALLATION DRAWINGS. I HAVE INCLUDED A LINK TO THE
 CONSTRUCTION SERVICES DEPARTMENT SITE THAT HAS MANY OF
 THE RELATED FORMS INCLUDING
 THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
 24) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-03-27 Cont ID  
Sent By rmcdouga Date 2015-03-27 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2015-03-27 Time 15:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-02-02 Cont ID  
Sent By dhayes Date 2015-02-02 Time 11:41 Rev Time 0.00
Received By dhayes Date 2015-02-02 Time 11:17 Sent To  
Notes
2015-02-02 11:41:41DATE: 02/02/2015
 PROJECT: 221 PURITAN RD
 PERMIT#: 14090756
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) MINIMUM PLAN REVIEW CRIERIA REQUIRES A RISER
 DIAGRAM, PANEL SCHEDULE AND FLOOR PLAN DETAILING
 CIRCUIT NUMBERS AT EACH OUTLET, DEVICE AND EQUIPMENT
 LOCATIONS. WPB AMENDMENTS FBC 107.3.2
 THERE IS STILL NO PANEL SCHEDULE AND NO CIRCUIT NUMBERS
 ON THE FLOOR PLAN.
  
 2) PROVIDE A MAIN SERVICE DISCONNECT AT A READILY
 ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF
 THE SERVICE CONDUCTORS. NEC 230.702) INDICATE THE
 LOCATION OF THE MAIN BREAKER AND THE PANEL ON THE FLOOR
 PLAN.
  
 3) THE MECHANICAL PLANS SUBMITTED ARE CONFLICTING WITH
 THE ELECTRICAL PLAN. PROVIDE A COHESIVE PLAN THE IS
 COORDINATED WITHE THE MECHANICAL PLANS. PROVIDE THE
 CIRCUIT NUMBERS WITH THE PROPPER OCPD AND WIRE SIZES
 ASSOCIATED WITH EACH CIRCUIT ANDINDICATE THE CIRCUIT
 NUMBERS ON THE FLOOR PLAN.
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
  
 5) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 7) BATHROOM BRANCH CIRCUITS IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. INDICATE THE
 REQUIRED 20AMP BRANCH CIRCUIT IN THE PANEL SCHEDULE AND
 ON THE FLOOR PLAN. INDICATE THE CORRESPONDING WIRE
 SIZES IN THE PANEL SCHEDULE FOR EACH NEW CIRCUIT OCPD.
  
 8) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315. THIS ARTICLE CALLS FOR SMOKE DETECTORS TO
 BE INSTALLED AND INTERCONNECTED INSIDE AND OUTSIDE OF
 ALL SLEEPING ROOMS. THERE IS ONLY A PARTIAL FLOOR PLAN
 SHOWN. EITHER PROVIDE A COMPLETE FLOOR PLAN INDICATING
 ALL REQUIRED SMOKE DETECTORS OR PROVIDE A NOTE THAT
 THEY ARE REQUIRED AS DECRIBED IN THE FBC SECTION 314
 AND 315 FOR CO DETECTORS.
  
 9) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1. THE PLANS ARE STILL NOT SIGNED. THE
 DESIGN MUST BEAR THE NAME AND SIGNATURE OF THE PERSON
 REPSONIBLE FOR THE DESIGN.
  
 10) UNDER ELECTRICAL NOTES THE ELECTRICAL CODE VERSION
 IS INDICATED AS 2010. THE ACTUAL NATIONAL ELECTRICAL
 CODE IN EFFECT AT THIS TIME IS 2008. ADJUST PLANS
 ACCORDINGLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-23 Cont ID  
Sent By dhayes Date 2014-09-23 Time 15:23 Rev Time 0.00
Received By dhayes Date 2014-09-23 Time 15:23 Sent To  
Notes
2014-09-23 16:47:26DATE: 9/23/2014
 PROJECT: 221 PURITAN RD
 PERMIT#: 14090756
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) MINIMUM PLAN REVIEW CRIERIA REQUIRES A RISER
 DIAGRAM, PANEL SCHEDULE AND FLOOR PLAN DETAILING
 CIRCUIT NUMBERS AT EACH OUTLET, DEVICE AND EQUIPMENT
 LOCATIONS. WPB AMENDMENTS FBC 107.3.2
  
 2) PROVIDE A MAIN SERVICE DISCONNECT AT A READILY
 ACCESSIBLE LOCATION NEAREST THE POINT OF ENTRANCE OF
 THE SERVICE CONDUCTORS. NEC 230.702) INDICATE
 RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6 FEET
 FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2 FEET
 IN WIDTH HAVE A RECEPTACLE. NEC 210.52.
  
 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
  
 4) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 5) REQUIRED GFI WITHIN 3 FT OF SINK 210.52(D),
 21011.C.3
  
 6) BATHROOM GFIC OUTLET PLANS FAIL TO INDICATE
 COMPLIANCE WITH SECTION 210.11 (C)(3) BATHROOM BRANCH
 CIRCUITS IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS.
  
 7) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 8) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-04-20 Cont ID  
Sent By rmcdouga Date 2015-04-20 Time 15:54 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2015-03-27 Time   Rev Time 0.00
Received By jgomez Date 2015-02-23 Time 10:07 Sent To  
Notes
2015-02-25 10:08:15RE-SUBMITTAL SENT TO R16 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-02 Cont ID  
Sent By dhayes Date 2015-02-02 Time 11:41 Rev Time 0.00
Received By dhayes Date 2014-12-24 Time 09:49 Sent To  
Notes
2014-12-29 09:50:21RE-SUBMITTAL SENT TO R2 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-16 Cont ID  
Sent By rmcdouga Date 2014-10-16 Time 17:30 Rev Time 0.00
Received By rmcdouga Date 2014-09-23 Time 15:05 Sent To  
Notes
2014-09-23 15:06:19R09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-04-22 Cont ID  
Sent By skennedy Date 2015-04-22 Time 15:33 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-03-27 Cont ID  
Sent By rmcdouga Date 2015-03-27 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2015-03-27 Time 14:04 Sent To  
Notes
2015-03-27 14:05:55BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-02-02 Cont ID  
Sent By rmcdouga Date 2015-02-02 Time 10:18 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 10:18 Sent To  
Notes
2015-02-02 10:51:12BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-10-16 Cont ID  
Sent By rmcdouga Date 2014-10-16 Time 07:42 Rev Time 0.00
Received By rmcdouga Date 2014-10-16 Time 07:03 Sent To  
Notes
2014-10-16 07:48:36IMPACT FEES
  
 PLANS ARE REQUIRED TO BE REVIEWED BY THE PBC IMPACT FEE
 OFFICE. CALL 233-5025. UPON APPROVAL, YOU MAY CHECK OUT
 ONE PLAN TO TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURN STAMPED PLAN WITH A COPY OF PAID RECEIPT AS
 APPLICABLE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2015-04-20 Cont ID  
Sent By rmcdouga Date 2015-04-20 Time 13:17 Rev Time 0.00
Received By rmcdouga Date 2015-04-20 Time 13:17 Sent To  
Notes
2015-04-20 13:21:29OWNER AND CONTRACTOR REQUESTED MECHANICAL TO BE UNDER A
 SEPARATE PERMIT. FEES IN THE AMOUNT OF $6,000.00 TO
 COVER THE HVAC WORK WERE REMOVED FROM THE PRIME PERMIT.
 A SEPARATE PERMIT APPLICATION, PLANS AND REVIEW IS
 REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-03-27 Cont ID  
Sent By rmcdouga Date 2015-03-27 Time 12:42 Rev Time 0.00
Received By rmcdouga Date 2015-03-27 Time 12:42 Sent To  
Notes
2015-03-27 13:50:00PLAN REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 MECHANICAL DENIED
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS. SUBMIT TWO
 COPIES OF THE COMPLETE CALCULATIONS SHOWING THE
 ORIENTATION OF THE STRUCTURE. ONLY ONE COPY OF THE
 PROJECT SUMMARY FOR EACH UNIT WAS SUBMITTED.
  
 2) THE EQUIPMENT INFORMATION IN THE LOAD CALCULATIONS
 IS REQUIRED TO MATCH THE EQUIPMENT SCHEDULE ON THE
 MECHANICAL PLANS AND THE ENERGY FORMS. FBC 107.2.1
  
 3) FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 4) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 5) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-02-02 Cont ID  
Sent By rmcdouga Date 2015-02-02 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 10:00 Sent To  
Notes
2015-02-02 09:52:49PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 MECHANICAL DENIED
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MECHANICAL PLANS SHOW TWO SEPARATE HVAC SYSTEMS.
 ONE IS FOR THE NEW ADDITION AND THE OTHER IS FOR THE
 EXISTING DWELLING. IF A NEW HVAC SYSTEM IS BEING
 INSTALLED IN THE EXISTING DWELLING, THEN THE ENTIRE
 SYSTEM IS REQUIRED TO COMPLY WITH THE 2010 FBC. PLEASE
 CLARIFY. FBC 107.2.1
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 3) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS.
  
 4) FBC 107.2.1 SPECIFY THE CFMS AT THE SUPPLY OUTLETS.
  
 5) THERE IS A CONFLICT BETWEEN THE ELECTRICAL PLANS AND
 THE MECHANICAL PLANS. THE ELECTRICAL PLAN SHOWS A
 MINI-SPLIT SYSTEM IN THE NEW ADDITION AND THE
 MECHANICAL PLAN SHOWS A DUCTED SYSTEM WITH THE AIR
 HANDLER IN THE ATTIC. PLEASE COORDINATE THE MECHANICAL
 INFORMATION. FBC 107.2.1
  
 6) FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 7) FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-10-06 Cont ID  
Sent By rbergsma Date 2014-10-06 Time   Rev Time 0.50
Received By rbergsma Date   Time   Sent To  
Notes
2014-10-06 13:09:03PLANS FOR ADDED SPACE TO RESIDENCE MUST INCLUDE STATE
 OF FLORIDA ENERGY CALCULATIONS
 SIZED DUCTWORK, EXHAUST WITH SIZES AND TERMINATION
 POINTS, CFM'S. STATED ON PLANS
 NEW A/C EQUIPTMENT MUST MATCH LOADS AND NOT EXCEED SAID
 LOADS BY 15%, LOCATIONS OF EQUIPTMENT MUST BE SHOWN

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-03-17 Cont ID  
Sent By tklarge Date 2015-03-07 Time 09:52 Rev Time 0.00
Received By tklarge Date 2015-03-07 Time 05:40 Sent To  
Notes
2015-02-25 08:15:53NEW DRAWINGS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-04 Cont ID  
Sent By tklarge Date 2015-01-04 Time 05:27 Rev Time 0.00
Received By tklarge Date 2015-01-04 Time 05:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-04 Cont ID  
Sent By tklarge Date 2014-10-04 Time 02:50 Rev Time 0.00
Received By tklarge Date 2014-10-04 Time 02:50 Sent To  
Notes
2014-10-04 02:58:24WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 1) SHT. S-2 HAS NOTES REFERRING TO A NEW TOILET, NEW
 LAVATORY & NEW BATHTUB, BUT NOTHING IS SHOWN ON THE
 PLANS. SUBMIT A FLOOR PLAN THAT CLEARLY REFLECTS THE
 ENTIRE SCOPE OF WORK TO BE PERFORMED UNDER THIS PERMIT.
 2) SHOW ALL THE FIXTURE CLEARANCES PER THE 2010 FBC,
 RESIDENTIAL, SEC.P2705.
 3) SUBMIT A SANITARY AND WATER RISER FOR REVIEW.SHOW
 ALL PIPE SIZES AND CONNECTION POINTS OF THE NEW PIPING
 TO THE EXISTING SYSTEMS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-04-20 Cont ID  
Sent By rmcdouga Date 2015-04-20 Time 13:21 Rev Time 0.00
Received By rmcdouga Date 2015-04-20 Time 13:21 Sent To  
Notes
2015-04-20 13:49:47GAF ASPHALT SHINGLES NOA NO. 14-1022.16

Review Stop Z ZONING
Rev No 3 Status P Date 2015-03-04 Cont ID  
Sent By sgraham Date 2015-03-04 Time 12:06 Rev Time 0.00
Received By sgraham Date 2015-03-04 Time 12:06 Sent To  
Notes
2015-03-04 12:07:283/4/15 TRELLIS IS BEING OMITTED FROM THE PLANS, DOES
 NOT MEET THE REAR SETBACK. SG
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-01-20 Cont ID  
Sent By sgraham Date 2015-01-20 Time 15:08 Rev Time 0.00
Received By sgraham Date 2015-01-20 Time 15:08 Sent To  
Notes
2015-01-20 15:09:271/19/15 ZONING FAILED 2ND CHECKLIST
  
 1. PROVIDE TWO UP TO DATE SURVEYS OF THE PROPERTY,
 HIGHLIGHTING THE LOCATION OF THE ADDITION.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-09-30 Cont ID  
Sent By sgraham Date 2014-09-30 Time 14:57 Rev Time 0.00
Received By sgraham Date 2014-09-30 Time 14:57 Sent To  
Notes
2014-09-30 14:58:569/30/14 ZONING FAILED
  
 1. SUBMIT TWO COPIES OF AN UP TO DATE SURVEY, SHOWING
 THE LOCATION OF THE NEW ADDITION.
2014-09-26 16:08:169/26/14