Plan Review Details - Permit 14090742
Plan Review Stops For Permit 14090742
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-10-16 Cont ID  
Sent By dhayes Date 2014-10-16 Time 10:55 Rev Time 0.00
Received By dhayes Date 2014-10-16 Time 10:31 Sent To  
Notes
2014-10-16 10:50:2210/16/2014
 PROJECT: 401 EXECUTIVE CNTR
 PERMIT#: 14090742
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 4RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) PROVIDE A PANEL SCHEDULE FOR EACH PANEL INVOLVED IN
 THIS SCOPE OF WORK INDICATING THE CIRCUIT NUMBER,
 AMPERE RATING AND VOLTAGE RATING FOR EACH CIRCUIT
 INVOLVED IN THIS SCOPE OF WORK.
  
 2) INDICATE THE CIRCUIT NUMBERS AND WIRE SIZES ON THE
 SITE PLAN FOR EACH CIRCUIT INVOLVED IN THIS SCOPE OF
 WORK.
  
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR THE FUTURE INSTALLATION OF SECURITY,
 AND/OR CCTV.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-10-10 Cont ID  
Sent By dhayes Date 2014-10-10 Time 10:14 Rev Time 0.00
Received By dhayes Date 2014-10-10 Time 10:14 Sent To  
Notes
2014-10-10 10:27:2610/10/2014
 PROJECT: 401 EXECUTIVE CNTR
 PERMIT#: 14090742
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A PANEL SCHEDULE FOR EACH PANEL INVOLVED IN
 THIS SCOPE OF WORK INDICATING THE CIRCUIT NUMBER,
 AMPERE RATING AND VOLTAGE RATING FOR EACH CIRCUIT
 INVOLVED IN THIS SCOPE OF WORK.
  
 2) INDICATE THE CIRCUIT NUMBERS AND WIRE SIZES ON THE
 SITE PLAN FOR EACH CIRCUIT INVOLVED IN THIS SCOPE OF
 WORK.
  
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR THE INSTALLATION OF SECURITY, AND/OR
 CCTV.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-09-26 Cont ID  
Sent By dhayes Date 2014-09-26 Time 16:23 Rev Time 0.00
Received By dhayes Date 2014-09-26 Time 16:23 Sent To  
Notes
2014-09-26 16:45:499/26/2014
 PROJECT: 401 EXECUTIVE CNTR
 PERMIT#: 14090742
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. FBC 107.2.1
  
 2) WIRE SIZE TO BE APPROVED FOR THE OCPD SIZE NEC310.16
  
 3) NEC 362.12 USES NOT PERMITTED. ENT SHALL NOT BE USED
 IN THE FOLLOWING: (5) FOR DIRECT EARTH BURIAL.
  
 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-09-22 Cont ID  
Sent By dhayes Date 2014-09-22 Time 15:22 Rev Time 0.00
Received By dhayes Date 2014-09-22 Time 15:22 Sent To  
Notes
2014-10-16 10:52:1809/22/2014
 PROJECT: 401 EXECUTIVE CNTR
 PERMIT#: 14090742
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A PANEL SCHEDULE FOR EACH PANEL INVOLVED IN
 THIS SCOPE OF WORK INDICATING THE CIRCUIT NUMBER,
 AMPERE RATING AND VOLTAGE RATING FOR EACH CIRCUIT
 INVOLVED IN THIS SCOPE OF WORK.
  
 2) INDICATE THE CIRCUIT NUMBERS AND WIRE SIZES ON THE
 SITE PLAN FOR EACH CIRCUIT INVOLVED IN THIS SCOPE OF
 WORK.
  
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 TO FBC 107.2.1
  
 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR THE INSTALLATION OF SECURITY, AND/OR
 CCTV.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-10-16 Cont ID  
Sent By dhayes Date 2014-10-16 Time 10:55 Rev Time 0.00
Received By dhayes Date 2014-10-15 Time 10:31 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-10 Cont ID  
Sent By dhayes Date 2014-10-10 Time 10:27 Rev Time 0.00
Received By dhayes Date 2014-10-06 Time 11:36 Sent To  
Notes
2014-10-06 11:36:49RE-SUBMITTAL SENT TO DAVID HAYES FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-09-26 Cont ID  
Sent By dhayes Date 2014-09-26 Time 16:23 Rev Time 0.00
Received By dhayes Date 2014-09-25 Time 14:41 Sent To  
Notes
2014-09-26 14:41:55SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-22 Cont ID  
Sent By dhayes Date 2014-09-22 Time 15:22 Rev Time 0.00
Received By dhayes Date 2014-09-22 Time 09:24 Sent To  
Notes
2014-09-22 09:25:05<5000 ELEC


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved