Plan Review Details - Permit 14090691
Plan Review Stops For Permit 14090691
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-01-10 Cont ID  
Sent By skennedy Date 2015-01-10 Time 09:10 Rev Time 0.00
Received By skennedy Date 2015-01-10 Time 09:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-20 Cont ID  
Sent By rmcdouga Date 2014-12-20 Time 11:55 Rev Time 0.00
Received By rmcdouga Date 2014-12-20 Time 09:32 Sent To E
Notes
2014-12-22 06:37:39PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) SUBMIT TWO SETS OF REVISED STRUCTURAL PLANS THAT
 ACCURATELY REFLECT THE REVISED SCOPE OF WORK THAT IS
 SHOWN ON THE NEW ARCHITECTURAL DRAWINGS. FBC 107.2.1
  
 2) SPECIFY THE DIMENSIONS OF THE EXISTING DOORS AND
 WINDOWS IN THE SCHEDULE ON SHEET A6.1. FBC R301.2.1 AND
 R310
  
 3) PRODUCT APPROVALS WERE SUBMITTED FOR SINGLE HUNG AND
 HORIZONTAL SLIDING WINDOWS, HOWEVER, THERE ARE NOT ANY
 SHOWN IN THE WINDOW SCHEDULE. PLEASE CLARIFY. FBC
 107.2.1
  
 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR
 STRUCTURAL MULLIONS AND AWNING WINDOWS IN WRITING BY
 THE DESIGNER OF RECORD. FBC 107.3.4
  
 5) THE PRODUCT APPROVALS SUBMITTED FOR THE SINGLE HUNG
 WINDOWS ( NOA NO. 13-1024.05 ) AND THE CASEMENT WINDOWS
 ( NOA NO. 09-1105.03 ) HAVE BEEN SUPERSEDED. FBC
 107.3.4 - PROVIDE TWO SETS OF THE CURRENT PRODUCT
 APPROVALS FOR THESE ITEMS WHICH ARE REGULATED BY DCA
 RULE 9N-3 THAT HAVE BEEN REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-15 Cont ID  
Sent By rmcdouga Date 2014-10-15 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2014-10-15 Time 07:00 Sent To  
Notes
2014-10-15 11:41:18PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THIS STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE WITH A
 BASE FLOOD ELEVATION OF 7 FEET WITH AN ADDITIONAL 6"
 FREEBOARD BY CITY ORDINANCE. THE PRE-FIRM STRUCTURE WAS
 BUILT IN 1965 AND HAS A VALUE OF $376,803.00 EXCLUDING
 THE LAND VALUE PER THE PBC PROPERTY APPRAISER. THE
 VALUATION FOR THE WORK THAT IS PROPOSED UNDER THIS
 PERMIT IS $100,000.00. THERE ARE PREVIOUS REPAIRS AND
 IMPROVEMENTS OF $10,500.00 THAT ARE APPLICABLE. THE
 TOTAL AMOUNT OF REPAIRS AND IMPROVEMENTS IS $110,500.00
 IS LESS THAN $188,401.50, WHICH IS 50% OF THE APPRAISED
 VALUE. THEREFORE, THIS IS NOT A SUBSTANTIAL IMPROVEMENT
 AND IS NOT REQUIRED TO BE BROUGHT INTO COMPLIANCE WITH
 THE MINIMUM BASE FLOOD ELEVATION.
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. REQUIRED FOR THE FOLLOWING ITEMS:
 EACH TYPE OF EXTERIOR DOOR AND WINDOW, AS WELL AS, THE
 CEMENT ROOF TILES.
  
 3) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO
 INSTALL THE ROOF TILES AND PROVIDE THE REQUIRED
 OVERTURN MOMENT RESISTANCE. MARK THE APPROPRIATE METHOD
 ON THE PRODUCT APPROVAL. IF A ROOF TILE ADHESIVE WILL
 BE USED, SUBMIT TWO COPIES OF ITS PRODUCT APPROVALS
 THAT HAVE BEEN APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. FBC - R 301.2.1
  
 4) SPECIFY THE SLOPE OF THE BALCONY ROOF ON THE PLANS.
 R905.3.2 DECK SLOPE.
 CLAY AND CONCRETE ROOF TILE SHALL BE INSTALLED ON ROOF
 SLOPES IN ACCORDANCE WITH THE RECOMMENDATIONS OF
 FRSA/TRI 07320 WHERE THE VASD IS DETERMINED IN
 ACCORDANCE WITH SECTION R301.2.1.3 OR THE
 RECOMMENDATIONS OF RAS 118, 119 OR 120.
  
 5) FBC - R312.3 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS FROM THE
 WALKING SURFACE TO THE REQUIRED GUARD HEIGHT WHICH
 ALLOW PASSAGE OF A SPHERE 4 INCHES (102 MM) IN
 DIAMETER. THE NEW BALCONY RAILINGS ARE REQUIRED TO
 COMPLY.
  
 6) FBC - R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 7) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALATION INSTRUCTIONS FOR THE 36"
 WOLF GAS GRILL. FBCR-G2408.1 (305.1) GENERAL.
 EQUIPMENT AND APPLIANCES SHALL BE INSTALLED AS REQUIRED
 BY THE TERMS OF THEIR APPROVAL, IN ACCORDANCE WITH THE
 CONDITIONS OF LISTING, THE MANUFACTURER?S INSTRUCTIONS
 AND THIS CODE. MANUFACTURERS? INSTALLATION INSTRUCTIONS
 SHALL BE AVAILABLE ON THE JOB SITE AT THE TIME OF
 INSPECTION. WHERE A CODE PROVISION IS LESS RESTRICTIVE
 THAN THE CONDITIONS OF THE LISTING OF THE EQUIPMENT OR
 APPLIANCE OR THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS, THE CONDITIONS OF THE LISTING AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS SHALL APPLY.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
 THE FOLLOWING IS A LINK TO THE PLAN REVIEW COMMENTS:
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PROPERTY/PROP_SE
 ARCH.ASPX
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-01-10 Cont ID  
Sent By skennedy Date 2015-01-10 Time 09:10 Rev Time 0.00
Received By skennedy Date 2015-01-10 Time 08:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-12-22 Cont ID  
Sent By dhayes Date 2014-12-22 Time 11:01 Rev Time 0.00
Received By dhayes Date 2014-12-22 Time 10:14 Sent To  
Notes
2014-12-22 11:01:3812/22/2014
 PROJECT: CHEATHAM RESIDENCE
 PERMIT#: 14090691
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE A SYMBOLS AND FIXTURE LEGEND TO IDENTIFY ALL
 SYMBOLS ON THE PLAN. FBC-WPB AMENDMENTS 107.3.2
  
 2) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 3) PROVIDE THE CIRCUIT UMBRS ON THE FLOOR PLAN. FBC-WPB
 AMENDMENTS 107.3.2
  
 4) WHERE RECEPTACLES ARE INSTALLED WITHIN 1.8 M (6 FT)
 OF THE OUTSIDE EDGE OF THE SINK. NEC 210.8 (5)
  
 5) INDICATE WHAT IS EXISTING TO REMAIN AND WHAT IS
 INSTALLED NEW.
  
 6) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.)
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE.NEC210.52(C)(1)
  
 7) AT LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED IN HALLWAYS, STAIRWAYS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER.
 INDICATE REQUIRED SWITCHES AT STAIR LANDINGS. NEC
 210.70(A)
  
 8) AT LEAST ONE WALL SWITCH? CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE
 EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS. NEC
 210.70(B)
  
 9) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-14 Cont ID  
Sent By dhayes Date 2014-10-14 Time 14:52 Rev Time 0.00
Received By dhayes Date 2014-10-14 Time 14:52 Sent To  
Notes
2014-10-14 14:58:5410/14/2014
 PROJECT: CHEATHAM RESIDENCE
 PERMIT#: 14090691
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE ELECTRICAL PLANS. NONE PROVIDED WITH
 SUBMITTAL PACKAGE AND YET IT IS EVIDENT FROM THE SCOPE
 OF WORK SHOWN THAT AN ELECTRICAL PERMIT IS REQUIRED.
 WPB AMENDMENTS TO FBC 107.3.2
  
 2) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
 3) ADDITIONAL NOTES AND OR DEFICIENCIES MAY BE NOTED
 ONCE ACTUAL ELECTRICAL PLANS HAVE BEE SUBMITTED FOR
 REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-10 Cont ID  
Sent By skennedy Date 2015-01-10 Time 09:10 Rev Time 0.00
Received By skennedy Date 2015-01-08 Time 11:51 Sent To  
Notes
2015-01-08 11:51:25IN MY OFFICE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-22 Cont ID  
Sent By dhayes Date 2014-12-22 Time 11:02 Rev Time 0.00
Received By dhayes Date 2014-11-21 Time 10:21 Sent To  
Notes
2014-11-22 10:21:15R16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-15 Cont ID  
Sent By rmcdouga Date 2014-10-15 Time 15:39 Rev Time 0.00
Received By rmcdouga Date 2014-09-20 Time 07:29 Sent To  
Notes
2014-09-20 07:30:00INCOMING SENT TO R-07 . JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-12-20 Cont ID  
Sent By hmoser Date 2014-12-20 Time 09:48 Rev Time 0.00
Received By rmcdouga Date 2014-12-20 Time 09:48 Sent To  
Notes
2014-12-20 09:50:42NO MECHANICAL PLANS WERE SUBMITTED AND NO MECHANICAL
 PERMIT WAS APPLIED FOR. SEPARATE PERMIT APPLICATION,
 PLANS AND REVIEW ARE REQUIRED FOR MECHANICAL WORK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-10-06 Cont ID  
Sent By rbergsma Date 2014-10-06 Time   Rev Time 0.50
Received By rbergsma Date   Time   Sent To  
Notes
2014-10-06 11:19:17PROVIDE MECHANICAL DETAILS FOR RELOCATED OR ADDED A/C
 DROPS, BATH EXHAUST FANS AND DUCT(S), KITCHEN AND BBQ
 HOOD (IF USED)

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-11-27 Cont ID  
Sent By tklarge Date 2014-11-27 Time 07:16 Rev Time 0.00
Received By tklarge Date 2014-11-27 Time 06:52 Sent To  
Notes
2014-11-27 07:16:51***PROVISO***
 1) CODE COMPLIANT SANITARY RISERS SHALL BE SUBMITTED
 FOR REVIEW AND APPROVAL PRIOR TO 1ST ROUGH INSPECTION.
 2) SEPARATE PLANS AND PERMIT REQD. FOR GAS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-04 Cont ID  
Sent By tklarge Date 2014-10-04 Time 03:15 Rev Time 0.00
Received By tklarge Date 2014-10-04 Time 03:15 Sent To  
Notes
2014-10-04 03:20:301) SUBMIT MANUFACTURR'S SPECIFICATION SHEETS FOR ALL OF
 THE GAS APPLIANCES. GAS APPLIANCES SHALL BE LISTED AND
 LABELED FOR THE APPLICATION IN WHICH THEY ARE USED PER
 THE FLORRIDA FUEL GAS CODE SEC.G2404.3.
 2) SUBMIT A GAS RISER FOR REVIEW. THE GAS PIPING SYSTEM
 SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA FUEL GAS
 CODE SEC.G2413, 2413.3.
 3) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 CHANGES/ADDITIONS THAT ARE BEING MADE TO THESE SYSTEMS.
 WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2014-12-01 Cont ID  
Sent By sgraham Date 2014-12-01 Time 16:11 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
2014-12-01 16:12:3912/1/14 ZONING FAILED
  
 1. PROVIDE TWO UP TO DATE SURVEYS.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-09-30 Cont ID  
Sent By sgraham Date 2014-09-30 Time 15:15 Rev Time 0.00
Received By sgraham Date 2014-09-30 Time 15:15 Sent To  
Notes
2014-09-30 15:16:519/30/14 ZONING FAILED
  
 1. SUBMIT TWO COPIES OF AN UP TO DATE, SHOWING ANY NEW
 ADDITIONS.
2014-09-26 16:02:559/26/14