| 2014-10-08 17:46:12 | PLAN REVIEW COMMENTS | | | | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) FBC-R703.6.3 WHERE CEMENT PLASTER (STUCCO) IS TO BE | | | APPLIED TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL | | | BE TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER | | | AND THE WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE | | | PROVIDED BETWEEN THE WATER-RESISTIVE BARRIER AND THE | | | CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE | | | FOLLOWING: | | | 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER | | | MATERIAL; OR | | | 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER | | | OVER AN APPROVED PLASTIC HOUSE WRAP; OR | | | 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN | | | ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION | | | INSTRUCTIONS. | | | | | | 2) FBC-R803.2.3.1 SHEATHING FASTENINGS. | | | WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO | | | ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON | | | CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE | | | FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING | | | MINIMUM DIMENSIONS: | | | 1. 0.113 INCH NOMINAL SHANK DIAMETER. | | | 2. RING DIAMETER OF 0.012 OVER SHANK DIAMETER. | | | 3. 16 TO 20 RINGS PER INCH. | | | 4. 0.280 INCH FULL ROUND HEAD DIAMETER. | | | 5. 2 INCH NAIL LENGTH. | | | WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G < | | | 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE | | | 4 INCHES ON CENTER IN NAILING ZONE 3 IN ACCORDANCE WITH | | | FIGURE R803.2.3.1 WHERE VASD AS DETERMINED IN | | | ACCORDANCE WITH SECTION R301.2.1.3 IS 130 MPH OR | | | GREATER. | | | | | | 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | 4) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORT | | | FOR THE ICYNENE SPRAY FOAM INSULATION. FBC R316 | | | | | | 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE METAL ROOFING | | | SUBMITTALS. | | | | | | 6) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN | | | PRESSURES PURSUANT TO FBC-R301.2. | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-10-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-03 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-03 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2014-10-03 15:37:57 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | BUILDING | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS | | | LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA | | | BUILDING CODE AND OTHER RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS AS REQUIRED BY FBC 107.2.1. | | | CLEARLY SPECIFY THE SCOPE OF WORK THAT WILL BE | | | PREFORMED UNDER THIS PERMIT. | | | | | | 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | NOTE: DUE TO THE MISSING INFORMATION, ADDITIONAL | | | COMMENTS MAY RESULT WHEN THE PLANS ARE RESUBMITTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-11-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
07:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-03 |
Time |
17:40 |
Sent To |
|
|
| Notes |
| 2014-11-04 08:08:17 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | | RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT OF | | | RE-INSPECTION FEE(S). | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-10-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-08 |
Time |
18:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-08 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2014-10-08 17:49:32 | PLAN REVIEW COMMENTS | | | | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | ELECTRICAL | | | | | | 1) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS | | | LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA | | | BUILDING CODE, 2008 NATIONAL ELECTRICAL CODE AND OTHER | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS | | | REQUIRED BY FBC 107.2.1. CLEARLY SPECIFY THE SCOPE OF | | | WORK THAT WILL BE PREFORMED UNDER THIS PERMIT. BASED ON | | | THE ELECTRICAL PLANS THAT WERE SUBMITTED, IT APPEARS | | | THAT THERE WILL BE A SERVICE CHANGE AND THE DWELLING IS | | | BEING RE-WIRED. PLEASE CLARIFY. | | | | | | 2) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | 3) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME | | | POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET. | | | | | | 4) NEC 210.8 (A) (1)-(8) - GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION REQUIRED. | | | | | | 5) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET | | | FOR WITHIN 25' OF MECHANICAL EQUIPMENT. | | | | | | 6) NEC 210.12 (B) - OUTLETS TO BE AFCI PROTECTED. | | | | | | 7) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE | | | REQUIRED. | | | | | | 8) FBC 107.3.5.3 SUBMIT A PANEL SCHEDULE. | | | | | | 9) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. | | | | | | 10) FBC- 107.3.5.3 - ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. | | | | | | 11) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE | | | ELECTRICAL EQUIPMENT ON THE PLANS. | | | | | | 12) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH | | | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | | OUTLETS. | | | | | | 13) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP | | | RECEPTACLES SHALL BE SUPPLIED BY NO FEWER THAN TWO | | | SMALL APPLIANCE BRANCH CIRCUITS. | | | | | | 14) NEC 210.70 (A) - (C) LIGHTING OUTLETS REQUIRED. AT | | | LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET IS | | | REQUIRED ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR | | | EXITS. | | | | | | 15) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE | | | PRESENT. | | | | | | 16) NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE | | | AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR | | | PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR | | | LESS. | | | | | | 17) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL | | | BE PROVIDED. | | | | | | 18) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE | | | REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE | | | PLANS. | | | | | | 19) NEC 210.52 (E)(1) ? AT LEAST ONE RECEPTACLE OUTLET | | | ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED | | | NOT MORE THAN 6 ? FT. ABOVE GRADE SHALL BE INSTALLED AT | | | THE FRONT AND BACK OF THE DWELLING. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2014-10-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-03 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-03 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2014-10-03 16:00:09 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | ELECTRICAL | | | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS | | | LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA | | | BUILDING CODE, 2008 NATIONAL ELECTRICAL CODE AND OTHER | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS | | | REQUIRED BY FBC 107.2.1. CLEARLY SPECIFY THE SCOPE OF | | | WORK THAT WILL BE PREFORMED UNDER THIS PERMIT. | | | | | | 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | 4) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME | | | POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET. | | | | | | 5) NEC 210.8 (A) (1)-(8) - GROUND-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION REQUIRED. | | | | | | 6) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET | | | FOR WITHIN 25' OF MECHANICAL EQUIPMENT. | | | | | | 7) NEC 210.12 (B) - OUTLETS TO BE AFCI PROTECTED. | | | | | | 8) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE | | | REQUIRED. | | | | | | 9) NEC 240.24(A) & (B) PANELS SHALL BE READILY | | | ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS. | | | SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL | | | FLOOR PLAN. | | | | | | 10) FBC 107.3.5.3 SUBMIT A PANEL SCHEDULE. | | | | | | NOTE: DUE TO THE MISSING INFORMATION, ADDITIONAL | | | COMMENTS MAY RESULT WHEN THE PLANS ARE RESUBMITTED. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2014-11-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-05 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-05 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2014-11-05 08:38:05 | DAISY PERRY SUBMITTED ENERGY CALCULATIONS AND EQUIPMENT | | | SIZING CALCULATIONS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-11-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-29 |
Time |
10:58 |
Sent To |
P |
|
| Notes |
| 2014-10-29 11:25:04 | TO T. LARGE'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-10-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-08 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-07 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2014-10-07 16:14:31 | TO RM'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-10-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-03 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-09-19 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2014-09-20 08:08:21 | INCOMING SENT TO R01 . JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2014-11-05 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-05 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-05 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2014-11-05 08:39:45 | APPROVED WITH EXCEPTION. AHRI CERTIFICATIONS FOR THE | | | HEATING AND COOLING EQUIPMENT ARE REQUIRED TO BE | | | SUBMITTED TO THE FIELD INSPECTOR. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2014-11-04 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-11-03 |
Time |
17:40 |
Sent To |
|
|
| Notes |
| 2014-11-04 08:43:09 | PREVIOUS COMMENTS WERE NOT ADDRESSED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2014-10-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-10-08 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-10-08 |
Time |
18:20 |
Sent To |
|
|
| Notes |
| 2014-10-08 18:43:42 | PLAN REVIEW COMMENTS | | | | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | MECHANICAL | | | | | | NOTE: MECHANICAL PLANS HAVE BEEN ADDED TO THIS | | | SUBMITTAL THAT WERE NOT INCLUDED IN THE ORIGINAL PLANS | | | THAT WERE SUBMITTED. | | | | | | 1) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS | | | LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR | | | SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA | | | BUILDING CODE AND OTHER RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS AS REQUIRED BY FBC 107.2.1. | | | CLEARLY SPECIFY THE SCOPE OF WORK THAT WILL BE | | | PREFORMED UNDER THIS PERMIT. | | | IS THIS AN EXISTING HVAC SYSTEM THAT IS BEING REPLACED, | | | A NEW INSTALLATION OR JUST NEW DUCT WORK. | | | | | | 2) FBC - R M1401.3 SIZING. HEATING AND COOLING | | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | | | 3) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND | | | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN | | | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT | | | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. | | | | | | 4) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW | | | CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, | | | KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, | | | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, | | | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, | | | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, | | | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM | | | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. | | | | | | NOTE: DUE TO THE MISSING INFORMATION, ADDITIONAL | | | COMMENTS MAY RESULT WHEN THE PLANS ARE RESUBMITTED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2014-10-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-11-04 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-10-29 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2014-10-29 11:49:01 | 1) NONE OF THE REVIEW COMMENTS FROM THE REVIEW DONE ON | | | 10/8/14. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2014-10-08 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-10-08 |
Time |
04:44 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-10-08 |
Time |
04:41 |
Sent To |
|
|
| Notes |
| 2014-10-08 04:44:13 | 1) INDICATE ON BOTH SETS OF PLANS THE ENTIRE SCOPE OF | | | WORK TO BE DONE. CLEARLY IDENTIFY WHAT WILL BE NEW AND | | | WHAT IS EXISTING TO REMAIN. A NARRATIVE DESCRIBING THE | | | SCOPE OF WORK WILL AID IN THE REVIEW.WPB AMEND. TO 2010 | | | FBC SEC.107.2.1. | | | SINCE THE PLANS ARE SO VAGUE ADDITIONAL REVIEW COMMENTS | | | MAY BE GENERATED UPON THE SECOND REVIEW. 2ND REQUEST. | | | 2) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR | | | PLAN THAT CLEARLY REFLECTS THE SCOPE OF WORK TO BE | | | DONE. | | | 3) IF ANY PLUMBING FIXTURES ARE TO BE RELOCATED SUBMIT | | | A SANITARY RISER DIAGRAM FOR REVIEW. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2014-09-30 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2014-09-30 |
Time |
03:42 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2014-09-30 |
Time |
03:42 |
Sent To |
|
|
| Notes |
| 2014-09-30 03:46:07 | 1) INDICATE ON BOTH SETS OF PLANS THE ENTIRE SCOPE OF | | | WORK TO BE DONE. CLEARLY IDENTIFY WHAT WILL BE NEW AND | | | WHAT IS EXISTING TO REMAIN. A NARRATIVE DESCRIBING THE | | | SCOPE OF WORK WILL AID IN THE REVIEW.WPB AMEND. TO 2010 | | | FBC SEC.107.2.1. | | | SINCE THE PLANS ARE SO VAGUE ADDITIONAL REVIEW COMMENTS | | | MAY BE GENERATED UPON THE SECOND REVIEW. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|
|