Plan Review Details - Permit 14090683
Plan Review Stops For Permit 14090683
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-11-03 Cont ID  
Sent By tklarge Date 2014-11-04 Time 04:30 Rev Time 0.00
Received By rmcdouga Date 2014-11-03 Time 17:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By rmcdouga Date 2014-10-08 Time 17:46 Rev Time 0.00
Received By rmcdouga Date 2014-10-08 Time 17:17 Sent To  
Notes
2014-10-08 17:46:12PLAN REVIEW COMMENTS
  
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC-R703.6.3 WHERE CEMENT PLASTER (STUCCO) IS TO BE
 APPLIED TO LATH OVER FRAME CONSTRUCTION, MEASURES SHALL
 BE TAKEN TO PREVENT BONDING BETWEEN THE CEMENT PLASTER
 AND THE WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE
 PROVIDED BETWEEN THE WATER-RESISTIVE BARRIER AND THE
 CEMENT PLASTER (STUCCO) CONSISTING OF ONE OF THE
 FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER
 MATERIAL; OR
 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP; OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
  
 2) FBC-R803.2.3.1 SHEATHING FASTENINGS.
 WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED TO
 ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. RING-SHANK NAILS SHALL HAVE THE FOLLOWING
 MINIMUM DIMENSIONS:
 1. 0.113 INCH NOMINAL SHANK DIAMETER.
 2. RING DIAMETER OF 0.012 OVER SHANK DIAMETER.
 3. 16 TO 20 RINGS PER INCH.
 4. 0.280 INCH FULL ROUND HEAD DIAMETER.
 5. 2 INCH NAIL LENGTH.
 WHERE ROOF FRAMING WITH A SPECIFIC GRAVITY, 0.42 < G <
 0.49 IS USED, SPACING OF RING-SHANK FASTENERS SHALL BE
 4 INCHES ON CENTER IN NAILING ZONE 3 IN ACCORDANCE WITH
 FIGURE R803.2.3.1 WHERE VASD AS DETERMINED IN
 ACCORDANCE WITH SECTION R301.2.1.3 IS 130 MPH OR
 GREATER.
  
 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 4) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORT
 FOR THE ICYNENE SPRAY FOAM INSULATION. FBC R316
  
 5) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE METAL ROOFING
 SUBMITTALS.
  
 6) FBC 107.3.5.3 - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By rmcdouga Date 2014-10-03 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2014-10-03 Time 15:14 Sent To  
Notes
2014-10-03 15:37:57PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS
 LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA
 BUILDING CODE AND OTHER RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS AS REQUIRED BY FBC 107.2.1.
 CLEARLY SPECIFY THE SCOPE OF WORK THAT WILL BE
 PREFORMED UNDER THIS PERMIT.
  
 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 NOTE: DUE TO THE MISSING INFORMATION, ADDITIONAL
 COMMENTS MAY RESULT WHEN THE PLANS ARE RESUBMITTED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-11-04 Cont ID  
Sent By rmcdouga Date 2014-11-04 Time 07:38 Rev Time 0.00
Received By rmcdouga Date 2014-11-03 Time 17:40 Sent To  
Notes
2014-11-04 08:08:17APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT OF
 RE-INSPECTION FEE(S).
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By rmcdouga Date 2014-10-08 Time 18:20 Rev Time 0.00
Received By rmcdouga Date 2014-10-08 Time 18:20 Sent To  
Notes
2014-10-08 17:49:32PLAN REVIEW COMMENTS
  
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 ELECTRICAL
  
 1) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS
 LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA
 BUILDING CODE, 2008 NATIONAL ELECTRICAL CODE AND OTHER
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS
 REQUIRED BY FBC 107.2.1. CLEARLY SPECIFY THE SCOPE OF
 WORK THAT WILL BE PREFORMED UNDER THIS PERMIT. BASED ON
 THE ELECTRICAL PLANS THAT WERE SUBMITTED, IT APPEARS
 THAT THERE WILL BE A SERVICE CHANGE AND THE DWELLING IS
 BEING RE-WIRED. PLEASE CLARIFY.
  
 2) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 3) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET.
  
 4) NEC 210.8 (A) (1)-(8) - GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION REQUIRED.
  
 5) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET
 FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 6) NEC 210.12 (B) - OUTLETS TO BE AFCI PROTECTED.
  
 7) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 8) FBC 107.3.5.3 SUBMIT A PANEL SCHEDULE.
  
 9) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 10) FBC- 107.3.5.3 - ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
  
 11) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE
 ELECTRICAL EQUIPMENT ON THE PLANS.
  
 12) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 13) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP
 RECEPTACLES SHALL BE SUPPLIED BY NO FEWER THAN TWO
 SMALL APPLIANCE BRANCH CIRCUITS.
  
 14) NEC 210.70 (A) - (C) LIGHTING OUTLETS REQUIRED. AT
 LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET IS
 REQUIRED ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR
 EXITS.
  
 15) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE
 PRESENT.
  
 16) NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE
 AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR
 PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR
 LESS.
  
 17) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 18) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE
 REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE
 PLANS.
  
 19) NEC 210.52 (E)(1) ? AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED
 NOT MORE THAN 6 ? FT. ABOVE GRADE SHALL BE INSTALLED AT
 THE FRONT AND BACK OF THE DWELLING.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By rmcdouga Date 2014-10-03 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2014-10-03 Time 15:38 Sent To  
Notes
2014-10-03 16:00:09PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 ELECTRICAL
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS
 LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA
 BUILDING CODE, 2008 NATIONAL ELECTRICAL CODE AND OTHER
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS
 REQUIRED BY FBC 107.2.1. CLEARLY SPECIFY THE SCOPE OF
 WORK THAT WILL BE PREFORMED UNDER THIS PERMIT.
  
 3) FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 4) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET.
  
 5) NEC 210.8 (A) (1)-(8) - GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION REQUIRED.
  
 6) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET
 FOR WITHIN 25' OF MECHANICAL EQUIPMENT.
  
 7) NEC 210.12 (B) - OUTLETS TO BE AFCI PROTECTED.
  
 8) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 9) NEC 240.24(A) & (B) PANELS SHALL BE READILY
 ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS.
 SPECIFY THE LOCATIONS OF THE PANELS ON THE ELECTRICAL
 FLOOR PLAN.
  
 10) FBC 107.3.5.3 SUBMIT A PANEL SCHEDULE.
  
 NOTE: DUE TO THE MISSING INFORMATION, ADDITIONAL
 COMMENTS MAY RESULT WHEN THE PLANS ARE RESUBMITTED.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-11-05 Cont ID  
Sent By rmcdouga Date 2014-11-05 Time 08:36 Rev Time 0.00
Received By rmcdouga Date 2014-11-05 Time 08:36 Sent To  
Notes
2014-11-05 08:38:05DAISY PERRY SUBMITTED ENERGY CALCULATIONS AND EQUIPMENT
 SIZING CALCULATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-04 Cont ID  
Sent By rmcdouga Date 2014-11-04 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2014-10-29 Time 10:58 Sent To P
Notes
2014-10-29 11:25:04TO T. LARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-08 Cont ID  
Sent By rmcdouga Date 2014-10-08 Time 18:43 Rev Time 0.00
Received By rmcdouga Date 2014-10-07 Time 16:13 Sent To  
Notes
2014-10-07 16:14:31TO RM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-03 Cont ID  
Sent By rmcdouga Date 2014-10-03 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2014-09-19 Time 08:04 Sent To  
Notes
2014-09-20 08:08:21INCOMING SENT TO R01 . JW

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-11-05 Cont ID  
Sent By rmcdouga Date 2014-11-05 Time 08:36 Rev Time 0.00
Received By rmcdouga Date 2014-11-05 Time 08:36 Sent To  
Notes
2014-11-05 08:39:45APPROVED WITH EXCEPTION. AHRI CERTIFICATIONS FOR THE
 HEATING AND COOLING EQUIPMENT ARE REQUIRED TO BE
 SUBMITTED TO THE FIELD INSPECTOR.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-11-04 Cont ID  
Sent By rmcdouga Date 2014-11-04 Time 08:28 Rev Time 0.00
Received By rmcdouga Date 2014-11-03 Time 17:40 Sent To  
Notes
2014-11-04 08:43:09PREVIOUS COMMENTS WERE NOT ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2014-10-08 Cont ID  
Sent By rmcdouga Date 2014-10-08 Time 18:43 Rev Time 0.00
Received By rmcdouga Date 2014-10-08 Time 18:20 Sent To  
Notes
2014-10-08 18:43:42PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MECHANICAL
  
 NOTE: MECHANICAL PLANS HAVE BEEN ADDED TO THIS
 SUBMITTAL THAT WERE NOT INCLUDED IN THE ORIGINAL PLANS
 THAT WERE SUBMITTED.
  
 1) AT THIS TIME THERE ARE SEVERAL OPEN PERMITS AT THIS
 LOCATION. THE PLANS THAT WERE SUBMITTED DO NOT INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE PROPOSED WORK OR
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE 2010 FLORIDA
 BUILDING CODE AND OTHER RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS AS REQUIRED BY FBC 107.2.1.
 CLEARLY SPECIFY THE SCOPE OF WORK THAT WILL BE
 PREFORMED UNDER THIS PERMIT.
 IS THIS AN EXISTING HVAC SYSTEM THAT IS BEING REPLACED,
 A NEW INSTALLATION OR JUST NEW DUCT WORK.
  
 2) FBC - R M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 3) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND
 SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN
 AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT
 CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS.
  
 4) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW
 CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST,
 KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS,
 EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR,
 ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION,
 COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS,
 APPLIANCES, BOILERS, REFRIGERATION, BATHROOM
 VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION.
  
 NOTE: DUE TO THE MISSING INFORMATION, ADDITIONAL
 COMMENTS MAY RESULT WHEN THE PLANS ARE RESUBMITTED.

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-10-30 Cont ID  
Sent By rmcdouga Date 2014-11-04 Time 08:43 Rev Time 0.00
Received By tklarge Date 2014-10-29 Time 11:48 Sent To  
Notes
2014-10-29 11:49:011) NONE OF THE REVIEW COMMENTS FROM THE REVIEW DONE ON
 10/8/14.

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-10-08 Cont ID  
Sent By tklarge Date 2014-10-08 Time 04:44 Rev Time 0.00
Received By tklarge Date 2014-10-08 Time 04:41 Sent To  
Notes
2014-10-08 04:44:131) INDICATE ON BOTH SETS OF PLANS THE ENTIRE SCOPE OF
 WORK TO BE DONE. CLEARLY IDENTIFY WHAT WILL BE NEW AND
 WHAT IS EXISTING TO REMAIN. A NARRATIVE DESCRIBING THE
 SCOPE OF WORK WILL AID IN THE REVIEW.WPB AMEND. TO 2010
 FBC SEC.107.2.1.
 SINCE THE PLANS ARE SO VAGUE ADDITIONAL REVIEW COMMENTS
 MAY BE GENERATED UPON THE SECOND REVIEW. 2ND REQUEST.
 2) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN THAT CLEARLY REFLECTS THE SCOPE OF WORK TO BE
 DONE.
 3) IF ANY PLUMBING FIXTURES ARE TO BE RELOCATED SUBMIT
 A SANITARY RISER DIAGRAM FOR REVIEW.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-30 Cont ID  
Sent By tklarge Date 2014-09-30 Time 03:42 Rev Time 0.00
Received By tklarge Date 2014-09-30 Time 03:42 Sent To  
Notes
2014-09-30 03:46:071) INDICATE ON BOTH SETS OF PLANS THE ENTIRE SCOPE OF
 WORK TO BE DONE. CLEARLY IDENTIFY WHAT WILL BE NEW AND
 WHAT IS EXISTING TO REMAIN. A NARRATIVE DESCRIBING THE
 SCOPE OF WORK WILL AID IN THE REVIEW.WPB AMEND. TO 2010
 FBC SEC.107.2.1.
 SINCE THE PLANS ARE SO VAGUE ADDITIONAL REVIEW COMMENTS
 MAY BE GENERATED UPON THE SECOND REVIEW.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  