Plan Review Details - Permit 14090659
Plan Review Stops For Permit 14090659
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-03-11 Cont ID  
Sent By jwitmer Date 2015-03-11 Time   Rev Time 0.00
Received By jwitmer Date 2015-03-11 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-02-28 Cont ID  
Sent By jwitmer Date 2015-02-28 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2015-02-28 Time 08:00 Sent To  
Notes
2015-02-28 11:40:57BUILDING PLAN REVIEW
 PERMIT: 14090659
 ADD: 500 BELVEDERE RD
 CONT: OAK CONSTRUCTION
 TEL:(954)583-9625
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: SAT. FEB. 28/2015
 ACTION:
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
  
 1) COMPLIED.
  
 2) COMPLIED.
  
  
 3) COMPLIED. SOILS REPORTS.
  
 4-13) BUILDING PROVISO;
  
 5-13) 107.3.4.2 DEFERRED SUBMITTALS: 107.3.4.2 FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE (PUBLIX) WHO SHALL REVIEW THEM AND
 FORWARD THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
  
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOFTOP
 INSULATION
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS, A/C ROOF CURBS AND ADAPTORS
  
 14)(A-C) COMPLIED.
  
 .
  
 14C) . REVISION REQUIRED. THE DOOR SCHEDULE HAS BEEN
 MOVED SO THE DOOR IDENTIFICATION NUMBERS ARE VISIBLE.
 THE REMAINING ISSUE IS THE DOOR HARDWARE SHOWS HARDWARE
 TYPE GROUPS BUT THERE IS NO HARDWARE SCHEDULE SHOWN ON
 THIS PAGE. COMPLIANCE WITH DOOR TYPE AND REQUIRED
 HARDWARE CAN NOT BE VERIFIED. RESPONSE INDICATES SEE
 SHEET PM-5. SHEET PM 4-5 BOTH SHOW THE HARDWARE SPECS,
 NOT A HARDWARE SCHEDULE. A REVISION WILL BE REQUIRED
 WITH A HARDWARE SCHEDULE, REVIEWED AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE THE FRAMING INSPECTION.
  
 14D-E) COMPIED.
  
 15) SEMI-COMPLIED. SHEET LS-1 VESTIBULE THE PLANS SHOW
 A NEW LOCATION FOR 2 ELECTRIC CARTS. THE LOCATION AS
 SHOWN ON THE PLANS IS NOT CLEAR IF THE 30 X 48 INCH
 CLEAR FLOOR SPACE IS MAINTAINED IN THE 2 ELECTRIC CART
 LOCATIONS. SHEET LS-1 AND EQ-1 ARE REVISED, SHEET EQ
 HAS A OTE CART STOP SEE A-1 FOR DETAILS BUT THERE IS NO
 DETAIL SHOWING THE ELECTRIC CART BUT A DETAIL OF THE
 FINISHED CORNER.
  
 16-17) COMPLIED.
  
 17)
  
 18A-B) 4TH REVIEW. DETERMINING THE WIND DESIGN CRITERIA
 FOR COMPONENTS & CLADDING AND ASSOCIATED PRESSURES.
 SHEET A-1 DESIGN PRESSURES ARE AS REQUESTED IN VASD.
 THE DESIGN CRITERIA THE DESIGNER OF RECORD HAS USED IS
 ASCE 7-10 TABLE 28.3-1. THIS TABLE IS TO BE USED IN
 CONJUNCTION WITH THE MWFRS, MAIN WIND FORCE RESISTING
 SYSTEM. WITHIN THIS TABLE THE MULTIPLIER OF 1.16 IS FOR
 A EXPOSURE D.
  
 PLEASE REFER BACK TO CHAPTER 26 WIND LOADS : GENERAL
 REQUIREMENTS 26.1.2.1 MAIN WIND FORCE RESISTING SYSTEM
 (2) IS FOR THE ENVELOPE REQUIREMENTS OF A BUILDING SUCH
 AS BAR JOIST SYSTEMS. FOR DETERMINING MWFRS YOU USE
 TABLE 28.2-1 STEP 4 DETERMINING VELOCITY PRESSURE
 EXPOSURE COEFFICIENT, K2 OR KH, SEE TABLE 28.3-1.
  
 SECTION 26.1.2.2 DEALS WITH COMPONENTS & CLADDING. ALSO
 SEE 26.7.4.2 ENVELOPE PRESSURES CHAPTER 28 FOR THE
 MWFRS. 26.7.4.4.
 COMPONENTS AND CLADDING ARE DESIGNED UNDER CHAPTER 30
 COMPONENTS AND CLADDING ARE BASED ON THE EXPOSURE
 CATEGORY RESULTING IN THE HIGHEST WIND LOADS FOR ANY
 WIND DIRECTION AT THE SITE. PLEASE REFER TO TABLE
 30.4.1 OR TABLE 30.5-1 (SIMPLIFIED METHOD) STEPS TO
 DETERMINE FOR THE STEPS TO DETERMINE COMPONENTS &
 CLADDING WIND LOADS FOR ENCLOSED LOW -RISE BUILDINGS.
  
 18C) THE ROOF ZONES NOT IDENTIFIED NOR THE PRESSURES
 FOR THE ROOF ZONE. THIS COMMENT WAS MEANT FOR ROOF
 ZONES FOR COMPONENTS AND CLADDING. SHEET S-7 THE DECK/
 ROOFING UPLIFT PLAN IS IN VULT. IS THIS FOR THE ACTUAL
 ROOF DECK? AND NOT THE ROOF COVERING, UNDER THE 4TH
 REVIEW THERE ARE NOW VASD PRESSURES FOR ROOF JOIST
 ASWELL FOR COMPONENTS AND CLADDING.
 MCG SHEET S.001 PROVIDES BOTH WALL AND ROOF PRESSURES
 FOR ZONES 1-5 THIS PLAN TAKES PRESSURES SUPPOSED AT 38
 FEET. THERE IS A LOWER ROOF WITH A 3 FT. PARAPET. ROOF
 ZONE 3 FOR THE LOWER ROOF SHOULD HAVE THE SAME
 PRESSURES AS FOR ZONE 2 FOR A MENA ROOF HEIGHT OF
 APPROX. 29 FT. THERE WILL STILL NEED PRESSURES A ZONE 3
 FOR THE HIGHER PORTION OF ROOF SEE MCG SHEETS A304 &
 A305 ELEVATIONS OF 36FT-8 IN AND 38 FT. I SPOKE WITH
 THE DESIGNERS OF USING THE 30 FT ELEVATION FOR THE
 LOWER ROOF AND WALL PRESSURES AND A SEPARATE HEADING
 FOR ROOF ZONE 3 AT ELEVATION 38 FT AND THE ASSOCIATED
 HIGHER PRESSURES.
  
 19-26) COMPLIED.
 .
  
 27) DEFERRED SUBMITTAL PRESSURES PROVIDE FOR INSULATION
 SHEETS . ROOF TOP INSULATION TO BE A DEFERRED
 SUBMITTAL.
  
 28) NO ACTION NEEDS TO BE TAKEN JUST A WORD OF CAUTION!
 SHEET S-4 BAR JOIST SPACING. NOTE DEPENDING ON THE
 ROOFING PRODUCT APPROVAL, SPACING OF BAR JOIST AND OR
 THE THICKNESS OF THE STEEL DECK MAY BE A ISSUE ONCE THE
 ROOFING APPROVAL HAS BEEN SUBMITTED. 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS. THE ISSUE IS NOT PRESSURES AS MUCH AS
 ALLOWABLE SPANS THAT WILL SHOW UP UNDER THE ROOFING
 APPROVAL.
  
  
 29 )BUILDING PROVISO, DEFERRED SUBMITTAL. ATAS WIND
 LOCK SOFFIT PANELSWERE SUBMITTED THE FL COVERSHEET WAS
 NOT INCLUDED IDENTIFYING THE PRODUCT. THE STRUCTURAL
 SHEETS DO NOT PROVIDE THE NEGATIVE PRESSUES FOR THE
 SOFFIT. SEE SHEET A502 DETAIL # 01. PRODUCT APPROVAL:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
  
 30) BUILDING PROVISO: ALL DEFERRED SUBMITTALS TO BE
 REVIEWED BY PUBLIX THE DESIGNER OF RECORD.2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE (DESIGNER OF RECORD) PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 31) COMPLIED.
  
 32) DEFERRED SUBMITTAL: DEALS WITH THE USE OF EFIS TYPE
 SYSTEMS. RESPONSE INDICATES 3 SETS OF PRODUCT APPROVAL
 BEING SUBMITTED, COMMENTS 5-13 THE DESIGNER OF RECORD
 "PUBLIX" HAS ELECTED TO HAVE THE PRODUCT APPROVALS BE A
 DEFERED SUBMITTAL. PLEASE NOTE THE RESPONSE INDICATES A
 SHEET T001, I'VE NOT FOUND THIS SHEET IN EITHER THE
 PUBLIX NOR MCG PLANS. THE RESPONSE ALSO INDICATES THAT
 THERE WAS A E-MAIL RESPONSE. WHEN THE DEFERRED
 SUBMITTAL IS SUBMITTED, THE MANUFACTURERS INSTALLATION
 BOOKLET (3) WILL BE REQUIRED, (1) FOR RECORD RETENTION,
 (1) FOR THE RESIDENT INSPECTOR AND (1) SET FOR THE
 CONTRACTOR AND MEP INSPECTORS.
  
 33) SEMI- COMPLIED. SHEET S001 OF THE MCG DRAWINGS LIST
 THE WIND DESIGN AS 170 VULT AND 132 VASD, THEN LIST THE
 PRESSURES FOR ALL ZONES BOTH POSITIVE AND NEGATIVE, IN
 VASD SEE COMMENT 18C.
  
 34) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 35) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-02-05 Cont ID  
Sent By jwitmer Date 2015-02-05 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2015-02-04 Time 10:38 Sent To  
Notes
2015-02-04 11:38:32BUILDING PLAN REVIEW
 PERMIT: 14090659
 ADD: 500 BELVEDERE RD
 CONT: OAK CONSTRUCTION
 TEL:(954)583-9625
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: SAT. FEB. 28/2015
 ACTION:
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
  
 1) COMPLIED.
  
 2) COMPLIED.
  
  
 3) COMPLIED. SOILS REPORTS.
  
 4-13) BUILDING PROVISO;
  
 5-13) 107.3.4.2 DEFERRED SUBMITTALS: 107.3.4.2 FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE (PUBLIX) WHO SHALL REVIEW THEM AND
 FORWARD THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
  
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOFTOP
 INSULATION
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS, A/C ROOF CURBS AND ADAPTORS
  
 14)(A-C) COMPLIED.
  
 .
  
 14C) . REVISION REQUIRED. THE DOOR SCHEDULE HAS BEEN
 MOVED SO THE DOOR IDENTIFICATION NUMBERS ARE VISIBLE.
 THE REMAINING ISSUE IS THE DOOR HARDWARE SHOWS HARDWARE
 TYPE GROUPS BUT THERE IS NO HARDWARE SCHEDULE SHOWN ON
 THIS PAGE. COMPLIANCE WITH DOOR TYPE AND REQUIED
 HARDWARE CAN NOT BE VERIFIED. RESPONCE INDICATES SEE
 SHEET PM-5. SHEET PM 4-5 BOTH SHOW THE HARDWARE SPECS,
 NOT A HARDWARE SCHEDULE. A REVISION WILL BE REQUIRED
 WITH A HARDWARE SCHEDULE, REVIEWED AND APPROVED BY THE
 BUILDING DEPARTMENT BEFORE THE FRAMING INSPECTION.
  
 14D-E) COMPIED.
  
 15) SEMI-COMPLIED. SHEET LS-1 VESTIBULE THE PLANS SHOW
 A NEW LOCATION FOR 2 ELECTRIC CARTS. THE LOCATION AS
 SHOWN ON THE PLANS IS NOT CLEAR IF THE 30 X 48 INCH
 CLEAR FLOOR SPACE IS MAINTAINED IN THE 2 ELECTRIC CART
 LOCATIONS. SHEET LS-1 AND EQ-1 ARE REVISED, SHEET EQ
 HAS A OTE CART STOP SEE A-1 FOR DETAILS BUT THERE IS NO
 DETAIL SHOWING THE ELECTRIC CART BUT A DETAIL OF THE
 FINISHED CORNER.
  
 16-17) COMPLIED.
  
 17)
  
 18A-B) 4TH REVIEW.DETERMINING THE WIND DESIGN CRITERIA
 FOR COMPONENTS & CLADDING AND ASSOCIATED PRESSURES.
 SHEET A-1 DESIGN PRESSURES ARE AS REQUESTED IN VASD.
 THE DESIGN CRITERIA THE DESIGNER OF RECORD HAS USED IS
 ASCE 7-10 TABLE 28.3-1. THIS TABLE IS TO BE USED IN
 CONJUNCTION WITH THE MWFRS, MAIN WIND FORCE RESISTING
 SYSTEM. WITHIN THIS TABLE THE MULTIPLIER OF 1.16 IS FOR
 A EXPOSURE D.
  
 PLEASE REFER BACK TO CHAPTER 26 WIND LOADS : GENERAL
 REQUIREMENTS 26.1.2.1 MAIN WIND FORCE RESISTING SYSTEM
 (2) IS FOR THE ENVELOPE REQUIREMENTS OF A BUILDING SUCH
 AS BAR JOIST SYSTEMS. FOR DETERMINING MWFRS YOU USE
 TABLE 28.2-1 STEP 4 DETERMINING VELOCITY PRESSURE
 EXPOSURE COEFFICIENT, K2 OR KH, SEE TABLE 28.3-1.
  
 SECTION 26.1.2.2 DEALS WITH COMPONENTS & CLADDING. ALSO
 SEE 26.7.4.2 ENVELOPE PRESSURES CHAPTER 28 FOR THE
 MWFRS. 26.7.4.4.
 COMPONENTS AND CLADDING ARE DESIGNED UNDER CHAPTER 30
 COMPONENTS AND CLADDING ARE BASED ON THE EXPOSURE
 CATEGORY RESULTING IN THE HIGHEST WIND LOADS FOR ANY
 WIND DIRECTION AT THE SITE. PLEASE REFER TO TABLE
 30.4.1 OR TABLE 30.5-1 (SIMLIFIED METHOD) STEPS TO
 DETERMINE FOR THE STEPS TO DETERMINE COMPONENTS &
 CLADDING WIND LOADS FOR ENCLOSED LOW -RISE BUILDINGS.
  
 18C) THE ROOF ZONES NOT IDENTIFIED NOR THE PRESSURES
 FOR THE ROOF ZONE. THIS COMMENT WAS MEANT FOR ROOF
 ZONES FOR COMPONENTS AND CLADDING. SHEET S-7 THE DECK/
 ROOFING UPLIFT PLAN IS IN VULT. IS THIS FOR THE ACTUAL
 ROOF DECK? AND NOT THE ROOF COVERING, UNDER THE 4TH
 REVIEW THERE ARE NOW VASD PRESSURES FOR ROOF JOIST
 ASWELL FOR COMPONENTS AND CLADDING.
 MCG SHEET S.001 PROVIDES BOTH WALL AND ROOF PRESSURES
 FOR ZONES 1-5 THIS PLAN TAKES PRESSURES SUPPOSED AT 38
 FEET. THERE IS A LOWER ROOF WITH A 3 FT. PARAPET. ROOF
 ZONE 3 FOR THE LOWER ROOF SHOULD HAVE THE SAME
 PRESSURES AS FOR ZONE 2 FOR A MENA ROOF HEIGHT OF
 APPROX. 29 FT. THERE WILL STILL NEED PRESSURES A ZONE 3
 FOR THE HIGHER PORTION OF ROOF SEE MCG SHEETS A304 &
 A305 ELEVATIONS OF 36FT-8 IN AND 38 FT. I SPOKE WITH
 THE DESIGNERS OF USING THE 30 FT ELEVATION FOR THE
 LOWER ROOF AND WALL PRESSURES AND A SEPARATE HEADING
 FOR ROOF ZONE 3 AT ELEVATION 38 FT AND THE ASSOCIATED
 HIGHER PRESSURES.
  
 19-26) COMPLIED.
 .
  
 27) DEFERRED SUBMITAL PRESSURES PROVIDE FOR INSULATION
 SHEETS . ROOF TOP INSULATION TO BE A DEFERRED
 SUBMITTAL.
  
 28) NO ACTION NEEDS TO BE TAKEN JUST A WORD OF
 CAUTION!L SHEET S-4 BAR JOIST SPACING. NOTE DEPENDING
 ON THE ROOFING PRODUCT APPROVAL, SPACING OF BAR JOIST
 AND OR THE THICKNESS OF THE STEEL DECK MAY BE A ISSUE
 ONCE THE ROOFING APPROVAL HAS BEEN SUBMITTED. 107.2.1.2
 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS. THE ISSUE IS NOT PRESSURES
 AS MUCH AS ALLOWABLE SPANS THAT WILL SHOW UP UNDER THE
 ROOFING APPROVAL.
  
  
 29 )BUILDING PROVISO, DEFERRED SUBMITTAL. ATAS WIND
 LOCK SUFFIT PANELSWERE SUBMITTED THE FL COVERSHEET WAS
 NOT INCLUDED IDENTIFYING THE PRODUCT. THE STRUCTURAL
 SHEETS DO NOT PROVIDE THE NEGATIVE PRESSUES FOR THE
 SOFFIT. SEE SHEET A502 DETAIL # 01. PRODUCT APPROVAL:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
  
 30) BUILDING PROVISO: ALL DEFERRED SUBMITTALS TO BE
 REVIEWED BY PUBLIX THE DESIGNER OF RECORD.2010 FBC
 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE (DESIGNER OF RECORD) PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 31) COMPLIED.
  
 32) DEFERRED SUBMITTAL: DEALS WITH THE USE OF EFIS TYPE
 SYSTEMS. RESPONSE INDICATES 3 SETS OF PRODUCT APPROVAL
 BEING SUBMITTED, COMMENTS 5-13 THE DESIGNER OF RECORD
 "PUBLIX" HAS ELECTED TO HAVE THE PRODUCT APPROVALS BE A
 DEFFERED SUBMITAL. PLEASE NOTE THE RESPONSE INDICATES A
 SHEET T001, I'VE NOT FOUND THIS SHEET IN EITHER THE
 PUBLIX NOR MCG PLANS. THE RESPONSE ALSO INDICATES THAT
 THERE WAS A E-MAIL RESPONSE. WHEN THE DEFERRED
 SUBMITTAL IS SUBMITTED, THE MANUFACTURERS INSTALATION
 BOOKLET (3) WILL BE REQUIRED, (1) FOR RECORD RETENTION,
 (1) FOR THE RESIDENT INSPECTOR AND (1) SET FOR THE
 CONTRACTOR AND MEP INSPECTORS.
  
 33) SEMI- COMPLIED. SHEET S001 OF THE MCG DRAWINGS LIST
 THE WIND DESIGN AS 170 VULT AND 132 VASD, THEN LIST THE
 PRESSURES FOR ALL ZONES BOTH POSITIVE AND NEGATIVE, IN
 VASD SEE COMMENT 18C.
  
 34) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 35) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-24 Cont ID  
Sent By jwitmer Date 2014-12-24 Time 08:42 Rev Time 0.00
Received By jwitmer Date 2014-12-24 Time 06:30 Sent To  
Notes
2014-12-24 08:42:12BUILDING PLAN REVIEW
 PERMIT: 14090659
 ADD: 500 BELVEDERE RD
 CONT: TBD
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. DEC. 24/ 2014
 ACTION: DENIED
  
  
 1) COMPLIED.
  
 2A) 2ND REQUEST. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION,
 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING
 OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY OTHERS, THE
 INSPECTIONS REQUIRED BY SECTION 109. HE/SHE MAY ACCEPT
 REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY.
 THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR FOR:
 BUILDING TYPE II CONSTRUCTION
 FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE FOOT
 FOR ALL MAJOR STRUCTURAL ALTERATIONS
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 2B) 2ND REQUEST. 110.4 INSPECTION AGENCIES. THE
 BUILDING OFFICIAL IS AUTHORIZED TO ACCEPT REPORTS OF
 APPROVED INSPECTION AGENCIES, PROVIDED SUCH AGENCIES
 SATISFY THE REQUIREMENTS AS TO QUALIFICATIONS AND
 RELIABILITY.
  
 2C)2ND REQUEST. FBC* 110.3.9 RESIDENT INSPECTOR. SUBMIT
 INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD,
 MANAGER OF THE RESIDENT INSPECTOR PROGRAM. KEN CONRAD
 CONTACT INFORMATION:
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2D)2ND REQUEST . SINCE THIS PROJECT WILL BE PART OF THE
 RESIDENT INSPECTOR PROGRAM A THIRD SET OF ALL PLANS AND
 SUPPORTING DOCUMENTS (ENERGY CALCULATIONS, SOILS
 REPORTS, PRODUCT APPROVALS ETC, WILL BE REQUIRED.
 107.3.1.
  
 NOTE, FORMS WERE E-MAILED TO :
 [email protected]
  
 3) 2ND REQUEST SEE COMMENT 2D.. SINCE THIS PROJECT WILL
 BE PART OF THE RESIDENT INSPECTOR PROGRAM A THIRD SET
 OF ALL PLANS AND SUPPORTING DOCUMENTS (ENERGY
 CALCULATIONS, SOILS REPORTS, PRODUCT APPROVALS ETC,
 WILL BE REQUIRED. 107.3.1.
 MISSING SOILS REPORTS, 2010 FBC-B 1803.5.2 QUESTIONABLE
 SOIL. WHERE THE CLASSIFICATION, STRENGTH OR
 COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 4) 2ND REQUEST. SUBMIT (3) COPIES. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
  
 PLEASE SEE RESPONCE TO COMMENT # 5. ANS: ACKNOWLEDGED.
 PLEASE NOTE AT THIS STAGE OFTHE PROJECT, NO PRODUCT
 APPROVAL SUBMITTALS HAVE BEEN SUBMITTED, REVIEWED OR
 APPROVED BY THE SUPERVISING ARCHITECT (PUBLIX).
  
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOFTOP
 INSULATION
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS, A/C ROOF CURBS AND ADAPTORS
  
 PLEASE NOTE THAT IF THE DESIGNER OF RECORD WISHES TO
 HAVE THE PRODUCT APPROVALS BE DEFERRED SUBMITTALS,
 PLEASE PROVIDE A WRITTEN REQUEST. THE PRODUCT APPROVALS
 LISTED ON THE MCG SET OF DRAWINGS WILL BE THE ONLY ONES
 ACCEPTED NO SUBSTATUTES.
  
 5 ) 2ND REQUEST. THE COVER SHEET LIST PRODUCT APPROVALS
 REQUIRED BY THE DESIGNER OF RECORD, ALL LISTED ARE
 FLORIDA APPROVALS ONLY, NONE OF THE PRODUCTS HAVE BEEN
 REVIEWED BY THE DESIGNER OF RECORD . 2010 FBC 107.3.4.1
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED
 BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 PLEASE SEE RESPONCE TO COMMENT # 5. ANS: ACKNOWLEDGED.
 PLEASE NOTE AT THIS STAGE OFTHE PROJECT, NO PRODUCT
 APPROVAL SUBMITTALS HAVE BEEN SUBMITTED, REVIEWED OR
 APPROVED BY THE SUPERVISING ARCHITECT.
  
 6) SEE RESPONCE TO COMMENT #5. . THE ROOFING REPORT
 SUBMITTED FL 5680-R9, LISTED IN THE DESIGNER OF ECORDS
 LIST IS THE MOST CURRENT REPORT FL 5680-R10.
  
 7) SEE RESPONCE TO COMMENT #5 MIAMI-DADE NOA 140626.02
 CARLISLE SURE WELD NOT ON THE DESINER OF RECODS LIST.
  
 8) SEE RESPONCE TO COMMENT #5. FL 11537-R4 DOOR NOT
 IDENTIFIED NOR PRESSURES, ONLY ONE COPY SUBMITTED.
 MISSING INSTALATION INSTRUCTIONS.
  
 9) SEE RESPONCE TO COMMENT #5. SUBMITTED FL 11749-R2
 DESIGNER OF RECORD REQUESTED FL 14636-R3.
  
 10)SEE RESPONCE TO COMMENT #5. SUBMITTED FL 13533-R4
 UPDATE TO THE CURRENT FL 13533-R5.
  
 11) SEE RESPONCE TO COMMENT #5. SUBMITTED DRYVIT
 SYSTEMS 11-1108.02 & 12-0703.03 MIAMI-DADE NOA, NOT ON
 LIST, NEVER REVIEWED.
  
 12) SEE RESPONCE TO COMMENT #5. SUBMITTED 1 COPY OF FL
 15110.1 MIAMI-DADE NOA IDENTIFY IF INSTALATION IS A "S"
 OR "NB" DOOR.
  
 13) SEE RESPONCE TO COMMENT #5. NO WINDOW REPORTS, WALL
 LOUVERS AND PRE-ENGINEERED A/C STANDS WERE SUBMITTED.
  
 NOTE!!!!!!!!!!! WHEN THE DESIGN PRESSURES ARE CORRECT,
 THE DESIGNER OF RECORD CAN ELECT TO SUBMIT THE PRODUCT
 APPROVALS AFTER THE PERMIT IS ISSUED, GIVING THE
 CONTRACTOR TIME TO SHOP AROUND AND PROVIDE PRODUCT
 APPROVALS THAT HAVE BEEN REVIEWED BY THE DESIGNER OF
 RECORD AND APPROVED. THIS WOULD BE A DEFERRED
 SUBMITTAL, THE DESIGNER OF RECORD WILL NEED TO WRITE
 THERE INTENT IF SO DESIRED.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
  
 2ND REVIEW ENDS RESPONCE BY PUBLIX. IT WOULD APPEAR
 THAT MCG ARCHITECTURE IS RESPONDING, NOT THE ARCHITECT
 OF RECORD, DAVID LEWIS TAULBEE, AR 91318.WE HAVE NOT
 RECEIVED A RESPONCE FROM PUBIX.L
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 ------------------
 14)(A) THERE ARE DISCREPANCIES IN THE LS-1 EGRESS DOOR
 IDENTIFICATION PLAN VERSES THE CHART AT THE BOTTOM OF
 THE PAGE. DISCREPANCY DOORS ON THE PLANS 22 & 18 ARE
 NOT ON THE CHART AND ON THE CHART DOORS 21 & 19 ARE NOT
 ON THE PLAN.
  
 14)(B) DOOR # 17,18 & 19 ARE NOT ON THE CHART NOR IS
 DOOR OPENING TO THE LEFT IN THE VESTIBULE BETWEEN DOORS
 3 & 90, ARROWS SHOWING AN EGRESS PATH AND A EXIT SIGN
 SHOWN, NO DOOR IS IDENTIFIED. THE DOORS CAN NOT BE
 IDENTIFIED ON SHEET A5 SINCE THE STAPLES THAT BIND THE
 PLANS TOGETHER ARE OVER THE IDENTIFYING DOOR NUMBERS.
  
 14C) SHEET A-5 THE DOOR SCHEDULE IS IN THE UPPER LEFT
 HAND CORNER SO FAR THE STAPLES WILL NOT LET YOU
 IDENTIFY THE DOOR. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 14D) DOOR # 3 APPEARS TO BE (2) 48 INCH SWING DOORS.
 BOTH DOORS ARE MISSING THE 18" CLEARANCE FOR
 MANEUVERING CLEARANCES 2010 FL ACC CODE TABLE
 404.2.4.1.
  
 14E) PLEASE PROVIDE A SURVEY OR SITE PLAN, THE ISSUE IS
 IS THERE A PROPERTY LINE BETWEEN PUBLIX AND THE OTHER
 STORES, OR SITE PROPERTY LINE. THE DESIGN TEAM IS
 TAKING AN EXECPTION TO UNLIMITED AREA UNDER 507.4.
 507.5 REQUIRES 3 HR WALLS FOR WALLS WITH ONLY 40'-0"
 CLEAR.
  
 15) SHEET LS-1 VESTIBULE POSSIBLY 2 ELECTRIC CARTS ARE
 IN THE EGRESS PATH.
 2010 FBC-B 1003.3.3 HORIZONTAL PROJECTIONS. STRUCTURAL
 ELEMENTS, FIXTURES OR FURNISHINGS SHALL NOT PROJECT
 HORIZONTALLY FROM EITHER SIDE MORE THAN 4 INCHES (102
 MM) OVER ANY WALKING SURFACE BETWEEN THE HEIGHTS OF 27
 INCHES (686 MM) AND 80 INCHES (2032 MM) ABOVE THE
 WALKING SURFACE.
 2010 FBC-B 1003.3.4 CLEAR WIDTH. PROTRUDING OBJECTS
 SHALL NOT REDUCE THE MINIMUM CLEAR WIDTH OF ACCESSIBLE
 ROUTES.
  
 16) LS1 BETWEEN GRID LINE 1 & 2 THERE APPEARS TO BE AN
 EXIT WAY FROM THE FRONT OF THE BUILDING BUT IT STOPS
 MIDWAY THROUGH THE BUILDING. THEN AT THE REAR CORNER OF
 THE BUILDING THERE IS DOOR 25, IS THIS EXIT IN THE SAME
 CORRIDOR OR IS THE REAR OF THE NEXT BUILDING IN FRONT
 OF THE DOOR? PLEASE PROVIDE WHERE THIS CORRIDOR ENDS?
 1027.2 EXIT DISCHARGE CAPACITY/ 1027.3 EXIT DISCHARGE
 LOCATION.
  
 17) SHEET A-1 ALL EXTERIOR 12" BLOCK WALLS SHOW THEY
 ARE FOAM FILED, PLEASE PROVIDE PRODUCT INFORMATION FOR
 FOAM INSULATION. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 18A) SHEET A-1 DESIGN PRESSURES ARE IN V-ULT, THEY DO
 NOT PROVIDE THE WIND DESIGN CRITERIA. 2010 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 18B) PLEASE ALSO PROVIDE THE VASD PRESSURES SINCE ALL
 THE PRODUCT APPROVALS ARE IN VASD. 1609.3.1.
  
 18C) THE ROOF ZONES NOT IDENTIFIED NOR THE PRESSURES
 FOR THE ROOF ZONE.
  
 19) SHEET A-2. DOORS 30 & 42 CAN NOT VERIFY THEIR FIRE
 RATING SINCE SHEET A5 THE NUMBER COLUMN IDENTIFYING THE
 DOORS IS STAPLED CAN NOT BE VIEWED UNDER THIS REVIEW.
 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 20A) SHEET A-2 NOTE BOTTOM OF SHEET INDICATES TYPE 1 &
 2 WALLS IN THE SEAFOOD & MEAT DEPARTMENT ARE TO BE
 FILED WITH CLOSED CELL SPRAY FOAM POLYURETHANE OR
 ICYENE INSULATION. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B 2603.4.1.2 (1-4) PROVIDE DOCUMENTATION.
  
 20B) SHEET A-2 NOTE BOTTOM OF SHEET INDICATES TYPE 1 &
 2 WALLS IN THE SEAFOOD & MEAT DEPARTMENT ARE TO BE
 FILED WITH CLOSED CELL SPRAY FOAM POLYURETHANE OR
 ICYENE INSULATION. THE USE OF "OR" THE DESIGNER OF
 RECORD MUST DECIDE WHICH SYSTEM WILL BE INSTALLED.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 21) SHEET A-9 GRAB BAR HEIGHTS ARE NOT PROVIDED,
 PROVIDE COMPLIANCE WITH 2010 FBC- ACCESSIBILITY CODE
 609.4. POSITION OF GRAB BARS.
  
 22) SHEET A-17 SECTION THROUGH PHARMACY SHOWS AN
 OPTIONAL DRIVE-THRU WINDOW. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 23) SHEET A-17 SECTIONS THROUGH PHARMACY SHOW GYPSUM
 BOARD SUSPENSION SYSTEM CEILING, THE PLANS DO NOT
 INDICATE HOW THE SYSTEM IS TO BE SUSPENDED, ONLY THAT
 THE 1 1/2" C CHANNEL IS TO OCCUR AT 48 INCHES O.C.?
 PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 2508.1
 GENERAL.
 GYPSUM BOARD AND GYPSUM PLASTER CONSTRUCTION SHALL BE
 OF THE MATERIALS LISTED IN TABLES 2506.2 AND 2507.2.
 THESE MATERIALS SHALL BE ASSEMBLED AND INSTALLED IN
 COMPLIANCE WITH THE APPROPRIATE STANDARDS LISTED IN
 TABLES 2508.1 AND 2511.1.1, AND CHAPTER 35.
  
 24) ADA-2 ATM MACHINES PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATIONS FOR FASTENING THE ATM MACHINE AND
 ANCHORING IT TO EITHER THE FLOOR OR WALL SYSTEM.
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 25A) ADA-2 ATM MACHINES PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-ACCESS. CODE 707.2 CLEAR FLOOR OR GROUND
 SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 25B) 07.5 SPEECH OUTPUT. MACHINES SHALL BE SPEECH
 ENABLED. OPERATING INSTRUCTIONS AND ORIENTATION,
 VISIBLE TRANSACTION PROMPTS, USER INPUT VERIFICATION,
 ERROR MESSAGES, AND ALL DISPLAYED INFORMATION FOR FULL
 USE SHALL BE ACCESSIBLE TO AND INDEPENDENTLY USABLE BY
 INDIVIDUALS WITH VISION IMPAIRMENTS. SPEECH SHALL BE
 DELIVERED THROUGH A MECHANISM THAT IS READILY AVAILABLE
 TO ALL USERS, INCLUDING BUT NOT LIMITED TO, AN INDUSTRY
 STANDARD CONNECTOR OR A TELEPHONE HANDSET. SPEECH SHALL
 BE RECORDED OR DIGITIZED HUMAN, OR SYNTHESIZED.
  
 25C) 707.6.1 INPUT CONTROLS. AT LEAST ONE TACTILELY
 DISCERNIBLE INPUT CONTROL SHALL BE PROVIDED FOR EACH
 FUNCTION. WHERE PROVIDED, KEY SURFACES NOT ON ACTIVE
 AREAS OF DISPLAY SCREENS, SHALL BE RAISED ABOVE
 SURROUNDING SURFACES. WHERE MEMBRANE KEYS ARE THE ONLY
 METHOD OF INPUT, EACH SHALL BE TACTILELY DISCERNABLE
 FROM SURROUNDING SURFACES AND ADJACENT KEYS.
  
 25D) 707.6.2 NUMERIC KEYS. NUMERIC KEYS SHALL BE
 ARRANGED IN A 12-KEY ASCENDING OR DESCENDING TELEPHONE
 KEYPAD LAYOUT. THE NUMBER FIVE KEY SHALL BE TACTILELY
 DISTINCT FROM THE OTHER KEYS.
  
 26A) SHEET RD-1 DETAIL (1) SCUPPERS AND OVERFLOW
 SCUPPERS PLEASE PROVIDE SIZING CALCULATIONS FOR BOTH
 THE SCUPPERS AND OVERFLOW SHALL COMPLY WITH SECTION
 1503 AND THE FLORIDA BUILDING CODE, PLUMBING, CHAPTER
 11.
  
 26B) SHEET RD-1 DETAIL (1) SCUPPERS AND OVERFLOW
 SCUPPERS PLEASE PROVIDE COMPLIANCE 1503.7 PROTECTION
 AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 26C) SHEET RD-1 DETAIL (13) & SHEET S-4 DETAIL (2) A
 PITCH PAN DETAIL, PLEASE NOTE FOR A/C ROOFTOP
 COMPRESSORS PITCH PANS CAN NOT BE USED, COMPLIANCE WITH
 1509.7 MECHANICAL UNITS. ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES
 (203 MM) ABOVE THE ROOF SURFACE (FINISH SURFACE, ALLOW
 FOR ROOF TOP INSULATION, AND UNIT OVER HANG OF CURB),
 OR WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON
 RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM CLEARANCE
 HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
  
  
 26D) SHEET RD-1 DETAIL (7) DOCK CANOPY GUTTER DETAIL
 PLEASE PROVIDE THE SIZING OF THE GUTTER AND THE TYPE OF
 FASTENERS FOR THE WEIGHT OF GUTTER AND RAINWATER RUN
 OFF. 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION
 DOCUMENTS FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR
 WALL ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE
 COMPLIANCE WITH THIS CODE. THE CONSTRUCTION DOCUMENTS
 SHALL PROVIDE DETAILS OF THE EXTERIOR WALL ENVELOPE AS
 REQUIRED, INCLUDING FLASHING, INTERSECTIONS WITH
 DISSIMILAR MATERIALS, CORNERS, END DETAILS, CONTROL
 JOINTS, INTERSECTIONS AT ROOF, EAVES OR PARAPETS, MEANS
 OF DRAINAGE, WATER-RESISTIVE MEMBRANE AND DETAILS
 AROUND OPENINGS.
  
  
 27) SHEET RD-2 DETAIL # 3 ROOR TOP INSULATION DETAIL,
 DETAIL <37.5 PLEASE ELIMINATE THE MEN ROOF IS ABOVE 30
 FEET WITH THE TOP PORTION OF THE ROOF AT 31'-4" AND THE
 TOP OF THE PARAPET AT 34'-0" THIS IS LESS THAN 3'-0"
 AND CREATES CORNER ZONES. THE PLANS WILL NEED TO SHOW
 INSULATION FASTENING FOR FULL SHEETS AND HALF SHEETS
 FOR ZONES 1, 2 & 3 WITH THE ASSOCIATED PRESSURES FOR
 BOTH FULL SHEETS AND HALF SHEETS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 28) SHEET S-4 BAR JOIST SPACING. NOTE DEPENDING ON THE
 ROOFING PRODUCT APPROVAL, SPACING OF BAR JOIST AND OR
 THE THICKNESS OF THE STEEL DECK MAY BE A ISSUE ONCE THE
 ROOFING APPROVAL HAS BEEN SUBMITTED. 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 *******************************************************
 *******************************************************
 *********************************************
  
 ARCHITECTURAL PLANS SUBMITTED SUPPLEMENTAL DOCUMENTS BY
 MCG ARCHITECTURE
  
 29) 2ND REQUEST. ATAS WIND LOCK SUFFIT PANELSWERE
 SUBMITTEDTHE FL COVERSHEET WAS NOT INCLUDED IDENTIFYING
 THE PRODUCT. THE STRUCTURAL SHEETS DO NOT PROVIDE THE
 NEGATIVE PRESSUES FOR THE SOFFIT. SEE SHEET A502 DETAIL
 # 01. PRODUCT APPROVAL: 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, SOFFITS, EFIS SYSTEMS,
  
 30) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 (DESIGNER OF RECORD) PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 31A) COMPLIED. 01/09/15. SHEET A201 AND 300 SERIES
 SHEETS INDICATE THE USE OF 5/8 INCH EXTERIOR GRADE
 PLYWOOD AS BACKING (SHEATHING) PLEASE SEE THE BUILDING
 IS DECLARED A TYPE IIB BUILDING. 03.1 ALLOWABLE
 MATERIALS. COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN
 BUILDINGS OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
  
 1.1 FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
 UPDATE PLANS TO FIRE RETARDANT TREATED PLYWOOD.
  
 31B) COMPLIED. SEE A-300 SERIES SHEETS AND SHOW
 COMPLIANCE WITH 2010 FBC-B 1406.2.4 FIREBLOCKING. WHERE
 THE COMBUSTIBLE EXTERIOR WALL COVERING IS FURRED FROM
 THE WALL AND FORMS A SOLID SURFACE, THE DISTANCE
 BETWEEN THE BACK OF THE COVERING AND THE WALL SHALL NOT
 EXCEED 15/8 INCHES (41 MM). WHERE REQUIRED BY SECTION
 717, THE SPACE THEREBY CREATED SHALL BE FIREBLOCKED.
 ALSO SEE 717.2.6 AND EXCEPTIONS.
  
 32) (3) COPIES OF EFIS FL 2030.0/ FL 2030.11 & NOA
 12-0628.11 WERE SUBMITTED BUT NO SHOP DRAWING STAMP OF
 APPROVAL FROM THE DESIGN PROFESSIONAL EITHER PUBLIX
 ARCHITECT OR MCG ARCHITECTURE. THE A-300 SERIES SHEETS
 SHOW THE USE OF EFIS SYSTEM, PLEASE SHOW COMPLIANCE
 WITH:
 2010 FBC-B 408.1 GENERAL.
 THE PROVISIONS OF THIS SECTION SHALL GOVERN THE
 MATERIALS, CONSTRUCTION AND QUALITY OF EXTERIOR
 INSULATION AND FINISH SYSTEMS (EIFS) FOR USE AS
 EXTERIOR WALL COVERINGS IN ADDITION TO OTHER APPLICABLE
 REQUIREMENTS OF CHAPTERS 7, 14, 16, 17 AND 26.
 1408.2 PERFORMANCE CHARACTERISTICS.
 EIFS SHALL BE CONSTRUCTED SUCH THAT IT MEETS THE
 PERFORMANCE CHARACTERISTICS REQUIRED IN ASTM E 2568.
 1408.3 STRUCTURAL DESIGN.
 THE UNDERLYING STRUCTURAL FRAMING AND SUBSTRATE SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST LOADS AS REQUIRED
 BY CHAPTER 16.
 1408.4 WEATHER RESISTANCE.
 EIFS SHALL COMPLY WITH SECTION 1403 AND SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST WIND AND RAIN IN
 ACCORDANCE WITH THIS SECTION AND THE MA
 1408.4.1 EIFS WITH DRAINAGE.
 EIFS WITH DRAINAGE SHALL HAVE AN AVERAGE MINIMUM
 DRAINAGE EFFICIENCY OF 90 PERCENT WHEN TESTED IN
 ACCORDANCE THE REQUIREMENTS OF ASTM E 2273 AND IS
 REQUIRED ON FRAMED WALLS OF TYPE V CONSTRUCTION, GROUP
 R1, R2, R3 AND R4 OCCUPANCIES.
 1408.4.1.1 WATER-RESISTIVE BARRIER.
 FOR EIFS WITH DRAINAGE, THE WATER-RESISTIVE BARRIER
 SHALL COMPLY WITH SECTION 1404.2 OR ASTM E 2570.
 1408.5 INSTALLATION.
 INSTALLATION OF THE EIFS AND EIFS WITH DRAINAGE SHALL
 BE IN ACCORDANCE WITH THE EIFS MANUFACTURER?S
 INSTRUCTIONS.
  
 33) 2ND REQUEST, SEMI COMPLIED. SHEET S001HAS
 COMPONENTS & CLADDING IN ZONES 1-5. SHEET S001
 INDICATES THE DESIGN PRESSURES WERE TAKEN AT 38'.
 33A) ROOF ZONES 1 & 2 PRESSURES ARE GOOD
 33B) ROOF ZONE # 3 IT APPEARS THE DESIGNER OF RECORD IS
 TAKING CREDIT FOR A 3'-0" PARPET. SHEET A-303 DETAIL #
 2 PROVIDES A DETAIL OF THIS AREA BUT NEITHER THE BOTTOM
 OF THE BAR JOIST BEARING HEIGHT IS GIVEN NOR IS THE
 FINISH ROOF HEIGHT NOT THE FINISH PARAPET HEIGHT GIVEN.
 33C) WALL ZONES 4 & 5 THE PRESSURES ARE LOW LESS THAN
 IF TAKEN AT 25' ABOVE GRADE FOR AN EXPOSURE C.
  
 34) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 35) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2014-09-30 Time 06:59 Sent To  
Notes
2014-09-30 11:21:01BUILDING PLAN REVIEW
 PERMIT: 14090659
 ADD: 500 BELVEDERE RD
 CONT: TBD
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 30/ 2014
 ACTION: DENIED
  
 NOTE! PLANS INDICATE THEY ARE ONLY 50% COMPLETE. A
 THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 1) THE PLANS SUBMITED SHOW TWO DIFFERENT SETS OF PLANS
 ,ONE HAS THE HEADING OF SUPPLEMENTAL DRAWINGS, BUT THEY
 ARE FROM A DIFFERENT ACHITECT, AND FIRM. PLEASE PROVIDE
 COMPLIANCE WITH FL. ADMINISTRATIVE CODE, 61G1-23.015
 RESPONSIBLE SUPERVISING CONTROL OVER ARCHITECTURAL
 PRACTICE OUTSIDE OF THE ARCHITECT'S OFFICE.
  
  
  
 2A) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY.
 THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR FOR:
 BUILDING TYPE II CONSTRUCTION
 FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE FOOT
 FOR ALL MAJOR STRUCTURAL ALTERATIONS
  
 SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES
 WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE
 BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED
 ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER
 CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH
 INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS
 INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
  
 2B) 110.4 INSPECTION AGENCIES. THE BUILDING OFFICIAL IS
 AUTHORIZED TO ACCEPT REPORTS OF APPROVED INSPECTION
 AGENCIES, PROVIDED SUCH AGENCIES SATISFY THE
 REQUIREMENTS AS TO QUALIFICATIONS AND RELIABILITY.
  
 2C) FBC* 110.3.9 RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD, MANAGER OF
 THE RESIDENT INSPECTOR PROGRAM. KEN CONRAD CONTACT
 INFORMATION:
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2D) SINCE THIS PROJECT WILL BE PART OF THE RESIDENT
 INSPECTOR PROGRAM A THIRD SET OF ALL PLANS AND
 SUPPORTING DOCUMENTS (ENERGY CALCULATIONS, SOILS
 REPORTS, PRODUCT APPROVALS ETC, WILL BE REQUIRED.
 107.3.1.
  
 NOTE, FORMS WERE E-MAILED TO :
 [email protected]
  
 3) MISSING SOILS REPORTS, 2010 FBC-B 1803.5.2
 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, STRENGTH
 OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR WHERE A
 LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 4) SUBMIT (3) COPIES. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES INCLUDING ROOFTOP
 INSULATION
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS, A/C ROOF CURBS AND ADAPTORS
  
 5) THE COVER SHEET LIST PRODUCT APPROVALS REQUIRED BY
 THE DESIGNER OF RECORD, ALL LISTED ARE FLORIDA
 APPROVALS ONLY, NONE OF THE PRODUCTS HAVE BEEN REVIEWED
 BY THE DESIGNER OF RECORD . 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) THE ROOFING REPORT SUBMITTED FL 5680-R9, LISTED IN
 THE DESIGNER OF ECORDS LIST IS THE MOST CURRENT REPORT
 FL 5680-R10.
  
 7) MIAMI-DADE NOA 140626.02 CARLISLE SURE WELD NOT ON
 THE DESINER OF RECODS LIST.
  
 8) FL 11537-R4 DOOR NOT IDENTIFIED NOR PRESSURES, ONLY
 ONE COPY SUBMITTED. MISSING INSTALATION INSTRUCTIONS.
  
 9) SUBMITTED FL 11749-R2 DESIGNER OF RECORD REQUESTED
 FL 14636-R3.
  
 10) SUBMITTED FL 13533-R4 UPDATE TO THE CURRENT FL
 13533-R5.
  
 11) SUBMITTED DRYVIT SYSTEMS 11-1108.02 & 12-0703.03
 MIAMI-DADE NOA, NOT ON LIST, NEVER REVIEWED.
  
 12) SUBMITTED 1 COPY OF FL 15110.1 MIAMI-DADE NOA
 IDENTIFY IF INSTALATION IS A "S" OR "NB" DOOR.
  
 13) NO WINDOW REPORTS, WALL LOUVERS AND PRE-ENGINEERED
 A/C STANDS WERE SUBMITTED.
  
 14)(A) THERE ARE DISCREPANCIES IN THE LS-1 EGRESS DOOR
 IDENTIFICATION PLAN VERSES THE CHART AT THE BOTTOM OF
 THE PAGE. DISCREPANCY DOORS ON THE PLANS 22 & 18 ARE
 NOT ON THE CHART AND ON THE CHART DOORS 21 & 19 ARE NOT
 ON THE PLAN.
  
 14)(B) DOOR # 17,18 & 19 ARE NOT ON THE CHART NOR IS
 DOOR OPENING TO THE LEFT IN THE VESTIBULE BETWEEN DOORS
 3 & 90, ARROWS SHOWING AN EGRESS PATH AND A EXIT SIGN
 SHOWN, NO DOOR IS IDENTIFIED. THE DOORS CAN NOT BE
 IDENTIFIED ON SHEET A5 SINCE THE STAPLES THAT BIND THE
 PLANS TOGETHER ARE OVER THE IDENTIFYING DOOR NUMBERS.
  
 14C) SHEET A-5 THE DOOR SCHEDULE IS IN THE UPPER LEFT
 HAND CORNER SO FAR THE STAPLES WILL NOT LET YOU
 IDENTIFY THE DOOR. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 14D) DOOR # 3 APPEARS TO BE (2) 48 INCH SWING DOORS.
 BOTH DOORS ARE MISSING THE 18" CLEARANCE FOR
 MANEUVERING CLEARANCES 2010 FL ACC CODE TABLE
 404.2.4.1.
  
 14E) PLEASE PROVIDE A SURVEY OR SITE PLAN, THE ISSUE IS
 IS THERE A PROPERTY LINE BETWEEN PUBLIX AND THE OTHER
 STORES, OR SITE PROPERTY LINE. THE DESIGN TEAM IS
 TAKING AN EXECPTION TO UNLIMITED AREA UNDER 507.4.
 507.5 REQUIRES 3 HR WALLS FOR WALLS WITH ONLY 40'-0"
 CLEAR.
  
 15) SHEET LS-1 VESTIBULE POSSIBLY 2 ELECTRIC CARTS ARE
 IN THE EGRESS PATH.
 2010 FBC-B 1003.3.3 HORIZONTAL PROJECTIONS. STRUCTURAL
 ELEMENTS, FIXTURES OR FURNISHINGS SHALL NOT PROJECT
 HORIZONTALLY FROM EITHER SIDE MORE THAN 4 INCHES (102
 MM) OVER ANY WALKING SURFACE BETWEEN THE HEIGHTS OF 27
 INCHES (686 MM) AND 80 INCHES (2032 MM) ABOVE THE
 WALKING SURFACE.
 2010 FBC-B 1003.3.4 CLEAR WIDTH. PROTRUDING OBJECTS
 SHALL NOT REDUCE THE MINIMUM CLEAR WIDTH OF ACCESSIBLE
 ROUTES.
  
 16) LS1 BETWEEN GRID LINE 1 & 2 THERE APPEARS TO BE AN
 EXIT WAY FROM THE FRONT OF THE BUILDING BUT IT STOPS
 MIDWAY THROUGH THE BUILDING. THEN AT THE REAR CORNER OF
 THE BUILDING THERE IS DOOR 25, IS THIS EXIT IN THE SAME
 CORRIDOR OR IS THE REAR OF THE NEXT BUILDING IN FRONT
 OF THE DOOR? PLEASE PROVIDE WHERE THIS CORRIDOR ENDS?
 1027.2 EXIT DISCHARGE CAPACITY/ 1027.3 EXIT DISCHARGE
 LOCATION.
  
 17) SHEET A-1 ALL EXTERIOR 12" BLOCK WALLS SHOW THEY
 ARE FOAM FILED, PLEASE PROVIDE PRODUCT INFORMATION FOR
 FOAM INSULATION. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 18A) SHEET A-1 DESIGN PRESSURES ARE IN V-ULT, THEY DO
 NOT PROVIDE THE WIND DESIGN CRITERIA. 2010 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 18B) PLEASE ALSO PROVIDE THE VASD PRESSURES SINCE ALL
 THE PRODUCT APPROVALS ARE IN VASD. 1609.3.1.
  
 18C) THE ROOF ZONES NOT IDENTIFIED NOR THE PRESSURES
 FOR THE ROOF ZONE.
  
 19) SHEET A-2. DOORS 30 & 42 CAN NOT VERIFY THEIR FIRE
 RATING SINCE SHEET A5 THE NUMBER COLUMN IDENTIFYING THE
 DOORS IS STAPLED CAN NOT BE VIEWED UNDER THIS REVIEW.
 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 20A) SHEET A-2 NOTE BOTTOM OF SHEET INDICATES TYPE 1 &
 2 WALLS IN THE SEAFOOD & MEAT DEPARTMENT ARE TO BE
 FILED WITH CLOSED CELL SPRAY FOAM POLYURETHANE OR
 ICYENE INSULATION. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B 2603.4.1.2 (1-4) PROVIDE DOCUMENTATION.
  
 20B) SHEET A-2 NOTE BOTTOM OF SHEET INDICATES TYPE 1 &
 2 WALLS IN THE SEAFOOD & MEAT DEPARTMENT ARE TO BE
 FILED WITH CLOSED CELL SPRAY FOAM POLYURETHANE OR
 ICYENE INSULATION. THE USE OF "OR" THE DESIGNER OF
 RECORD MUST DECIDE WHICH SYSTEM WILL BE INSTALLED.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH
 DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION,
 IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 21) SHEET A-9 GRAB BAR HEIGHTS ARE NOT PROVIDED,
 PROVIDE COMPLIANCE WITH 2010 FBC- ACCESSIBILITY CODE
 609.4. POSITION OF GRAB BARS.
  
 22) SHEET A-17 SECTION THROUGH PHARMACY SHOWS AN
 OPTIONAL DRIVE-THRU WINDOW. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 23) SHEET A-17 SECTIONS THROUGH PHARMACY SHOW GYPSUM
 BOARD SUSPENSION SYSTEM CEILING, THE PLANS DO NOT
 INDICATE HOW THE SYSTEM IS TO BE SUSPENDED, ONLY THAT
 THE 1 1/2" C CHANNEL IS TO OCCUR AT 48 INCHES O.C.?
 PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 2508.1
 GENERAL.
 GYPSUM BOARD AND GYPSUM PLASTER CONSTRUCTION SHALL BE
 OF THE MATERIALS LISTED IN TABLES 2506.2 AND 2507.2.
 THESE MATERIALS SHALL BE ASSEMBLED AND INSTALLED IN
 COMPLIANCE WITH THE APPROPRIATE STANDARDS LISTED IN
 TABLES 2508.1 AND 2511.1.1, AND CHAPTER 35.
  
 24) ADA-2 ATM MACHINES PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATIONS FOR FASTENING THE ATM MACHINE AND
 ANCHORING IT TO EITHER THE FLOOR OR WALL SYSTEM.
 107.2.1.3. ADDITIONAL INFORMATION IS REQUIRED.
  
 25A) ADA-2 ATM MACHINES PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-ACCESS. CODE 707.2 CLEAR FLOOR OR GROUND
 SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 25B) 07.5 SPEECH OUTPUT. MACHINES SHALL BE SPEECH
 ENABLED. OPERATING INSTRUCTIONS AND ORIENTATION,
 VISIBLE TRANSACTION PROMPTS, USER INPUT VERIFICATION,
 ERROR MESSAGES, AND ALL DISPLAYED INFORMATION FOR FULL
 USE SHALL BE ACCESSIBLE TO AND INDEPENDENTLY USABLE BY
 INDIVIDUALS WITH VISION IMPAIRMENTS. SPEECH SHALL BE
 DELIVERED THROUGH A MECHANISM THAT IS READILY AVAILABLE
 TO ALL USERS, INCLUDING BUT NOT LIMITED TO, AN INDUSTRY
 STANDARD CONNECTOR OR A TELEPHONE HANDSET. SPEECH SHALL
 BE RECORDED OR DIGITIZED HUMAN, OR SYNTHESIZED.
  
 25C) 707.6.1 INPUT CONTROLS. AT LEAST ONE TACTILELY
 DISCERNIBLE INPUT CONTROL SHALL BE PROVIDED FOR EACH
 FUNCTION. WHERE PROVIDED, KEY SURFACES NOT ON ACTIVE
 AREAS OF DISPLAY SCREENS, SHALL BE RAISED ABOVE
 SURROUNDING SURFACES. WHERE MEMBRANE KEYS ARE THE ONLY
 METHOD OF INPUT, EACH SHALL BE TACTILELY DISCERNABLE
 FROM SURROUNDING SURFACES AND ADJACENT KEYS.
  
 25D) 707.6.2 NUMERIC KEYS. NUMERIC KEYS SHALL BE
 ARRANGED IN A 12-KEY ASCENDING OR DESCENDING TELEPHONE
 KEYPAD LAYOUT. THE NUMBER FIVE KEY SHALL BE TACTILELY
 DISTINCT FROM THE OTHER KEYS.
  
 26A) SHEET RD-1 DETAIL (1) SCUPPERS AND OVERFLOW
 SCUPPERS PLEASE PROVIDE SIZING CALCULATIONS FOR BOTH
 THE SCUPPERS AND OVERFLOW SHALL COMPLY WITH SECTION
 1503 AND THE FLORIDA BUILDING CODE, PLUMBING, CHAPTER
 11.
  
 26B) SHEET RD-1 DETAIL (1) SCUPPERS AND OVERFLOW
 SCUPPERS PLEASE PROVIDE COMPLIANCE 1503.7 PROTECTION
 AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 26C) SHEET RD-1 DETAIL (13) & SHEET S-4 DETAIL (2) A
 PITCH PAN DETAIL, PLEASE NOTE FOR A/C ROOFTOP
 COMPRESSORS PITCH PANS CAN NOT BE USED, COMPLIANCE WITH
 1509.7 MECHANICAL UNITS. ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES
 (203 MM) ABOVE THE ROOF SURFACE (FINISH SURFACE, ALLOW
 FOR ROOF TOP INSULATION, AND UNIT OVER HANG OF CURB),
 OR WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON
 RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM CLEARANCE
 HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
  
  
 26D) SHEET RD-1 DETAIL (7) DOCK CANOPY GUTTER DETAIL
 PLEASE PROVIDE THE SIZING OF THE GUTTER AND THE TYPE OF
 FASTENERS FOR THE WEIGHT OF GUTTER AND RAINWATER RUN
 OFF. 107.2.4 EXTERIOR WALL ENVELOPE. CONSTRUCTION
 DOCUMENTS FOR ALL BUILDINGS SHALL DESCRIBE THE EXTERIOR
 WALL ENVELOPE IN SUFFICIENT DETAIL TO DETERMINE
 COMPLIANCE WITH THIS CODE. THE CONSTRUCTION DOCUMENTS
 SHALL PROVIDE DETAILS OF THE EXTERIOR WALL ENVELOPE AS
 REQUIRED, INCLUDING FLASHING, INTERSECTIONS WITH
 DISSIMILAR MATERIALS, CORNERS, END DETAILS, CONTROL
 JOINTS, INTERSECTIONS AT ROOF, EAVES OR PARAPETS, MEANS
 OF DRAINAGE, WATER-RESISTIVE MEMBRANE AND DETAILS
 AROUND OPENINGS.
  
  
 27) SHEET RD-2 DETAIL # 3 ROOR TOP INSULATION DETAIL,
 DETAIL <37.5 PLEASE ELIMINATE THE MEN ROOF IS ABOVE 30
 FEET WITH THE TOP PORTION OF THE ROOF AT 31'-4" AND THE
 TOP OF THE PARAPET AT 34'-0" THIS IS LESS THAN 3'-0"
 AND CREATES CORNER ZONES. THE PLANS WILL NEED TO SHOW
 INSULATION FASTENING FOR FULL SHEETS AND HALF SHEETS
 FOR ZONES 1, 2 & 3 WITH THE ASSOCIATED PRESSURES FOR
 BOTH FULL SHEETS AND HALF SHEETS.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 107.2.1.2 FOR
 ROOF ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 28) SHEET S-4 BAR JOIST SPACING. NOTE DEPENDING ON THE
 ROOFING PRODUCT APPROVAL, SPACING OF BAR JOIST AND OR
 THE THICKNESS OF THE STEEL DECK MAY BE A ISSUE ONCE THE
 ROOFING APPROVAL HAS BEEN SUBMITTED. 107.2.1.2 FOR ROOF
 ASSEMBLIES REQUIRED BY THE CODE, THE CONSTRUCTION
 DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND DELINEATE THE
 TYPE OF ROOFING SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 *******************************************************
 *******************************************************
 *********************************************
  
 ARCHITECTURAL PLANS SUBMITTED SUPPLEMENTAL DOCUMENTS BY
 MCG ARCHITECTURE
  
 29) ATAS WIND LOCK SUFFIT PANELS WILL REQUIRE A PRODUCT
 APPROVAL: 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, SOFFITS, EFIS SYSTEMS,
  
 30) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 (DESIGNER OF RECORD) PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 31) SHEET A201 AND 300 SERIES SHEETS INDICATE THE USE
 OF 5/8 INCH EXTERIOR GRADE PLYWOOD AS BACKING
 (SHEATHING) PLEASE SEE THE BUILDING IS DECLARED A TYPE
 IIB BUILDING. 03.1 ALLOWABLE MATERIALS. COMBUSTIBLE
 MATERIALS SHALL BE PERMITTED IN BUILDINGS OF TYPE I OR
 II CONSTRUCTION IN THE FOLLOWING APPLICATIONS AND IN
 ACCORDANCE WITH SECTIONS 603.1.1 THROUGH 603.1.3:
  
 1.1 FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
 UPDATE PLANS TO FIRE RETARDANT TREATED PLYWOOD.
  
 31) SEE A-300 SERIES SHEETS AND SHOW COMPLIANCE WITH
 2010 FBC-B 1406.2.4 FIREBLOCKING. WHERE THE COMBUSTIBLE
 EXTERIOR WALL COVERING IS FURRED FROM THE WALL AND
 FORMS A SOLID SURFACE, THE DISTANCE BETWEEN THE BACK OF
 THE COVERING AND THE WALL SHALL NOT EXCEED 15/8 INCHES
 (41 MM). WHERE REQUIRED BY SECTION 717, THE SPACE
 THEREBY CREATED SHALL BE FIREBLOCKED. ALSO SEE 717.2.6
 AND EXCEPTIONS.
  
 32) THE A-300 SERIES SHEETS SHOW THE USE OF EFIS
 SYSTEM, PLEASE SHOW COMPLIANCE WITH:
 2010 FBC-B 408.1 GENERAL.
 THE PROVISIONS OF THIS SECTION SHALL GOVERN THE
 MATERIALS, CONSTRUCTION AND QUALITY OF EXTERIOR
 INSULATION AND FINISH SYSTEMS (EIFS) FOR USE AS
 EXTERIOR WALL COVERINGS IN ADDITION TO OTHER APPLICABLE
 REQUIREMENTS OF CHAPTERS 7, 14, 16, 17 AND 26.
 1408.2 PERFORMANCE CHARACTERISTICS.
 EIFS SHALL BE CONSTRUCTED SUCH THAT IT MEETS THE
 PERFORMANCE CHARACTERISTICS REQUIRED IN ASTM E 2568.
 1408.3 STRUCTURAL DESIGN.
 THE UNDERLYING STRUCTURAL FRAMING AND SUBSTRATE SHALL
 BE DESIGNED AND CONSTRUCTED TO RESIST LOADS AS REQUIRED
 BY CHAPTER 16.
 1408.4 WEATHER RESISTANCE.
 EIFS SHALL COMPLY WITH SECTION 1403 AND SHALL BE
 DESIGNED AND CONSTRUCTED TO RESIST WIND AND RAIN IN
 ACCORDANCE WITH THIS SECTION AND THE MA
 1408.4.1 EIFS WITH DRAINAGE.
 EIFS WITH DRAINAGE SHALL HAVE AN AVERAGE MINIMUM
 DRAINAGE EFFICIENCY OF 90 PERCENT WHEN TESTED IN
 ACCORDANCE THE REQUIREMENTS OF ASTM E 2273 AND IS
 REQUIRED ON FRAMED WALLS OF TYPE V CONSTRUCTION, GROUP
 R1, R2, R3 AND R4 OCCUPANCIES.
 1408.4.1.1 WATER-RESISTIVE BARRIER.
 FOR EIFS WITH DRAINAGE, THE WATER-RESISTIVE BARRIER
 SHALL COMPLY WITH SECTION 1404.2 OR ASTM E 2570.
 1408.5 INSTALLATION.
 INSTALLATION OF THE EIFS AND EIFS WITH DRAINAGE SHALL
 BE IN ACCORDANCE WITH THE EIFS MANUFACTURER?S
 INSTRUCTIONS.
  
 33) SHEET S001HAS COMPONENTS & CLADDING THAT ARE
 DIFFERENT FROM THOUGHS FOUND ON SHEET A-1 WHICH
 PRESSURES ARE TTO BE USED FORTHIS PROJECT? DISCREPANCY.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 34) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 35) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-01-29 Cont ID  
Sent By rlecky Date 2015-01-29 Time 11:49 Rev Time 0.00
Received By rlecky Date 2015-01-29 Time 10:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-01-06 Cont ID  
Sent By rlecky Date 2015-01-06 Time 13:04 Rev Time 0.00
Received By rlecky Date 2015-01-06 Time 11:23 Sent To  
Notes
2014-12-04 14:02:45NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-09 Cont ID  
Sent By rlecky Date 2014-10-09 Time 13:49 Rev Time 0.00
Received By rlecky Date 2014-10-09 Time 10:07 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2015-02-10 Cont ID  
Sent By cranford Date 2015-02-10 Time 15:31 Rev Time 0.00
Received By cranford Date 2015-02-10 Time 15:31 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2014-12-15 Cont ID  
Sent By cranford Date 2014-12-15 Time 15:09 Rev Time 0.00
Received By cranford Date 2014-12-15 Time 14:49 Sent To Z
Notes
2014-12-15 15:08:58ALSO REVIEWED UNDER ENGINEERING DEVELOPMENT APPROVAL
 E14060020

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2014-10-03 Cont ID  
Sent By cranford Date 2014-10-03 Time 09:29 Rev Time 0.00
Received By cranford Date 2014-10-02 Time 14:19 Sent To P
Notes
2014-10-03 09:32:56DEMONSTRATE THAT THE STORMWATER MANAGEMENT SYSTEM HAS
 BEEN DESIGN TO INCLUDE THE VELOCITY AND DURATION OF THE
 DISCHARGE FROM THE ROOF DRAINS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-02-11 Cont ID  
Sent By pleduc Date 2015-02-11 Time   Rev Time 0.00
Received By pleduc Date 2015-02-11 Time 15:56 Sent To  
Notes
2015-02-11 16:07:25THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 SHEET'S LS - 1 AND A - 1, COMPLIED
  
 ADDITIONAL: THE DOOR SCHEDULE ONLY LISTS THE FRONT EXIT
 DOOR AS BEING 12' WIDE, NO CLEAR OPENING DIMENSION IS
 INDICATED TO VERIFY THE EXIT CAPACITY.
 ONE ONE SHEET THERE ARE FOUR DOOR AND FOUR EXIT ARROWS
 SHOWING FROM THE FRONT FOYER AREA. ANOTHER SHEET SHEET
 SHOWS TWO. THE FOYER EXIT DESIGN IS NOT CONSISTENT
 AND NEEDS CORRECTION. REMAINS- PROVISO: WILL ADDRESS
 DURING CONSTRUCTION.
  
 SHEET'S LS - 1 AND A - 1, DOORS 16, 18, AND 22 ARE
 INDICATED AS EXITS. APPEARS TO BE COMPLIED; HOWEVER,
 PROVISO: WILL ADDRESS DURING CONSTRUCTION.
  
 ADDITIONAL : THE SUBMITTAL CONTINUES TO SHOW A FENCED
 IN AREA IN THE REAR OF THE BUILDING THAT THESE THREE
 EXIT DOORS OPEN UP TO. THERE DOES NOT SEEM TO BE AN
 EXIT OUT OF THIS
 FENCED IN AREA. IF THERE IS NO CLEAR EXIT FROM THIS
 AREA , THESE THREE DOORS CAN NOT BE USED AS EXIT DOORS
 AND YOUR EXIT CALCULATIONS NEED TO BE CORRECTED.
 APPEARS TO BE COMPLIED; HOWEVER, PROVISO : WILL ADDRESS
 DURING CONSTRUCTION.
  
 SHEET A - 5, THE DOOR SCHEDULE IS STAPLED IN SUCH A WAY
 THAT IT IS UNREADABLE AND DOORS CAN NOT BE LOCATED OR
 VERIFIED. COMPLIED
  
 ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND
 HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN
 THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS
 CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR
 TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL
 BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR
 SCHEDULE. PROVISO: WILL ADDRESS DURING CONSTRUCTION.
  
 EMERGENCY LIGHTING IS NOT PROVIDED FOR OR INDICATED.
 COMPLIED
  
  
 ADDITIONAL EXIT SIGNS SHALL BE PLACED AT THE END OF
 MAIN ISLES AND AT THE OPPOSITE CORNERS OF THE MAIN
 SHOPPING AREA. (NOTE THE LOCATIONS ON SHEET LS - 1)
 ADDITIONAL SIGNS MAY BE ADDED IF OBSTRUCTED BY LINE OF
 SITE ISSUES DURING INSPECTIONS. PROVISO: WILL ADDRESS
 ANY ADDITIONAL NEEDED EXIT SIGNS DURING CONSTRUCTION.
  
 THE PROPOSED GENERATOR SHALL MEET THE REQUIREMENTS OF
 NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS. THE GENERATOR SHALL BE PROTECTED FROM DAMAGE
 BY VEHICLE TRAFFIC. COMPLIED
  
 A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING
 FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN
 EMERGENCY AT ANY TIME. COMPLIED
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR. PROVISO: WILL ADDRESS DURING CONSTRUCTION.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL. COMPLIED
  
 A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE. COMPLIED
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-12-05 Cont ID  
Sent By pleduc Date 2014-12-05 Time   Rev Time 0.00
Received By pleduc Date 2014-12-05 Time 11:43 Sent To  
Notes
2014-12-18 11:06:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE FOLLOWING PREVIOUS COMMENTS DID NOT APPEAR TO BE
 ADDRESSED IN THIS RESUBMITTAL WITH ADDITIONAL
 INFORMATION.
  
  
 SHEET'S LS - 1 AND A - 1, THE FRONT DOOR DIMENSIONS
 COULD NOT BE VERIFIED TO ACCOUNT FOR THE OCCUPANCY EXIT
 LOADS. IT APPEARS THAT 1/2 OF THE OCCUPANY CAN NOT EXIT
 THROUGH THE FRONT DOORS. PLEASE PROVIDE GREATER DETAIL
 OF THE OPENING DIMENSIONS AND CALCULATIONS.
  
 ADDITIONAL: THE DOOR SCHEDULE ONLY LISTS THE FRONT EXIT
 DOOR AS BEING 12' WIDE, NO CLEAR OPENING DIMENSION IS
 INDICATED TO VERIFY THE EXIT CAPACITY.
 ONE ONE SHEET THERE ARE FOUR DOOR AND FOUR EXIT ARROWS
 SHOWING FROM THE FRONT FOYER AREA. ANOTHER SHEET SHEET
 SHOWS TWO. THE FOYER EXIT DESIGN IS NOT CONSISTENT
 AND NEEDS CORRECTION.
  
 SHEET'S LS - 1 AND A - 1, DOORS 16, 18, AND 22 ARE
 INDICATED AS EXITS. THERE APPEARS TO BE A CHAIN LINK
 FENCE AREA THAT THESE DOORS EXIT DISCHARGE TO. THE EXIT
 DISCHARGE SHALL BE TO A UNOBSTRUCTED PUBLIC WAY.
  
 ADDITIONAL : THE SUBMITTAL CONTINUES TO SHOW A FENCED
 IN AREA IN THE REAR OF THE BUILDING THAT THESE THREE
 EXIT DOORS OPEN UP TO. THERE DOES NOT SEEM TO BE AN
 EXIT OUT OF THIS
 FENCED IN AREA. IF THERE IS NO CLEAR EXIT FROM THIS
 AREA , THESE THREE DOORS CAN NOT BE USED AS EXIT DOORS
 AND YOUR EXIT CALCULATIONS NEED TO BE CORRECTED.
  
 SHEET A - 5, THE DOOR SCHEDULE IS STAPLED IN SUCH A WAY
 THAT IT IS UNREADABLE AND DOORS CAN NOT BE LOCATED OR
 VERIFIED.
  
 ADDITIONAL : THE STAPLES MUST BE MOVED TO ALLOW FOR
 EASY VIEWING OF ALL DRAWINGS AND TABLES.
  
 ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND
 HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN
 THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS
 CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR
 TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL
 BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR
 SCHEDULE.
  
 EMERGENCY LIGHTING IS NOT PROVIDED FOR OR INDICATED.
  
 ADDITIONAL : A STATEMENT, NOTE OR SYMBOL REGARDING
 EMERGENCY LIGHTING SHALL BE INDICATED ON THE LIFE
 SAFETY AND ELECTRICAL PLAN.
  
 ADDITIONAL EXIT SIGNS SHALL BE PLACED AT THE END OF
 MAIN ISLES AND AT THE OPPOSITE CORNERS OF THE MAIN
 SHOPPING AREA. (NOTE THE LOCATIONS ON SHEET LS - 1)
 ADDITIONAL SIGNS MAY BE ADDED IF OBSTRUCTED BY LINE OF
 SITE ISSUES DURING INSPECTIONS.
  
 ADDITIONAL : ANY PERSON STANDING ON ANY MAIN ISLE SHALL
 BE ABLE TO SEE AN EMERGENCY LIGHT.
  
 THE PROPOSED GENERATOR SHALL MEET THE REQUIREMENTS OF
 NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS. THE GENERATOR SHALL BE PROTECTED FROM DAMAGE
 BY VEHICLE TRAFFIC.
  
 ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE
 APPROPRIATE.
  
 THE ELEVATOR SHALL CONFORM TO THE REQUIREMENTS TO THE
 FIREFIGHTERS EMERGENCY OPERATIONS AND ACCOMODATE THE
 EMS STANDARDS FOR STRETCHER DIMENSIONS.
  
 ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE
 APPROPRIATE.
  
 A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING
 FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN
 EMERGENCY AT ANY TIME.
  
 ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE
 APPROPRIATE.
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE
 APPROPRIATE.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE
 APPROPRIATE.
  
 A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE.
  
 ADDITIONAL : PROVIDE STATEMENT OR NOTE WHERE
 APPROPRIATE.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-10-23 Cont ID  
Sent By pleduc Date 2014-10-23 Time   Rev Time 0.00
Received By pleduc Date 2014-10-20 Time 14:26 Sent To PC
Notes
2014-10-21 17:06:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 SHEET'S LS - 1 AND A - 1, THE FRONT DOOR DIMENSIONS
 COULD NOT BE VERIFIED TO ACCOUNT FOR THE OCCUPANCY EXIT
 LOADS. IT APPEARS THAT 1/2 OF THE OCCUPANY CAN NOT EXIT
 THROUGH THE FRONT DOORS. PLEASE PROVIDE GREATER DETAIL
 OF THE OPENING DIMENSIONS AND CALCULATIONS.
  
 SHEET'S LS - 1 AND A - 1, DOORS 16, 18, AND 16 ARE
 INDICATED AS EXITS. THERE APPEARS TO BE A CHAIN LINK
 FENCE AREA THAT THESE DOORS EXIT DISCHARGE TO. THE EXIT
 DISCHARGE SHALL BE TO A UNOBSTRUCTED PUBLIC WAY.
  
 SHEET A - 5, THE DOOR SCHEDULE IS STAPLED IN SUCH A WAY
 THAT IT IS UNREADABLE AND DOORS CAN NOT BE LOCATED OR
 VERIFIED.
  
 ALL FIRE RATED OPENING PROTECTIONS (FIRE DOORS AND
 HARDWARE) SHALL BE CLEARLY IDENTIFIED AND INDICATED IN
 THE DOOR SCHEDULE. ALL DOORS THAT OPEN ONTO EXIT ACCESS
 CORRIDORS SHALL BE AT LEAST 20 MINUTE FIRE RATED AND BE
 EQUIPPED WITH SELF-CLOSING DEVICES THAT CAUSE THE DOOR
 TO POSITIVELY LATCH WHEN CLOSED. THIS REQUIREMENT SHALL
 BE CLEARLY INDICATED AND ILLUSTRATED ON THE DOOR
 SCHEDULE.
  
 EMERGENCY LIGHTING IS NOT PROVIDED FOR OR INDICATED.
  
 ADDITIONAL EXIT SIGNS SHALL BE PLACED AT THE END OF
 MAIN ISLES AND AT THE OPPOSITE CORNERS OF THE MAIN
 SHOPPING AREA. (NOTE THE LOCATIONS ON SHEET LS - 1)
 ADDITIONAL SIGNS MAY BE ADDED IF OBSTRUCTED BY LINE OF
 SITE ISSUES DURING INSPECTIONS.
  
 THE PROPOSED GENERATOR SHALL MEET THE REQUIREMENTS OF
 NFPA 110, STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS. THE GENERATOR SHALL BE PROTECTED FROM DAMAGE
 BY VEHICLE TRAFFIC.
  
 THE LOCATIONS OF THE COMPACTOR AND THE GENERATOR AND
 ANY OTHER STRUCTURE OF OBJECT SHALL NOT ENCROACH ON THE
 REQUIRED 20' FIRE LANE ALONG ALL SIDES OF THE BUILDING.
 THE FIRE LANE SHALL BE INDICATED BY FIRE LANE MARKING
 TO INCLUDE PAINT AND SIGNAGE.
  
 THE ELEVATOR SHALL CONFORM TO THE REQUIREMENTS TO THE
 FIREFIGHTERS EMERGENCY OPERATIONS AND ACCOMODATE THE
 EMS STANDARDS FOR STRETCHER DIMENSIONS.
  
 ALL FIRE DEPARTMENT SPRINKLER SYSTEM CONNECTIONS
 (FDC,S) FOR THE PROJECT SHALL BE IDENTIFIED AND
 COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 ALL FIRE WATER MAINS, SIZES AND THEIR VALVE ASSEMBLIES
 SHALL BE CLEARLY IDENTIFIED AND ILLUSTRATED ON THE
 PLAN.
  
 A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING
 FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN
 EMERGENCY AT ANY TIME.
  
 NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR
 ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR
 MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE
 PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY
 DOOR.
  
 ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN. THE FIRE HYDRANT AND FDC'S FOR THIS
 PROJECT SHALL BE CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION. IT WILL RECOMMEND THAT THE PROPOSED
 NEW HYDRANT LOCATIONS BE MOVED CLOSER TO THE BUILDING
 IN AN AGREEABLE LOCATION.
  
 ALL KITCHEN EQUIPMENT AND OPERATIONS SHALL COMPLY WITH
 NFPA 96, STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS.
 EXTINGUISHMENT AND VENTILATION SYSTEM SHOP DRAWINGS
 SHALL BE SUBMITTED SEPARATELY FOR APPROVAL.
  
 A MONITORED FIRE ALARM SYSTEM IS REQUIRED FOR THIS
 STRUCTURE.
  
 SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 TRASH AND DEBRIS IS TO BE REMOVED FROM THE SITE DAILY
 OR MORE OFTEN TO REDUCE THE ACCUMULATION OF POTENTIAL
 LIFE AND FIRE SAFETY HAZARDS.
  
 CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY WITH
 NFPA 241. MUTLTIPLE CONSTRUCTION TRAILERS SHALL COMPLY
 WITH THE REQUIRED SEPARATION DISTANCES OR THEY SHALL BE
 SPRINKLERED.
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-02-03 Cont ID  
Sent By tklarge Date 2015-02-03 Time 07:52 Rev Time 0.00
Received By tklarge Date 2015-02-03 Time 07:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-03-11 Cont ID  
Sent By   Date 2015-03-11 Time   Rev Time 0.00
Received By   Date 2015-03-10 Time   Sent To  
Notes
2015-03-11 16:11:58THE PERMIT IS READY FOR ISSUANCE LOCATED AT J. W. SIDE
 TABLE.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-02-28 Cont ID  
Sent By   Date 2015-02-28 Time   Rev Time 0.00
Received By   Date 2015-02-20 Time   Sent To  
Notes
2015-02-28 08:13:55SENT TO C-27/ C-28

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-02-18 Cont ID  
Sent By hmoser Date 2015-02-18 Time 13:03 Rev Time 0.00
Received By hmoser Date 2015-01-28 Time 12:26 Sent To  
Notes
2015-01-28 12:26:31C27 / C28
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-06 Cont ID  
Sent By rlecky Date 2015-01-06 Time 13:08 Rev Time 0.00
Received By rlecky Date 2014-12-03 Time 13:49 Sent To  
Notes
2014-12-04 13:49:34RE-SUBMITTAL SENT TO C27 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-23 Cont ID  
Sent By pleduc Date 2014-10-23 Time 10:43 Rev Time 0.00
Received By pleduc Date 2014-09-18 Time 07:43 Sent To  
Notes
2014-09-19 07:43:36C25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2015-03-11 Cont ID  
Sent By jwitmer Date 2015-03-11 Time   Rev Time 0.00
Received By jwitmer Date 2015-03-11 Time   Sent To  
Notes
2015-03-11 16:10:523/11/2015 MU 2015-005718-0000 NO IMPACT FEES DUE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-12-24 Cont ID  
Sent By jwitmer Date 2014-12-24 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2014-12-24 Time 08:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-24 Cont ID  
Sent By jwitmer Date 2014-12-24 Time 08:42 Rev Time 0.00
Received By jwitmer Date 2014-12-24 Time 08:42 Sent To  
Notes
2014-12-24 08:43:05BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-02-18 Cont ID  
Sent By hmoser Date 2015-02-18 Time 13:03 Rev Time 0.00
Received By hmoser Date 2015-02-18 Time 09:28 Sent To  
Notes
2015-02-18 13:03:14PASS PROVISO
 1) REFER TO SECTION 301.12 WIND RESISTANCE.
 2010 FBC (M) PROVIDE A DETAIL FROM THE
 ENGINEER ON THE CURB TO ROOF TIEDOWN.
 SIZE AND TYPE OF ANCHORS USED
 2) REFER TO SECTION 503.2.5.4 SHUTOFF
 DAMPER CONTROLS. FOR FRESH AIR
 AND EXHAUST. 2010 FLORIDA ENERGY CODE
 3) HOODS AND COOLERS ARE NOT PART OF THIS REVIEW
 SEPARATE APPLICATION, PLANS AND PERMITS ARE REQUIRED
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-01-03 Cont ID  
Sent By hmoser Date 2015-01-03 Time 09:12 Rev Time 0.00
Received By hmoser Date 2015-01-03 Time 07:02 Sent To  
Notes
2015-01-03 09:12:08PLAN DENIED
 1) MISSING FIRE DAMPER IN ROOM 112 ELEC. EQUIP.
 ROOM . REFER TO SECTION 607.5.3 FBC (M) 2010
 2) PLEASE MARK RATED WALLS ON MECHANICAL PLAN
 PER SECTION 107 FBC 2010
 3) MARK OR NUMBER ROOMS ON MECHANICAL PLAN.
 PER SECTION 107 FBC 2010
 4) REFER TO SECTION 304.11 GUARDS FBC (M) 2010
 5) REFER TO SECTION 1509.7 AND TABLE 1509.7 FBC 2010
 6) HOODS AND COOLERS WILL NOT BE REVIEWED UNDER THIS
 PERMIT NUMBER
 SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
2014-12-04 14:02:25NEW SHEETS SUBMITTED. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-10-08 Cont ID  
Sent By rbergsma Date 2014-10-08 Time   Rev Time 1.50
Received By rbergsma Date 2014-10-08 Time   Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-02-03 Cont ID  
Sent By tklarge Date 2015-02-03 Time 07:52 Rev Time 0.00
Received By tklarge Date 2015-01-31 Time 08:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-12-17 Cont ID  
Sent By tklarge Date 2014-12-17 Time 07:25 Rev Time 0.00
Received By tklarge Date 2014-12-15 Time 14:24 Sent To  
Notes
2014-12-17 06:59:391) PLUMBING PLANS REFER TO CIVIL DRAWINGS AND SITE PLAN
 FOR CONTINUATION OF PLUMBING LINES. SITE PLANS AND
 CIVIL DRAWINGS HAVE NOTE BEEN SUBMITTED WITH THESE
 PLANS. SUBMIT 2 COPIES OF SITE PLANS AND CIVIL
 DRAWINGS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.2ND
 REQUEST.
 2) SHT. A-9 SHOWS THE STANDARD TOILET STALL AS 5 FT. IN
 LENGTH AND SHT.ADA-1 SHOWS THE LENGTH AS 6 FT. 2 INCHES
 IN LENGTH. CLARIFY.
 3) SHT. EQ-1 SUBMIT DETAILS FOR THE GREASE CONTAINER
 REFERENCED BETWEEN GRID LINES #9 & #10. SUBMIT DETAILS
 FOR FASTENING, ETC. ONLY ONE SHEET FOR THIS CONTAINER
 HAS BEEN SUBMITTED AND IT IS BASICALLY A COVER SHEET
 THAT GIVES VERY LITTLE INFORMATION.WPB AMEND.TO 2010
 FBC SEC. 107.2.1.
 4) THE DRINKING FOUNTAINS SHOWN ON THE MEZZANINE LEVEL
 SHALL BE AVAILABLE TO THE PUBLIC FOR USE. IF THE UNITS
 ON THE MEZZANINE LEVEL ARE FOR EMPLOYEES THEN UNITS
 SHALL BE LOCATED ON THE FIRST FLOOR FOR THE PUBLIC.
 THERE SHALL BE A MINIMUM OF TWO DRINKING FOUNTAINS
 SHALL BE REQUIRED PER THE 2010 FL. ACCESSIBILITY CODE
 SEC. 211.1. THE RESPONSE REFERRING TO THE DELI COUNTER
 SODA FOUNTAIN DISPENSING WATER IS INADEQUATE AND DOES
 NOT COMPLY WITH THE ACCESSIBILITY CODE.
 5) THE LETTER FROM THOMAS ENGINEERING BY BRANDON ULMER
 SHALL BEAR A WET SIGNATURE IN ACCORDANCE WITH FL.
 ADMIN. CODE RULE 61G15-23.002.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-10-16 Cont ID  
Sent By tklarge Date 2014-10-16 Time 09:07 Rev Time 0.00
Received By tklarge Date 2014-10-06 Time 04:46 Sent To  
Notes
2014-10-15 14:26:031) PLANS SUBMITTED SHOW TWO DIFFERENT SETS OF PLANS-ONE
 HAS HEADING OF SUPPLEMENTAL DRAWINGS BUT ARE FROM A
 DIFFERENT ARCHITECT. PROVIDE COMPLIANCE W/ FL, ADMIN.
 CODE RULE 61G1-23.015.
 2) THE PLANS FROM PUBLIX DESIGN DEPARTMENT REFER TO
 CIVIL DRAWINGS BUT THERE ARE NO CIVIL DRAWINGS IN THE
 SET OF PLANS. SUBMIT A COMPLETE SET OF CIVIL DRAWINGS
 FOR REVIEW.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 3) SHOW THE SQUARE FOOTAGE OF THE CANOPY THAT IS
 DRAINED BY THE 10" X 5" GUTTERS.
 4) SHT. P100 - SUMP PUMP DETAIL - NOTES" REFER TO SLAB
 UNDER DRAINDRAIN DETAIL." THERE IS NO DRAIN DETAIL.
 CLARIFY.
 5) A UNISEX TOILET ROOM IS REQUIRED PER TABLE 403.1
 FOOTNOTE "G" AND 2010 FPC SEC.403.5.
 6) SHT. EQ-1 - SUBMIT DETAILS FOR THE GREASE CONTAINER
 REFERENCED BETWEEN GRID LINES #9 & #10. WPB AMEND. TO
 2010FBC SEC. 107.2.1.
 7) SHT. A-2 - THE SINK IN THE LOUNGE SHALL COMPLY WITH
 THE FL. ACCESSIBILITY CODE SEC.212.
 8) SHT. A-8 - SOME OF THE PLUMBING VENTS APPEAR TO BE
 WITHIN 10 FT. OF AIR INTAKE OPENINGS ON THE ROOF..
 COMPLY W/ FPC SEC.904.5. PLACE A NOTE ON THE PLAN
 STATING THAT THE PLUMBING VENTS THROUGH THE ROOF WILL
 COMPLY W/ SEC.904.5 OF THE FPC.
 9) SHT. A-8 - SOME OF THE INFO & EQUIPMENT APPEARS TO
 BE CUT OFF/ MISSING FROM THE ROOF PLAN. CLARIFY.
 10) SHT A-9 -TOILET ACCESSORY LEGEND - ITEM R18 REFERS
 TO VERTICAL GRAB BAR- GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION PER THE FACBC SEC.609.4.
 11) SHT.A-9 - SHOWS THE STANDARD TOILET STALL IN THE
 WOMEN'S RESTROOM AS 34 1/8 INCHES WIDE AND 5 FT. IN
 LENGTH AND SHT. ADA-1 SHOWS THE STALL AS 3 FT. WIDE AND
 6 FT.2 INCHES IN LENGTH. CLARIFY.
 12) SHT.P-1 - DRAWING NOTES - #30 - STATES THE GAS LINE
 TO THE STANDBY GENERATOR TO BE 1 1/2 " BUT THE PLAAN
 APPEARS TO SHOW 2". CLARIFY.
 13) SHT. P-1- PLUMBING DESIGN DATA - EMERGENCY
 GENERATOR GAS LINE SIZING - SHOWS THE PIPE LENGTHAS 20
 FT.BUT 12 FT. IS USED IN THE EQUATION. CLARIFY.
 14) SUBMIT MANUFACTURER SPECIFICATIONS FOR THE
 GENERATORS. GENERATORS SHALL COMPLY WITH NFPA 37 AND
 MEET THE REQUIREMENTS OF UL 2200. WPB AMEND. TO 2010
 FBC SEC.,107.2.1.
 15) SHT.P-2 - FIXTURE P-23 IS SHOWN ON THE FLOOR PLAN
 BUT NOT ON THE RISER DIAGRAM.
 16) SHT. P-2 - FIXTURE P-18 IS SHOWN ON SHT.P-1 BUT NOT
 ON THE RISER ON SHT. P-2.
 17) SUBMIT MANUF. SPEC SHEETS FOR THE STANCOR OIL
 MINDER PUMP. WPB AMEND.TO 2010 FBC SEC.107.2.1.
 18) SHT. P-3 - SHOWS CONDENSATE DRAINING INTO THE
 GREASY WASTE SYSTEM. WASTES THAT DO NOT REQUIRE
 TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO
 ANY SEPARATOR OR INTERCEPTOR. 2010 FPC SEC.1003.2. SEE
 CONDENSATES IN MEAT & DELI DEPARTMENTS.
 19) SHT.P-4 - GROUND FLOOR BATHROOMS SHOWS THE
 CLEANOUTS FOR THE STACKS TURNED INTO THE MEAT COOLER.
 IS THIS CORRECT? CLARIFY.
 20) SHT. P-4 - THE VENT FROM THE FIRST FLOOR RESTROOMS
 IS 3" THEN REDUCES TO 2" AT THE VENT CONNECTION W/
 FIXTURE P-5.CLARIFY.
 21) SHT. P-4 - THE VENT FROM FIXTURE P-5 IN THE WOMEN'S
 RESTROOM IS SHOWN AS 2" THEN INCREASES TO 3". CLARIFY.
 22) SHT. P-4 - SIZE THE DRAIN LINE FOR FIXTURE P-5 IN
 THE MEN'S RESTROOM.
 23) SHT.P-4 - SHOWS THE CONDENSATE FROM AH-2 DRAINING
 INTO THE GREASY WASTE. WASTES THAT DO NOT REQUIRE
 TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED INTO
 ANY SEPARATOR OR INTERCEPTOR. 2010 FPC SEC.1003.2.
 24) SHT. P-6 - DETAIL #5 - THE DESIGN OF THE
 INTERCEPTOR DOES NOT COMPLY W/ SEC.1003.5.2 OF THE 2010
 FPC. THE INLET INVERT SHALL DISCHARGE A MINIMUM OF 2
 1/2 " ABOVE THE LIQUID LEVEL LINE AND THE INLET AND
 OUTLET PIPING SHALL BE A MIN. OF 4" IN DIAMETER.
 25) THE DRINKING FOUNTAINS SHALL BE AVAILABLE TO PUBLIC
 FOR USE. A MINIMUM OF 2 DRINKING FOUNTAINS SHALL BE
 INSTALLED ON THE FIRST FLOOR FOR CUSTOMERS IN
 ACCORDANCE WITH THE 2010 FL. ACCESSIBILITY CODE
 SEC.211.2
 26) SHT. P-3 - GREASE INTERCEPTOR SIZING - THE SIZING
 CRITERIA SHOWN ON THE PLANS IS FOR HYDRO-MECHANICAL
 TYPE INTERCEPTORS. DETAIL #5 ON SHT.P-6 SHOWS A
 CONCRETE VAULT GRAVITY INTERCEPTOR. YOU CANNOT USE THE
 CRITERIA FOR A HYDRO-MECHANICAL UNIT TO SIZE A GRAVITY
 TYPE INTERCEPTOR. THE FORMULAS IN TABLE 1003.5.1 MUST
 BE USED FOR THE GRAVITY INTERCEPTOR. REFER TO 2010 FPC
 SEC.1003.5.1.

Review Stop Z ZONING
Rev No 3 Status P Date 2015-01-30 Cont ID  
Sent By llouie Date 2015-01-30 Time   Rev Time 0.00
Received By llouie Date 2015-01-30 Time   Sent To  
Notes
2015-01-30 13:57:39ART IN PUBLIC PLACES REQUIREMENT:
  
 PURSUANT TO THE ART IN PUBLIC PLACES ORDINANCE NO.
 4504-14, AN ART ASSESSMENT FOR THE PROJECT IS REQUIRED
 SINCE THE VALUE OF NEW BUILDING CONSTRUCTION
 ($1,950,000) EXCEED THE VALUE OF $500,000. THE
 APPLICANT SHALL COMPLETE ONE OF THE FOLLOWING WITHIN
 NINETY (90) DAYS OF THE ISSUANCE OF THE FIRST BUILDING
 PERMIT:
  
 OPTION 1: SUBMIT DOCUMENTATION EVIDENCING THE ESCROW OF
 FUNDS FOR A WORK OF ART OR HISTORIC OR CULTURAL
 ELEMENTS VALUED IN AN AMOUNT OF ONE PERCENT OF THE
 TOTAL VERTICAL CONSTRUCTION COSTS IN COMPLIANCE WITH
 ORDINANCE NO. 4504-14 AND SUBMIT AN APPLICATION FOR
 APPROVAL OF THE WORK OF ART OR HISTORIC OR CULTURAL
 ELEMENTS.
  
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO ONE PERCENT OF
 THE TOTAL VERTICAL CONSTRUCTION COSTS FOR DEPOSIT TO
 THE ART IN PUBLIC PLACES FUND.
  
 *** UNLESS AN ALTERNATIVE DEADLINE IS ESTABLISHED IN A
 DEVELOPMENT ORDER, OR A TIME EXTENSION IS GRANTED BY
 THE DIRECTOR OF DEVELOPMENT SERVICES, NO CERTIFICATE OF
 OCCUPANCY FOR THE PROJECT SHALL BE ISSUED UNTIL THE
 ARTWORK IS INSTALLED, THE FINAL REVISED CONSTRUCTION
 COST AFFIDAVIT AND ACCOUNTING OF THE ESCROWED ART FUNDS
 HAS BEEN PROVIDED; AND/OR THE FULL ART ASSESSMENT HAS
 BEEN PAID TO THE CITY. ***
  
 APPLICATION AND ZONING NOTE ATTACHED TO PLANS. LINDA
 LOUIE SPOKE TO ALEKS BOSOY, PROJECT ARCHITECT ON 12/23
 REGARDING AIPP REQUIREMENT. MR. BOSOY WILL RELAY
 MESSAGE TO LEE JOHNSON, DIRECTOR OF CONSTRUCTION FOR
 KIMCO. EMAIL WITH APPLICATION AND AIPP ORDINANCE SENT
 AND RECEIVED BY MR. BOSOY AND MR. JOHNSON ON 10/17/14.
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE
 ARE QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-12-23 Cont ID  
Sent By llouie Date 2014-12-23 Time 10:03 Rev Time 0.00
Received By llouie Date 2014-12-23 Time 10:03 Sent To  
Notes
2014-12-23 10:04:27ART IN PUBLIC PLACES REQUIREMENT:
  
 PURSUANT TO THE ART IN PUBLIC PLACES ORDINANCE NO.
 4504-14, AN ART ASSESSMENT FOR THE PROJECT IS REQUIRED
 SINCE THE VALUE OF NEW BUILDING CONSTRUCTION
 ($1,950,000) EXCEED THE VALUE OF $500,000. THE
 APPLICANT SHALL COMPLETE ONE OF THE FOLLOWING WITHIN
 NINETY (90) DAYS OF THE ISSUANCE OF THE FIRST BUILDING
 PERMIT:
  
 OPTION 1: SUBMIT DOCUMENTATION EVIDENCING THE ESCROW OF
 FUNDS FOR A WORK OF ART OR HISTORIC OR CULTURAL
 ELEMENTS VALUED IN AN AMOUNT OF ONE PERCENT OF THE
 TOTAL VERTICAL CONSTRUCTION COSTS IN COMPLIANCE WITH
 ORDINANCE NO. 4504-14 AND SUBMIT AN APPLICATION FOR
 APPROVAL OF THE WORK OF ART OR HISTORIC OR CULTURAL
 ELEMENTS.
  
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO ONE PERCENT OF
 THE TOTAL VERTICAL CONSTRUCTION COSTS FOR DEPOSIT TO
 THE ART IN PUBLIC PLACES FUND.
  
 *** UNLESS AN ALTERNATIVE DEADLINE IS ESTABLISHED IN A
 DEVELOPMENT ORDER, OR A TIME EXTENSION IS GRANTED BY
 THE DIRECTOR OF DEVELOPMENT SERVICES, NO CERTIFICATE OF
 OCCUPANCY FOR THE PROJECT SHALL BE ISSUED UNTIL THE
 ARTWORK IS INSTALLED, THE FINAL REVISED CONSTRUCTION
 COST AFFIDAVIT AND ACCOUNTING OF THE ESCROWED ART FUNDS
 HAS BEEN PROVIDED; AND/OR THE FULL ART ASSESSMENT HAS
 BEEN PAID TO THE CITY. ***
  
 APPLICATION AND ZONING NOTE ATTACHED TO PLANS. LINDA
 LOUIE SPOKE TO ALEKS BOSOY, PROJECT ARCHITECT ON 12/23
 REGARDING AIPP REQUIREMENT. MR. BOSOY WILL RELAY
 MESSAGE TO LEE JOHNSON, DIRECTOR OF CONSTRUCTION FOR
 KIMCO. EMAIL WITH APPLICATION AND AIPP ORDINANCE SENT
 AND RECEIVED BY MR. BOSOY AND MR. JOHNSON ON 10/17/14.
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE
 ARE QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-10-09 Cont ID  
Sent By llouie Date 2014-10-09 Time 17:11 Rev Time 0.00
Received By llouie Date 2014-10-09 Time 17:11 Sent To  
Notes
2014-10-09 17:11:43** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) PLAN SET NOT COMPLETE. NEED TO SEE EXTERIOR SITE
 IMPROVEMENTS/PLAN AND ASSOCIATED CALCULATIONS PER THE
 APPROVED SITE PLAN. (REFERENCE: ISPR14-01/Z14030044)
  
 2.) THE VALUE OF NEW BUILDING CONSTRUCTION ON THE
 PROJECT SITE ($1,950,000) IS GREATER THAN $500,000.
 PURSUANT TO THE ART IN PUBLIC PLACES ORDINANCE
 (ORDINANCE NO. 4504-14), AN ART ASSESSMENT FOR THE
 PROJECT IS REQUIRED. PLEASE COMPLETE THE ART IN PUBLIC
 PLACES ORDINANCE FORM IN THE DEVELOPMENT SERVICES -
 CONSTRUCTION SERVICES DEPARTMENT OR CONTACT LINDA
 LOUIE, PLANNER, FOR MORE INFORMATION.
  
 PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS
 MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE
 @ (561) 822-1458 IF YOU HAVE QUESTIONS.
  