| 2014-09-17 18:54:07 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2010 |
| | |
| | TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED |
| | |
| | PLEASE SEE LAST NOTE REGARDING MY CONTACT WITH THE |
| | MANUFACTURER SENT 8AM ON 9/18/2014. ALTHOUGH IT IS THE |
| | CONTRACTOR'S RESPONSIBILITY TO PROVIDE DOCUMENTS TO |
| | DEMONSTRATE CODE COMPLIANCE, I HAVE REQUESTED THESE |
| | DOCUMENTS FROM THE MANUFACTURER. IF THEY PROVIDE THEM |
| | TO ME, I WILL EMAIL TO YOU FOR RESUBMITTAL. |
| | |
| | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| | NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| | BELOW WILL NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E 84 OR UL 723. |
| | |
| | 4. THE MANUFACTURER WAS CONTACTED IN AN ATTEMPT TO |
| | OBTAIN THE REQUIRED DOCUMENTS FOR YOU. ON THEIR WEBSITE |
| | (WWW.PROFLEX.US/WORDPRESS/CONTACT/) I PLACED THE |
| | FOLLOWING MESSAGE TO TECHNICAL SUPPORT: |
| | |
| | A CONTRACTOR HAS APPLIED FOR A PERMIT USING PROFLEX |
| | CISM 40 MIL. AS THIS APPLICATION IS IN A HIGH RISE (NON |
| | COMBUSTIBLE CONSTRUCTION) RESIDENTIAL CONDOMINIUM, |
| | PLEASE EMAIL THE THREE TEST RESULTS TO ME AS DESCRIBED |
| | BELOW. IF THEY ARE NOT AVAILABLE, PLEASE ADVISE. IF THE |
| | TESTRESULTS ARE CURRENTLY UNAVAILABLE BUT YOU ARE |
| | WILLING TO COMMIT IN WRITING TO HAVING THE TEST |
| | PERFORMED AND CAN EXPLAIN WHY YOU HAVE A REASONABLE |
| | EXPECTATION THAT THE TEST WILL PASS (COMPLY WITH THE |
| | MINIMUM REQUIREMENTS OF THE FBC/IBC), I WILL ISSUE THE |
| | PERMIT BASED ON THE COMMITMENT LETTER. PLEASE NOTE THAT |
| | ALL THREE REQUIREMENTS CAN ALSO BE FOUND IN THE IBC |
| | (THE BASE CODE), WHICH MAKES THIS A NATIONAL |
| | REQUIREMENT FOR ANY STATE/JURISDICTION WHICH HAS |
| | ADOPTED THE IBC (NOT A FLORIDA SPECIFIC REQUIREMENT). |
| | |
| | COMMENTS 1 - 3 WERE SENT TO THE MANUFACTURER. |
| | |
| | |
| | |
| | |
| | |