Plan Review Details - Permit 14090616
Plan Review Stops For Permit 14090616
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-25 Cont ID  
Sent By shill Date 2014-09-25 Time 18:41 Rev Time 0.00
Received By shill Date 2014-09-24 Time 18:41 Sent To FIRE
Notes
2014-09-25 10:05:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, SCOPE OF THIS REVISION IS NOT CLEAR. THIS
 APPEARS TO BE THE SAME PLAN THAT WAS SUBMITTED FOR
 PERMIT UNDER THE MASTER. THE SCOPE OF THE MASTER
 PERMIT, 13100744, WAS "DEMO OF INTERIOR NON BEARING
 WALLS, DEMO OF BUILT IN FURNITURE."
  
 THE SCOPE OF THIS REVISION IS "REMOVAL OF INTERIOR
 WALL."
  
 WHEN CHANGES ARE DONE TO A PLAN, THE DESIGN
 PROFESSIONAL IS TO CLOUD ALL CHANGES. THE SHEET D-1
 SUBMITTED FOR PERMIT HAS A PROJECT NAME OF "A PROPOSED
 INTERIOR DEMOLITION FOR: ROXY'S PUB" AND "PERMIT REVIEW
 SET 10-21-2013."
  
 THE NEW SHEET D-1 HAS A PROJECT NAME OF "STAIR
 REPLACEMENT FOR: SKY 309" AND "PERMIT REVIEW SET
 1-31-2014."
  
 THE TWO PLANS APPEAR VERY SIMILAR, AND NOTHING IS
 CLOUDED TO SHOW WHAT HAS CHANGED. BASED ON WRITTEN
 DESCRIPTIONS OF WORK, THE SCOPE OF WORK FOR THIS
 REVISION HAS ALREADY BEEN REVIEWED AND ISSUED (DEMO OF
 INTERIOR WALLS, BUILT IN FURNITURE).
  
 IF CONTRACTOR WISHES TO EXTEND THE SCOPE OF THE PERMIT
 ALREADY ISSUED, REVISE THE PLAN TO DEPICT WORK COVERED
 UNDER THE DEMO PERMIT 13100744 AND INDICATE WORK TO BE
 COVERED UNDER THE REVISION.
  
 2. PER CONVERSATION WITH OWNER, STAIR DEMO IS NOT
 INCLUDED IN THE SCOPE OF THIS PERMIT. PER OUR ISSUED
 PERMIT, SCOPE OF ORIGINAL PERMIT IS LIMITED TO THE
 PERMIT DESCRIPTION, ALTHOUGH THE PLAN SHOWS ADDITIONAL
 DEMOLITION. IF IT IS DETERMINED THAT A REVISION IS
 REQUIRED, THIS REVISION WILL BE ISSUED WITH PROVISO.
  
 3. VALUE FOR THIS REVISION IS $0. IF SCOPE IS
 INCREASED, PLEASE INCLUDE VALUE OF ADDITIONAL WORK, FBC
 109.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-10-02 Cont ID  
Sent By dhayes Date 2014-10-02 Time 09:22 Rev Time 0.00
Received By dhayes Date 2014-10-02 Time 09:22 Sent To  
Notes
2014-10-02 09:27:3910/2/2014
 PROJECT: SKY 390
 PERMIT#: 13100744, REVISION #14090616
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) NOTE "F" ALL ELETRICAL ITEMS THAT ARE TO BE CAPPED
 AND ABEANDONNED SHALL NOT BE CAPPED OR ABBANDONNED
 BEHINED FINAL FINISHES AND SHALL REMAIN ACCESSABLE AND
 NOT "TOTALLY CONCEALED"
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-09-30 Cont ID  
Sent By shill Date 2014-09-30 Time   Rev Time 0.00
Received By pleduc Date 2014-09-30 Time 11:38 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-10-02 Cont ID  
Sent By dhayes Date 2014-10-02 Time 09:28 Rev Time 0.00
Received By dhayes Date 2014-09-17 Time 15:18 Sent To  
Notes
2014-09-19 15:18:54TO SH DESK
  