| 2014-09-26 07:29:22 | BUILDING PLAN REVIEW |
| | PERMIT: 14090548 |
| | ADD: 529 S FLAGLER DR. # 10-E |
| | CONT: CAMBRDGE CONSTRUCTION |
| | TEL: (561)784-3722 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. SEPT. 26/ 2014 |
| | ACTION: BUILDING PROVISO |
| | |
| | 1) NEW WALK IN SHOWER ENCLOSURE MUST COMPLY WITH: |
| | 2010 FBC-B 2509.2 BASE FOR TILE. |
| | GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| | DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| | SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT |
| | SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 |
| | OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| | RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| | SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| | REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| | WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| | |
| | 2509.3 LIMITATIONS. |
| | WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED |
| | IN THE FOLLOWING LOCATIONS: |
| | 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| | AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| | (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| | INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD. |
| | |