| 2014-09-22 16:16:12 | TO MISC. 2 |
| | |
| | |
| 2014-09-22 15:54:46 | DATE: 9/22/2014 |
| | PROJECT: FOREVER 21 SIGN |
| | PERMIT#: 14090501 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) NEC 600.6(A)(1)DISCONNECTS. |
| | EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER |
| | CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE |
| | LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY |
| | OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL |
| | UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN OR |
| | OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. |
| | |
| | 2) FBC-E 505.2.4 ENERGY |
| | ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| | HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| | NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| | CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| | SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| | OF POWER FOR A MINIMUM OF 10 HOURS. |
| | |
| | 3) WPB AMENDMENTS TO THE FBC SECTION 109.3 VALUATION. |
| | THE CLAIMED VALUATION OF THE, ALTERATION, APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION.THE BUILDING OFFICIAL |
| | SHALL RESERVE THE RIGHT TO DENY THE PERMIT. THE |
| | APPLICANT HAS THE RIGHT TO SHOW DETAILED, QUANTITY |
| | ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING |
| | LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING |
| | OFFICIAL. |
| | FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN |
| | FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING |
| | ONLY LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE |
| | LATEST PUBLISHED DATA OF NATIONAL CONSTRUCTION COST |
| | ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS |
| | PUBLISHED BY INTERNATIONAL CODE CONGRESS. FINAL |
| | BUILDING PERMIT VALUATION SHALL BE SET BY THE BUILDING |
| | OFFICIAL. FBC WPB AMENDMENTS. SECTION 109.3 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |