| Plan Review Stops For Permit 14090427 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2014-11-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-11-07 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-11-07 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2014-09-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2014-09-25 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2014-09-25 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2014-09-25 13:54:49 | BUILDING PLAN REVIEW | | | REVISION: 14090427/ 14021079 | | | PERMIT: 12030240 | | | ADD: 6701 N JOG RD. | | | CONT: | | | TEL: (561 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: THURS. SEPT. 25/2014 | | | ACTION: DENIED | | | | | | 1) SHEET A5-100 INDICATES THIS TO BE REVISION # 5. THE | | | REVISION SHOWS A RECONFIGURATION OF THE BREAK ROOM AND | | | NEW RESTROOM BEING ADDED REDUCING THE SIZE OF THE BREAK | | | ROOM. NOTE NO PLUMBING SHEETS WERE SUBMITED UNDER THIS | | | REVIEW. THE REVISION BEFORE 24021079 THIS | | | RECONFIGURATION HADN'T OCCURED. 107.2.1.3 ADDITIONAL | | | INFORMATION IS REQUIRED. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-01-26 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2015-01-26 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-01-26 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-11-12 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-11-12 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-11-12 |
Time |
16:29 |
Sent To |
|
|
| Notes |
| 2014-11-12 16:50:22 | 11/12/2014 | | | PROJECT: SWA WAREHOUSE BUILDING | | | PERMIT#: 14090427 | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) CLARIFY CIRCUITRY FEEDING NEW EMERGENCY EXIT LIGHTS. | | | THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL BE | | | THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL | | | SWITCHES. NEC 70012.(F) | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2014-09-25 |
|
|
Cont ID |
|
| Sent By |
dhayes |
Date |
2014-09-25 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2014-09-25 |
Time |
16:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2014-10-31 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-10-31 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-10-31 |
Time |
13:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2014-10-01 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2014-10-01 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2014-09-30 |
Time |
14:55 |
Sent To |
|
|
| Notes |
| 2014-09-30 15:43:30 | 6701 NORTH JOG ROAD - MAINTENANCE BUILDING | | | PERMIT #14090427 | | | RACK #14080063 | | | MASTER #12030240 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | COULD NOT LOCATE PORTABLE FIRE EXTINGUISHERS ON MAIN | | | FLOOR OR MEZZANINE LEVEL. TRAVEL DISTANCE TO | | | EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | SEVERAL EMERGENCY LIGHT FIXTURES HAVE BEEN ADDED AROUND | | | THE BUILDING INTERIOR PERIMETER; HOWEVER, NO DEVICS | | | HAVE BEEN ADDED AT/BELOW THE MEZZANINE OR THE AISLES | | | BETWEEN THE HIGH-PILED (18.5 FEET) STORAGE RACKS. | | | EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO | | | PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN | | | AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN | | | 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT | | | FLOOR LEVEL. | | | | | | ADDITIONAL ILLUMINATED EXIT SIGNS ARE NEEDED TO | | | ACCOMODATE THE VISUAL OBSTRUCTIONS CREATED BY THE | | | MEZZANINE AND HIGH-PILED STORAGE RACKS. | | | | | | SEPARATE PLANS AND PERMIT NEEDED FOR PAINT SPRAY BOOTH. | | | | | | A REQUEST FOR TCO HAS BEEN INDICATED; HOWEVER, THE | | | PLANS INDICATE A REVISION TO THE BREAKROOM AND RESTROOM | | | AREAS. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-01-26 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2015-01-26 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2014-12-22 |
Time |
19:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-12-22 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2014-11-12 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2014-10-14 |
Time |
13:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2014-10-01 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2014-09-25 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2014-09-23 |
Time |
10:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2015-02-06 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-02-06 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-02-06 |
Time |
16:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2015-01-28 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2015-01-28 |
Time |
10:16 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2015-01-28 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2015-01-28 10:16:48 | WRONG SIGNATURE REPORT SUBMITTED. |
|
|