Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-10-16 Cont ID  
Sent By jwitmer Date 2014-10-16 Time 09:29 Rev Time 0.00
Received By jwitmer Date 2014-10-16 Time 08:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-09-19 Cont ID  
Sent By jwitmer Date 2014-09-19 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2014-09-19 Time 13:55 Sent To  
Notes
2014-09-19 14:19:56BUILDING PLAN REVIEW
 PERMIT: 14090381
 ADD: 1703 PALM BEACH LAKES SUITE # B01
 CONT: TBD
 TEL: (561)348- 4805
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. SEPT. 19/2014
 ACTION: DENIED
  
 1) THE COVERSHEET INDICATES THE OCCUPANT LOAD AS PARTS
 OF OCCUPANTS. OCCUPANT LOADS ARE ALWAYS ROUNDED UP TO
 THE NEXT WHOLE PERSON.
 SEE BOAF INFORMAL INTERPRETATION # 5479
 DATE: TUE DEC 18 2007
 REPORT #: 5479
 CODE: BUILDING
 SECTION: 1004.1.2
 QUESTION:
 IS IT THE INTENT OF SECTION 1004.1.2 TO ALLOW THE
 LARGEST NUMBER COMPUTED IN ACCORDANCE WITH
 TABLE 1004.1.2 TO BE ROUNDED TO THE NEAREST WHOLE
 NUMBER? COMMENT: FOR EXAMPLE, A
 BUSINESS OCCUPANCY IN A BUILDING WITH 3215 GROSS SQUARE
 FEET, CALCULATED OCCUPANCY LOAD
 WOULD BE 32.15 WOULD I ROUND DOWN TO 32 OCCUPANTS OR
 WOULD I BE REQUIRED TO ROUND UP TO
 33 OCCUPANTS
 ANSWER:
 ROUND UP TO 33
 COMMENTARY:
 OCCUPANTS ONLY COME AS A WHOLE.
  
 2) THE REQUIRED EGRESS WIDTH WILL ALSO NEED TO BE
 UPDATED. 2010 FBC-B 1005.1.
  
 3) SHEET A3.3 DOES NOT GIVE THE DIMENSIONS FOR THE
 RESTROOM ACCESSIBLE FIXTURES NOR GRAB BARS NOR BACKING
 REQUIREMENTS FOR THE GRAB BARS.
 2010 FL ACCESS. CODE 604.2, 606.3, 604.5.1 & 604.5.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-09-23 Cont ID  
Sent By rlecky Date 2014-09-23 Time 11:46 Rev Time 0.00
Received By rlecky Date 2014-09-23 Time 10:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-09-15 Cont ID  
Sent By scaldero Date 2014-09-15 Time 16:49 Rev Time 0.00
Received By scaldero Date 2014-09-15 Time 16:49 Sent To  
Notes
2014-09-15 16:58:27PERMIT # 14090381
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 EVERY TENANT SPACE SHALL BE TIED INTO THE FIRE ALARM
 SYSTEM FOR THE BUILDING.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-10-18 Cont ID  
Sent By tklarge Date 2014-10-18 Time 07:19 Rev Time 0.00
Received By tklarge Date 2014-10-10 Time 14:07 Sent To  
Notes
2014-10-10 14:07:20INCOMING SENT TO B-17 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-09-26 Cont ID  
Sent By tklarge Date 2014-09-26 Time 14:04 Rev Time 0.00
Received By tklarge Date 2014-09-11 Time 07:37 Sent To  
Notes
2014-09-12 07:47:18B09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-09-19 Cont ID  
Sent By jwitmer Date 2014-09-19 Time 13:56 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-09-26 Cont ID  
Sent By rbergsma Date 2014-09-26 Time   Rev Time 0.50
Received By rbergsma Date   Time   Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-10-18 Cont ID  
Sent By tklarge Date 2014-10-18 Time 07:19 Rev Time 0.00
Received By tklarge Date 2014-10-18 Time 07:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-09-26 Cont ID  
Sent By tklarge Date 2014-09-26 Time 14:04 Rev Time 0.00
Received By tklarge Date 2014-09-26 Time 14:03 Sent To  
Notes
2014-09-26 14:03:531) SHT. AG- ACCESSIBILITY GUIDELINES - CHAPTER 6
 GUIDELINES - WATER CLOSETS AND LAVATORY CLEARANCES
 DETAILS SHOW VERTICAL GRAB BARS. GRABS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION PER FL. ACCESS. CODE
 SEC.609.4. VERTICAL GRAB BARS ARE NOT PERMITTED. ALSO,
 SEE SHEETS A3.3 (R.R. ELEVATIONS)
 2) TOILET PAPER DISPENSERS SHALL BE 7"MINIMUM AND 9"
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER AND 15' MINIMUM AND 48"
 MAXIMUM ABOVE THE FINISHED FLOOR AND NOT BE LOCATED
 BEHIND GRAB BARS PER THE FAC SEC.604.7.
 3) SUBMIT A WATER AND SANITARY RISER DIAGRAM THAT
 REFLECTS THE SCOPE OF WORK TO BE DONE PER SEC.
 107.3.5.1.3 OF THE 2010 WPB AMENDMENTS TO THE 2010 FBC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2014-09-25 Cont ID  
Sent By eschneid Date 2014-09-25 Time 13:47 Rev Time 0.50
Received By eschneid Date 2014-09-25 Time 13:47 Sent To  
Notes